PAGE 2 OF 2
WIRING
Figure 3
Wiring Information
TO NEXT ADDRESSABLE DEVICE
LINE 1
1
LINE
2
LINE
2
LINE
EARTH GROUND
1
2
3
FROM INITIATING CONTROL PANEL
OR PREVIOUS ADDRESSABLE DEVICE
NOTES
:
1. Recommended wire sizes:
18 AWG minimum, 14 AWG maximum
2. Wire larger than 14 AWG can damage the connector.
3.
When using shielded cable without metal raceway or with
nonmetallic raceway,
the shields should be terminated at the device
ground terminal. If the device box is already grounded by another
means, such as being mounted to a grounded structure, the wire
shields should be continuous and must be grounded solely at the point
of origin; for example, at the control panel.
4.
When using shielded cable with metal raceway,
the wiring shields
shall be continuous and grounded solely at the point of origin. The
device ground terminal shall be connected to the grounded device
box.
5.
When using metal raceway without shielded cable,
connect the
device ground terminal to the grounded device box.
6. Metal raceway should be thoroughly grounded throughout the system.
7. The 8700-S and 8700-D draw 1mA from the addressable device
circuit.
8. The 8700-S and 8700-D are polarity insensitive devices. Line 1 and
Line 2 can be either line of the loop.
3½ INCH DEEP
SWITCH BOX
(USER SUPPLIED)
MODEL
SB-5R
BACKPLATE
BACKPLATE
SURFACE
MOUNTING
ENCLOSURE
FLUSH
MOUNTING
ENCLOSURE
HOUSING HINGED
TO BACKPLATE
HOUSING
LOCKING
SCREW
5½ in.
3 in.
4 in.
2¾ in.
3½ in.
NAMEPLATE
INSTALLATION
Distribute the manual station boxes throughout the protected area so that they
are unobstructed, readily accessible, and located in the normal exit path. Place the manual station accord-
ing to the regulations of the authorities having jurisdiction.
Surface Mounting
Mount the backplate to a Faraday Model 8864 Backbox as shown in Figure 4.
Flush Mounting
Mount the backplate to a user supplied single gang switchbox.
Do not overtighten the screws. Overtightening may distort the backplate.
P/N 315-033200FA-5
Figure 4
Mounting