FAN COIL ROOM THERMOSTAT
CH130ARR2
7.2 - SYSTEM INSTALLATION PARAMETERS (HIDDEN MENU)
PARAMETER
DESCRIPTION
DEFAULT
FIELD
P06
Plant type (
PLANT
)
2P
2P: 2 pipes
4P:
4
pipes
P07
Hot water/electrical resistance valve selection
1
1: hot water valve
2: electrical resistance
P08
Ventilation modes
1
1: continuous
2: continuous-stop winter mode
3: continuous-stop summer mode
4: subordinated to valve status
5: subordinated-stop in winter mode
6: subordinated-stop in summer mode
P9
Adjustment modes
1
1: Manual Winter/Summer mode
2: Automatic Winter/Summer mode
P10
Anti-stratification
1
1: not active
2: summer only
3: winter only
P11*
Temperature sensor on remote actuator sensor
input
Reading frequency : Once a minute
1
1: not connected
2: winter only minimum sensor
3: winter/summer minimum sensor
4: automatic change-over
5: return ( only if P13 is other than 6 )
P12
Temperature sensor on external sensor input
Reading frequency : Once a minute
Options 7-8-9 are only visible if CH172D was
selected as remote actuator ( P51 )
1
1: not connected
2: ON/OFF
3:
manual
change-over
4: comfort/economy
5: reduction (-3.0°C 3.0°C
summer)
6: return ( only if P12 is other than 5 )
7: winter only minimum sensor
8: winter/summer minimum sensor
9:
automatic
change-over
P13
Auxiliary input
Reading frequency : Once every 10 seconds
1
1: not connected
2: ON/OFF
3:
manual
change-over
4: comfort/economy
5: reduction (-3.0°C 3.0°C
summer)
P14
P13 - P14
input polarity
1
n.o.
normally open
n.c.
normally closed
1:
P12
(n.o.)
P13
(n.o.)
2:
P12
(n.o.)
P13
(n.c.)
3:
P12
(n.c.)
P13
(n.o.)
4:
P12
(n.c.)
P13
(n.c.)
P15
Room temperature correction
0.0 °C
-4.0°C … 4.0°C (0.1°C step)
P16
Temperature correction on external sensor
0.0 °C
-4.0°C … 4.0°C (0.1°C step)
P17
Temperature correction on remote sensor
0.0 °C
-4.0°C … 4.0°C (0.1°C step)