Faraday 8709 Installation Instructions And Wiring Download Page 2

P/N 315-034904FA-3

PAGE 2 OF 2

Figure 3

8709 Wiring Diagram - Style 4 (Class B) Operation

1. All wiring must comply with

national and local codes.

2. In order to provide adequate

protection, it is recom-
mended that you do not
install more than 20 devices
on a single 8709.

3. Wire size:  18 to 14 AWG.
4. The total wire resistance

(both wires) between 8709s
cannot exceed 20 ohms.

5. Do not install more than

fifteen 8709s per Address-
able Device Circuit.

6. All circuits are supervised.
7. Refer to the control unit’s

Owner’s Manual for the list
of compatible devices.

8. All terminals are power

limited

.

LINE 1

LINE 2

SEE CONTROL UNIT OWNER’S MANUAL

FOR COMPATIBLE ADDRESSABLE DEVICES

FROM ADDRESSABLE DEVICE

CIRCUIT OF A COMPATIBLE

CONTROL UNIT OR PREVIOUS

ADDRESSABLE DEVICE

ADDRESSABLE DEVICE CIRCUIT

IN

IN OUT OUT EARTH

IN

IN OUT OUT EARTH

IN

IN OUT OUT EARTH

WIRING

The 8709 is a polarity insensitive module. Refer to Figure 1 for the location of the two input terminals and
two output terminals. Line 1 and Line 2 can be either line of the loop.

The 8709 may be used in two circuit configurations as follows:

Style 4 Operation

(See Figure 3) In Style 4 (Class B) wiring, each 8709 isolates a branch or section of the addressable
device circuit. Note that a short on the main branch causes the entire loop to fail. To prevent this, mount
the 8709s at the control unit enclosure and run each branch independently.

Style 6 Operation

(See Figure 4) In Style 6 (Class A) wiring, the 8709s are wired in series with the addressable device circuit
wiring. This results in a single continuous loop. If any group in the loop has a short, that group is lost and a
Class A circuit failure results.

1. All wiring must comply with

national and local codes.

2. In order to provide adequate

protection, it is recom-
mended that you do not
install more than 20 devices
on a single 8709.

3. Wire size:  18 to 14 AWG.
4. The total wire resistance

(both wires) between 8709s
cannot exceed 20 ohms.

5. Do not install more than

fifteen 8709s per Address-
able Device Circuit.

6. All circuits are supervised.
7. Refer to the control unit’s

Owner’s Manual for the list
of compatible devices.

8. All terminals are power

limited.

SEE CONTROL UNIT OWNER’S MANUAL

FOR COMPATIBLE ADDRESSABLE DEVICES

ADDRESSABLE DEVICE CIRCUIT

TO ADDRESSABLE DEVICE

CIRCUIT IN TERMINALS

TO ADDRESSABLE DEVICE

CIRCUIT OUT TERMINALS

INSIDE ENCLOSURE

LINE 1

LINE 2

LINE 2

LINE 1

IN

IN OUT OUT

IN

IN

OUT

OUT

EARTH

EARTH

IN

IN

OUT

OUT

EARTH

IN

IN

OUT

OUT

EARTH

IN

IN OUT OUT EARTH

IN

IN OUT OUT EARTH

Figure 4

8709 Wiring Diagram - Style 6 (Class A) Operation (Single Loop)

ELECTRICAL RATINGS

The 8709 draws 1mA from the addressable device circuit.