35 -
ENG
C820RQ
Energy class
When the
TPI
adjustment is active, it is necessary to set the energy class of the building
for enabling the optimisation of the system's runtimes.
Default parameter = A4
A4, A3, A2, A1, B, C, D, E, F, G
Function only available for TPI adjustment.
TPI Adjustment Period
The
TPI
Adjustment Period indicates the duration of a system on+off cycle. This
period depends on the type of the emission terminal.
The values for the Adjustment Period are set automatically by setting the emission
terminal (see table
P13
); however, they can still be changed.
Default value = 15
5 ÷ 60 min
Function only available for TPI adjustment.
Type of emission terminals
If the
TPI
adjustment is activated, it is necessary to also set other related parameters.
The emission terminal identifies the final element of the heating/cooling system.
By setting the emission terminal, the values of the Proportional Band and the
Adjustment Period are automatically set (see the below table); however, they can
still be changed.
Emission terminal
Proportional band [°C]
Setting period [min]
Radiators
0.5
15
Fan coil
0.5
15
Floor
1
30
Default value = 1
1 = Radiators
2 = Fan Coil
3 = Floor
Function only available for TPI adjustment.