ART.3001 20  230 V 

ART.3001 40  230 V

ART.3002 20  24 V

ART.3002 40  24 V

ART.3005 20  230 V 

ART.3005 40  230 V

ART.3006 20  24 V

ART.3006 40  24 V

ART.3007 8  230 V 

ART.3008 8  24 V

ARTICLE

VOLTAGE 

FREQUENCY

ABSORBED 

POWER

R O TAT I O N 

ANGLE

ROTATION

 TIME

TORQUE

ROOM 

TEMPERATURE

DEGREE OF 

PROTECTION

COLOUR

3001 20

230 V-50Hz

4,5 VA

90°

20 S

6 Nm

-10° + 50°C

IP54

YELLOW

3001 40

230 V-50Hz

4,5 VA

90°

40 S

10 Nm

-10° + 50°C

IP54

YELLOW

3002 20

24 V-50Hz

4,5 VA

90°

20 S

6 Nm

-10° + 50°C

IP54

YELLOW

3002 40

24 V-50Hz

4,5 VA

90°

40 S

10 Nm

-10° + 50°C

IP54

YELLOW

3005 20

230 V-50Hz

4,5 VA

90°

20 S

6 Nm

-10° + 50°C

IP54

GREEN

3005 40

230 V-50Hz

4,5 VA

90°

40 S

10 Nm

-10° + 50°C

IP54

GREEN

3006 20

24 V-50Hz

4,5 VA

90°

20 S

6 Nm

-10° + 50°C

IP54

GREEN

3006 40

24 V-50Hz

4,5 VA

90°

40 S

10 Nm

-10° + 50°C

IP54

GREEN

3007 8

230 V-50Hz

   6 VA

90°

8 S

6 Nm

-10° + 50°C

IP54

GREY

3008 8

24 V-50Hz

   6 VA

90°

8 S

6 Nm

-10° + 50°C

IP54

GREY

1.  DESCRIPTION

The actuator, incorporating an appropriate servomotor, permits automatic 
operation of a zone valve. It operates in response to a signal from a 
thermostat with traditional ON-OFF regulation, a clock-thermostat or from 
any other suitable electrical open/close contact. An indicator shows the 
position of the stem and thus the real position of the valve. Note: This 
system should not be operated within an explosive atmosphere.
Prior to installation check that the actuator is in the “OPENING” position; 
the indicator must be positioned in the same direction as the thermal 

fluid flow. Check the screwdriver slot position: it must be the same as the 
actuator pivot. Insert the stud bolts in the holes in the flange of the valve 

and lock in position with the screw nuts. 
The actuator is suitable for use with all FAR zone valves.

2. USE OF MANUAL RELEASE

The manual release can be used:

-  when  it  is  necessary  to  shut  off  the  water  supply  in                                                                                                                                               

  event of maintenance work on the system

- in order to position the valve once the motor is installed

- or in case of power failure.

In order to manually open or close the actuator, push 
the yellow key and simultaneously turn the position 
indicator counter-clockwise through 90°. Normal 
functioning will return automatically.

3.ELECTRICAL CONNECTION

  Before connecting the actuator ensure that the selected model is compatible with the available network voltage.

All connections must to be made by qualified personnel, with respect for the overall electrical system and taking care that the electricity 

supply is switched off. Incorrect connection may damage both persons and equipment. All FAR actuators have been designed with an 

additional auxiliary microswitch, an exchange contact without voltage, for low-tension signals (max. 230 V.) and/or to supply applications 

with low electrical input (max 2A).

WIRING CONNECTIONS: ACTUATOR AND THERMOSTAT

WIRING CONNECTION: ACTUATOR, THERMOSTAT AND PUMP STARTING

To control opening and closing of a zone valve via an actuator, 
connect the blue wire to the neutral one, the brown to the phase and 
the black to the thermostat. The valve opens in presence of phase 
on the black wire.

An inner auxiliary microswitch connected to the grey and white 
wires (clean contact), independent from the actuator circuit, permits 
connection in parallel of more than one actuator to control a single 
device, such as a pump or boiler. To control the starting of the pump, 
connect the grey and white wires to the 2 terminals provided in the 
boiler for connection to the thermostat.

