![Faraday RSE-300 Owner'S Manual Download Page 49](http://html1.mh-extra.com/html/faraday/rse-300/rse-300_owners-manual_3409721049.webp)
15073 OWNER’S MANUAL
447179 Issue 1 Rev. A
42
7.2.4
Four-Wire (Separately Powered) Smoke and Heat
Detectors
Faraday
Detector
w/Base
Mfg. Detector w/Base
Maximum
Standby
Current
Maximum
Alarm
Current
Notes
Air Products & Controls
9269
RW-DC-N
0.081m
115mA
Must use EOL Relay
9270
RW-DC-P
0.110m
115mA
Must use EOL Relay
Apollo Fire Detectors
9260 w/9266 55000-350 w/45681-227
0.130m
100mA
Must use EOL Relay
9261 w/9266 55000-250 w/45681-227
0.081m
100mA
Must use EOL Relay
9264 w/9266 55000-153 w/45681-227
0.086m
100mA
Must use EOL Relay
9274 w/9266 55000-152 w/45681-227
0.096m
100mA
Must use EOL Relay
9259 w/9266 55000-150 w/45681-227
0.086m
100mA
Must use EOL Relay
9221 w/9266 55000-151 w/45681-227
0.086m
100mA
Must use EOL Relay
9222 w/9266 55000-380 w/45681-227
0.205m
100mA
Must use EOL Relay
System Sensor
9337
1112/24
0.050mA
25mA
Must use EOL Relay
9338
2112/24
0.050mA
25mA
Must use EOL Relay
9339
2112/24T
0.050mA
25mA
Must use EOL Relay
9340
2112/24TSRB
15mA
45mA
Must use EOL Relay
9358 w/9362 1451 w/B402B
0.120mA
36mA
Must use EOL Relay
9359 w/9362 2451 w/B402B
0.120mA
36mA
Must use EOL Relay
9360 w/9362 2451TH w/B402B
0.120mA
36mA
Must use EOL Relay
9447 w/9362 5451 w/B402B
0.120mA
36mA
Must use EOL Relay
9421 w/9362 4451HT w/B402B
0.120mA
36mA
Must use EOL Relay
9183 w/9186 2151 w/B112LP
0.120mA
36mA
Must use EOL Relay
9184 w/9186 1151 w/B112LP
0.120mA
36mA
Must use EOL Relay
Notes:
1. For specific wiring and installation information, read the instructions provided with each device.
2. Each 9273 EOL Relay requires 15 mA. standby current.
firealarmresources.com