Faraday 8840 Installation/Wiring Instructions Download Page 1

INTRODUCTION

Faraday Detector Models 8840 and 8839 are System LW-400, System
LW-401, System LW-450, System LW-500 and MPC-600 compatible air
duct detectors. They are designed for use in heating, ventilating, and air
conditioning duct systems to detect the presence of combustion products
in a duct system. (Refer to TECHNICAL DATA below for air duct operating
conditions.)

When smoke or combustion products are detected, shutdown of the duct
system and/or operation of supplementary equipment is provided by the
related system control panel with the 8840.

TECHNICAL DATA

TABLE 1

AIR DUCT CONDITIONS

Temperature Range: 32

O

F (0

O

C) - 100

O

F (38

O

C) per UL 268/268A

Altitude Range: 8840 and 8839 — No altitude limitations

Relative Humidity Range: 0-93% (non-condensating) per UL 268-268A

Air Duct Velocity Range: 300-4000 ft/min – 8840 and 8839

Sampling Tube Pressure Range of Differences:

.01-1.0 inches of water column

CAUTION: These air duct detectors are designed for detection and con-

trol of products of combustion in a duct system. They are not
to be used for open area protection.

DO NOT USE air duct detectors with Alarm Verification.

INSTALLATION/WIRING INSTRUCTIONS

AIR DUCT DETECTOR

Models 8840 AND 8839*

FARADAY

*See Compatible Control Equipment Table on the last page.

P/N 315-095659FA-3

firealarmresources.com

Summary of Contents for 8840

Page 1: ...0 TECHNICAL DATA TABLE 1 AIR DUCT CONDITIONS Temperature Range 32O F 0O C 100O F 38O C per UL 268 268A Altitude Range 8840 and 8839 No altitude limitations Relative Humidity Range 0 93 non condensatin...

Page 2: ...overcome the limitations of spot type smoke and heat detec tors in the duct However since stratification can occur in the air stream after a long duct run locate the detector after bends or inlets whi...

Page 3: ...the back of the detector housing 2 so that the larger hole on the gasket lines up with the sam pling tube hole on the sampling chamber and the smaller hole lines up with the housing mounting hole b Af...

Page 4: ...4 Figure 3 Exploded View firealarmresources com...

Page 5: ...pling tube at the job site as described below TABLE 2 SAMPLING TUBE SELECTION CHART Sampling Tube Standard Outside Duct Width Model No Tube Length 1 ft 93 4 in or less 8932 2 ft 1 ft 93 4 in 3 ft 33 4...

Page 6: ...he inlet tube 3 by inserting it through the air sampling chamber as shown in Figure 3 Face sampling tube holes into the air stream Figure 4 and secure to the housing with 8 32 screws 12 d Install the...

Page 7: ...7 Figure 5 Typical Connections for the 8840 8839 firealarmresources com...

Page 8: ...nd local codes 3 Refer to the 8717 Installation Instructions P N 315 033280FA 4 Refer to the 8727W 8727C Installation Instructions P N 315 033230FA TB 1 TB 2 TB 3 4 3 2 1 5 5 6 7 8 9 10 11 5 5 6 7 8 9...

Page 9: ...nected to the base or air duct hous ing that were compatible with the old detector may not be compatible with the new detector Always read the Installation Instructions accompanying the detector to de...

Page 10: ...n snugly but not so tightly as to warp the cover and cause air leakage around the edges of the cover LED Indicator Operation The 8840 contains an LED indicator capable of flashing either one of three...

Page 11: ...impaired It is recommended that the sam pling tubes be checked and cleaned periodically The detector mainte nance program should consist of periodic cleaning of dust from the detec tor head by using...

Page 12: ...LW 400 P N 315 092430FA 4 LWZE 4A LW 401 P N 315 096018FA 2 8840 USING 8710 DETECTOR Equipment Installation Wiring Compatibility Identifier Instructions MPC 6000 P N 315 447309 1 The detector model nu...