1

2

3

N

5

6

7

INTERNAL TERMINAL BOARD

GREY

WHITE

BLUE

BROWN

BLACK

CONNECTION

DESCRIPTION

MICROSWITCH

COMMON CONTACT

CONNECTED TO THE COMMON CONTACT

OF THE MICROSWITCH

N.O. OF THE

MICROSWITCH

CONNECTED TO THE NORMALLY OPEN 

CONTACT OF THE MICROSWITCH

SIGNAL INDICATOR

WITH OPEN VALVE PRESENCE OF

PHASE ON TERMINAL

NEUTRAL

CONNECTION TO THE NEUTRAL OF SYSTEM

PHASE

CONNECTION TO THE PHASE OF SYSTEM

OPEN

WITH PHASE ON THE BLACK THE VALVE

IS OPEN 

CLOSE

IN ABSENCE OF PHASE ON THE

BLACK, THE VALVE IS CLOSED

SIGNAL INDICATOR

WITH CLOSE VALVE PRESENCE OF

PHASE ON TERMINAL

COLOUR

1

GREY

2

WHITE

3

-

N

BLUE

5

BROWN

6

BLACK

7

-

DIRECTIVE 2002/96/CE FOR WASTE DISPOSAL OF ELECTRICAL AND ELECTRONIC EQUIPMENT

The EEC Standard 2002/96/CE on WEEE (waste of electrical and electronic equipment) provides that they must be 

eliminated separately and not like a solid urban waste.

For the correct disposal of WEEE must apply to the local authority, who will give all the information needed about the 

modality to follow.

DECLARATION OF CONFORMITY

FAR Rubinetterie declare under their own responsibility that actuators are according to EEC Standards: 

2004/108/CE and 2006/95/CE.

4.TECHNICAL ASSISTANCE

Should  technical  assistance  be  required,  do  not  operate;  remove  the  actuator  from  the  valve  and  contact  FAR  Rubinetterie  SpA                          

via Morena, 20 - 28024 GOZZANO (NO) ITALY, TEL. 0322/ 94722 - -956450 - Fax 0322/ 955332.

The actuator is provided with a double isolation, so earthing is not required.

FIXING NUTS

DO NOT REMOVE THE 

TWO MENTIONED NUT

TUERCAS DE FIJACION

NO QUITAR LAS DOS 

TUERCAS INDICADAS

FAR Rubinetterie S.p.A. - www.far.eu

SERVOMOTOR “SMALL” 

INSTRUCCIONES PARA EL USO

ART.3001 20  230 V 

ART.3001 40  230 V

ART.3002 20  24 V

ART.3002 40  24 V

ART.3005 20  230 V 

ART.3005 40  230 V

ART.3006 20  24 V

ART.3006 40  24 V

ART.3007 8  230 V 

ART.3008 8  24 V

ARTICULO

TENSION

FRECUENCIA

POTENCIA

ABSORBIDA

ANGULO DE 

ROTACION

TIEMPO DE

ROTACION

PAR

MOTRIZ

TEMPERATURA

DE TRABAJO

GRADO DE

PROTECCION

COLOR

3001 20

230 V-50Hz

4,5 VA

90°

20 S

6 Nm

-10°C + 50°C

IP54

AMARILLO

3001 40

230 V-50Hz

4,5 VA

90°

40 S

10 Nm

-10°C + 50°C

IP54

AMARILLO

3002 20

24 V-50Hz

4,5 VA

90°

20 S

6 Nm

-10°C + 50°C

IP54

AMARILLO

3002 40

24 V-50Hz

4,5 VA

90°

40 S

10 Nm

-10°C + 50°C

IP54

AMARILLO

3005 20

230 V-50Hz

4,5 VA

90°

20 S

6 Nm

-10°C + 50°C

IP54

VERDE

3005 40

230 V-50Hz

4,5 VA

90°

40 S

10 Nm

-10°C + 50°C

IP54

VERDE

3006 20

24 V-50Hz

4,5 VA

90°

20 S

6 Nm

-10°C + 50°C

IP54

VERDE

3006 40

24 V-50Hz

4,5 VA

90°

40 S

10 Nm

-10°C + 50°C

IP54

VERDE

3007 8

230 V-50Hz

   6 VA

90°

8 S

6 Nm

-10°C + 50°C

IP54

GRIS

3008 8

24 V-50Hz

   6 VA

90°

8 S

6 Nm

-10°C + 50°C

IP54

GRIS

1. DESCRIPCIÓN DEL SERVOMOTOR

El servomotor, constituido por un motoreductor permite la maniobra, de 
un válvula de zona de forma completamente automática llevando la señal 
para su funcionamiento mediante un termostato ambiente con regulación 
ON-OFF de tipo tradicional, crono termostato o de cualquier contacto 
eléctrico de apertura/cierre. Mediante un indicador es posible conocer en 
qué posición se encuentra la válvula.
Para la instalación controlar que el servomotor este en posición “ABIERTO” 

verificando que el indicador de posición este orientado en el sentido de 
movimiento  del  fluido.  Predisponer    la  válvula  en  posición  “ABIERTA”  o 

sea que el corte para el destornillador este orientado como el perno del 
servomotor. Insertar el prisionero en el taladro de la brida de la válvula 
y blocarlas con las tuercas que se acompañan. El servomotor se puede 
instalar sobre todas las válvulas de zona FAR. No están preparados para 
utilizar en atmósfera explosiva.

