Faraday 8840 Installation/Wiring Instructions Download Page 5

5

Sampling Tube Selection

There are four standard lengths of inlet sampling tubes. To ensure accurate
air sampling, select the appropriate length and determine the outside width of
the duct. Select the sampling tube nearest to, but greater than, the duct width
(Table 2). The outlet sampling tube for all ducts is a fixed length of 4 inches
(10.1 cm). Trim the inlet sampling tube at the job site as described below.

TABLE 2

SAMPLING TUBE SELECTION CHART

Sampling Tube

Standard

Outside Duct Width

Model No.

      Tube Length

1 ft 9

3

/

4

 in or less

8932

2 ft

1 ft 9

3

/

4

 in - 3 ft 3

3

/

4

 in

8933

3 ft 6 in

3 ft 3

3

/

4

 in - 6 ft 3

3

/

4

 in or less

8934

6 ft 6 in

6 ft 3

3

/

4

 in - 9 ft 9

3

/

4

 in or less

8935

10 ft

Greater than 9 ft 9

3

/

4

 in

Consult factory

Note: Each model is manufactured with a different number and size of

sampling hole. Only the specific tube must be used for the specified
duct width.

Figure 4

Sampling Tube Orientation

firealarmresources.com

Summary of Contents for 8840

Page 1: ...0 TECHNICAL DATA TABLE 1 AIR DUCT CONDITIONS Temperature Range 32O F 0O C 100O F 38O C per UL 268 268A Altitude Range 8840 and 8839 No altitude limitations Relative Humidity Range 0 93 non condensatin...

Page 2: ...overcome the limitations of spot type smoke and heat detec tors in the duct However since stratification can occur in the air stream after a long duct run locate the detector after bends or inlets whi...

Page 3: ...the back of the detector housing 2 so that the larger hole on the gasket lines up with the sam pling tube hole on the sampling chamber and the smaller hole lines up with the housing mounting hole b Af...

Page 4: ...4 Figure 3 Exploded View firealarmresources com...

Page 5: ...pling tube at the job site as described below TABLE 2 SAMPLING TUBE SELECTION CHART Sampling Tube Standard Outside Duct Width Model No Tube Length 1 ft 93 4 in or less 8932 2 ft 1 ft 93 4 in 3 ft 33 4...

Page 6: ...he inlet tube 3 by inserting it through the air sampling chamber as shown in Figure 3 Face sampling tube holes into the air stream Figure 4 and secure to the housing with 8 32 screws 12 d Install the...

Page 7: ...7 Figure 5 Typical Connections for the 8840 8839 firealarmresources com...

Page 8: ...nd local codes 3 Refer to the 8717 Installation Instructions P N 315 033280FA 4 Refer to the 8727W 8727C Installation Instructions P N 315 033230FA TB 1 TB 2 TB 3 4 3 2 1 5 5 6 7 8 9 10 11 5 5 6 7 8 9...

Page 9: ...nected to the base or air duct hous ing that were compatible with the old detector may not be compatible with the new detector Always read the Installation Instructions accompanying the detector to de...

Page 10: ...n snugly but not so tightly as to warp the cover and cause air leakage around the edges of the cover LED Indicator Operation The 8840 contains an LED indicator capable of flashing either one of three...

Page 11: ...impaired It is recommended that the sam pling tubes be checked and cleaned periodically The detector mainte nance program should consist of periodic cleaning of dust from the detec tor head by using...

Page 12: ...LW 400 P N 315 092430FA 4 LWZE 4A LW 401 P N 315 096018FA 2 8840 USING 8710 DETECTOR Equipment Installation Wiring Compatibility Identifier Instructions MPC 6000 P N 315 447309 1 The detector model nu...

Reviews: