P/N 315-034860FA-4
Page 2 of 2
Accessory Devices
Faraday Cat. No.
Mfg. Part Number
Description
R711-1
711-1
Polarized Auxiliary Relay
RSE 300
15073
Remote Signal Expander
Notes:
1.
The accessory devices listed above may be wired to activate from the notification appliance circuits.
2.
For specific wiring and installation information, read the instructions provided with each device.
Figure 2
8706 Wiring
NOTES:
1.
For a list of compatible notification appliances, refer to P/N 315-096363FA.
2.
Notification Appliance Circuit ratings:
Style Z, Class A or Style Y, Class B
See Installation Instructions for compatible Notification Appliances.
Supervisory current (max.):
30mA max from external supply
1mA max from addressable device circuit wiring
Alarm voltage:
24VDC nominal
Alarm current (max.):
1.5A at 24VDC nominal
NAC cable requirements:
Wire size:
18 to 14 AWG
Voltage drop (max.):
3VDC (from power supply to EOL)
3.
If Earth Ground is available, the green wire should be connected to earth ground terminal (TB2, terminal 6).
4.
If Earth Ground is NOT available, all the NAC wiring should be located in the same room as the module.
5.
The Notification Appliance Circuit polarity is shown in active state.
6.
Power Supply Input Wire Size: 18 to 14 AWG
7.
The following minimum revisions are required for proper operation of the 8706.
FDLC
1.5
NAC
2.18
PANEL
5.0
DC INPUT:
VDC FILTERED
FULL WAVE MODULE INPUT SUPPLY:
MPC-6000/-7000, RSE-300* (TB2) OR
UL LISTED REGULATED 24 VDC
POWER SUPPLY (POWER LIMITED).
18.8-28.2
8706 MODULE IS USED FOR
NAC SUPERVISION AND ACTIVATION
FROM ADDRESSABLE DEVICE CIRCUIT
OF A COMPATIBLE FARADAY
FIRE ALARM CONTROL PANEL OR
PREVIOUS ADDRESSABLE DEVICE
ADDRESSABLE DEVICE CIRCUIT
24VDC NOMINAL, SUPERVISED
LINE 1
LINE 2
GROUND
8706
8706
8706 MODULE IS USED FOR
NAC SUPERVISION AND ACTIVATION
SHIELD
GROUND
24K, 1/2W, 5%
END OF LINE RESISTOR
P/N 140-034677
SHIELD
STYLE Y
SUPERVISED STROBE ACTIVATION “SPECIAL APPLICATION”
SUPV: 1mA
ACTIVATED: 1.5A MAX
18.8V-28.2V FILTERED FULL WAVE RECTIFIED (SEE NOTE 2)
POLARITY SHOWN IN ACTIVE STATE
STYLE Z
24K, 1/2W, 5%
EOL RESISTOR
P/N 140-034677
ALL WIRING MUST COMPLY WITH NATIONAL AND LOCAL CODES.
DC INPUT RATED
18.8-28.2VDC FWR
SUPV: 30mA
ACTIVATED: 1.5A MAX
TB1 ON BACK SIDE
TB2 ON BACK SIDE
6
5
4
3
2
1
6
5
4
3
2
1
1
2
3
4
5
6
1
2
3
4
5
6
PROGRAMMING
POINTS
TB1 ON BACK SIDE
TB2 ON BACK SIDE
PROGRAMMING
POINTS
NOTIFICATION APPLIANCE
CIRCUIT SUPERVISED,
SEE NOTE 2
SUPERVISED
24 VDC
NAC UNITS
SEE NOTE 1
POSITIVE AND NEGATIVE
GROUND FAULT
DETECTED AT
<500 OHMS FOR
TERMINALS 3-6 ON TB1
*REFER TO RSE-300 INSTALLATION INSTRUCTIONS, P/N 315-099082FA, FOR PROPER SETTING OF SWITCH 4. THE AUXILIARY POWER OUTPUT MUST BE CONFIGURED TO “ALWAYS ON.”
When connected to NAC of MPC panel, the NAC must be configured as "Always ON."
The input power and NAC power inputs on TB2 (1-4) MUST be connected to the same source.