2. UTILIZACION DEL BLOQUEO MANUAL

El bloqueo manual puede ser utilizado para:

  

-  Interrumpir el flujo de agua en el caso de intervenir                                                                                                                                       

    extraordinariamente sobre la instalación.

   

-  Posicionar la válvula una vez instalado el motor

-  Falta de corriente eléctrica.
Para actuar en apertura o cierre el motor manualmente 
tener pulsado el botón de color amarillo y al mismo 
tiempo girar 90° en sentido antihorario el indicador 
de posición.
El restablecimiento del funcionamiento normal se 
produce automáticamente.

3. CONEXIONADO ELÉCTRICO

  Antes de conectar eléctricamente el servomotor cerciorarse que el modelo elegido sea compatible con la tensión de red disponible.

Todas las conexiones deben ser efectuadas por personal especializado respetando el esquema eléctrico (indicado en el propio servomotor) 

y asegurándose que la línea eléctrica no esté bajo tensión, una conexión errónea puede provocar daño bien al operario o bien al servomotor. 

Todas las versiones vienen dotadas de micro interruptor auxiliar suplementario o sea con contacto de intercambio sin tensión a disposición 

del usuario para señal a baja tensión (max.230 V) y/o para alimentar a bajo absorción (máx. 2 A).

CONEXIÓN A 3 HILOS: MANDO CON TERMOSTATO AMBIENTE

CONEXIÓN A 5 HILOS: MANDO CON TERMOSTATO AMBIENTE Y ACCIONAMIENTO BOMBA

Para comandar la apertura y el cierre de la válvula de zona por medio 
del servomotor basta conectar el cable de color azul al neutro de la 
alimentación, el cable de color marrón a la fase y el cable de color negro 
al termostato de ambiente. Con  presencia de fase sobre el cable negro 
la válvula abre. 
Para el correcto funcionamiento del servomotor es importante que el 
cable marrón este siempre bajo tensión.

La presencia del micro interruptor auxiliar (contacto pulido) interno 
conectado al cable gris y blanco, siendo independiente del circuito 
del servomotor permite conectar más servomotores en paralelo para 
gobernar un único aparato como por ejemplo la bomba o la caldera. En el 
caso que se deba comandar el funcionamiento de la bomba incorporada 
en la caldera, basta conectar el cable de color gris y blanco a los dos 
contactos predispuestos (en la caldera) para conectar al termostato.

El servomotor incorpora doble aislamiento, por lo cual no es necesario instalar toma de tierra.

1

2

3

N

5

6

7

CONEXIONES INTERNAS

GRIS

BLANCO

AZUL

MARRÓN

NEGRO

COLOR

1

GRIS

2

BLANCO

3

-

N

AZUL

5

MARRÓN

6

NEGRO

7

-

CONEXIONADO

DESCRIPCIÓN

COMÚN MICRO INTERRUPTOR

CONECTADO AL COMÚN MICRO AUXILIAR

N.A. DEL MICRO

CONECTADO AL N.A. DEL MICRO AUXILIAR

INDICADOR LUMINOSO

CON VÁLVULA ABIERTA, PRESENCIA DE 

FASE

NEUTRO

CONEXIÓN DE NEUTRO

FASE

CONEXIÓN DE FASE

ABRE

CON FASE AL NEGRO: ABRE

CIERRA

SIN FASE AL NEGRO: CIERRA

INDICADOR LUMINOSO

CON VÁLVULA CERRADA PRESENCIA DE 

FASE EN E BORNE

DIRECTIVA 2002/96/CE SOBRE RECHAZO APARATOS ELECTRICOS Ó ELECTRONICOS

La directiva comunitaria 2002/90/CE  sobre RAEE (Rechazo aparatos eléctricos o electrónicos) prevé que sea prohibido 

tirar cualquier tipo de RAEE como rechazo sólido urbano y debe ser obligatoriamente gestionado separadamente.

Para el correcto rechazo del RAEE es necesario dirigirse a la autoridad local que informara de la modalidad y proceso 

a seguir así como el lugar y la hora donde debe ser entregado el material.

DECLARACION DE CONFORMIDAD

FAR Rubinetterie declara bajo su responsabilidad que los servomotores que fábrica son de conformidad a lo que exige la directiva 

comunitaria 2004/108/CE y 2006/95/CE.

Art.3001- 3002- 3005- 3006-3007-3008

GB

E

www.far-moscow.ru  Москва, ул. Народного Ополчения, д. 34, стр. 3  (499) 519-03-69

Reviews: