background image

7

Built in Electrical Safety

For your safety and protection this appliance is manufactured

with a grounded plug on its power cord. The power cord must

be plugged into a properly grounded receptacle. If a ground-

ed receptacle does not exist, have one installed by a certified

electrician. Do not cut or remove the grounding prong on the

power cord plug if equipped. We recommend that this electri-

cal  circuit/receptacle  operate  under  a  separate  breaker  or

fuse.
If an extension cord is required, it must have a minimum of

14  gauge  conductors  if  25  feet  long  or  less  and  12  gauge

conductors if greater than 25 feet long.

Electrical Requirements

For 115V operation, a common grounded outlet on a 15 amp

circuit is required. The dehumidifier draws approx. 8 amps at

80°F,  60%  RH.  If  used  in  a  wet  area,  a  ground  fault  inter-

rupter (GFI) is required.

Power Button (Fig. 1)

The  dehumidifier  is  turned  on  or  off  by

pressing  the  power  button.  When  the

dehumidifier is started, the hour meter will

display the cumulative hours. 

Pump Purge Button (Fig. 2)

In normal operation, the pump will automat-

ically empty the reservoir. Pressing this but-

ton allows manual emptying of the reservoir.

Press once, and the pump will operate for

20 seconds. Press and hold the button and

the pump will activate for 30 seconds.

Always manually purge the water reservoir

before  transport  or  storage.  Turn  off  the

power and allow the plugged in dehumidifier

to rest 5 minutes before the final purge.

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, 
fire, or electrical shock.

WARNING

Place dehumidifier inside area to be dried. Make sure all win-

dows and doors are closed to the outside and seal off the wet

area from any unaffected areas. Route condensate hose into

a  drain,  or  a  very  large  container.  Press  the  On/Off  button

(Fig. 1) to activate the dehumidifier.

OPERATION

Fig. 1

Fig. 2

Digital Hour Counter (Fig. 3)

The counter will accumulate and display the total running hours

of the unit in 1/10 of an hour. 

Hour Button (Fig. 4)

Press the HOURS button when the dehu-

midifier cannot be plugged in and the hour

meter  needs  to  be  read.  The  digital  hour

meter will display the last saved cumulative

time for ten seconds.

Defrost Indicator (Fig. 5)

The defrost indicator will light to indicate the

dehumidifier is in defrost cycle. During this

period, the compressor is not running.

Defrost Cycle

When ice builds up on the coils, a thermistor activates the elec-

tronic control and defrost light. The compressor is turned off by

the thermistor temperature measurement. The blower will contin-

ue to run, causing air to flow through the evaporator coil and melt

the ice. When the ice is melted, the thermistor will end the defrost

cycle and the compressor will be started.

Disconnect dehumidifier from power supply. The hour meter uses

a battery backup for display when the dehumidifier is unplugged

and the hour button is depressed. To change the battery, it is nec-

essary  to  remove  the  four  (4)  screws  from  the  control  panel.

Disconnect the old battery and replace with new battery. Replace

control panel and screws. Do not overtighten screws.

Water Removal

The dehumidifier is equipped with an internal condensate pump

to remove the water that is collected from the air. This allows the

water to be pumped 20 feet with the attached hose. If the water

needs to be pumped more than 20 feet above the unit, a second

pump must be added to relay the water. The condensate pump

automatically purges for 20 seconds every four minutes.

Fig. 3

Fig. 4

Fig. 5

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.

WARNING

Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,

fire, or electrical shock.

Battery Replacement

(1)

AVERTISSEMENT

Built in Electrical Safety

For your safety and protection this appliance is manufactured

with a grounded plug on its power cord. The power cord must

be plugged into a properly grounded receptacle. If a ground-

ed receptacle does not exist, have one installed by a certified

electrician. Do not cut or remove the grounding prong on the

power cord plug if equipped. We recommend that this electri-

cal  circuit/receptacle  operate  under  a  separate  breaker  or

fuse.
If an extension cord is required, it must have a minimum of

14  gauge  conductors  if  25  feet  long  or  less  and  12  gauge

conductors if greater than 25 feet long.

Electrical Requirements

For 115V operation, a common grounded outlet on a 15 amp

circuit is required. The dehumidifier draws approx. 8 amps at

80°F,  60%  RH.  If  used  in  a  wet  area,  a  ground  fault  inter-

rupter (GFI) is required.

Power Button (Fig. 1)

The  dehumidifier  is  turned  on  or  off  by

pressing  the  power  button.  When  the

dehumidifier is started, the hour meter will

display the cumulative hours. 

Pump Purge Button (Fig. 2)

In normal operation, the pump will automat-

ically empty the reservoir. Pressing this but-

ton allows manual emptying of the reservoir.

Press once, and the pump will operate for

20 seconds. Press and hold the button and

the pump will activate for 30 seconds.

Always manually purge the water reservoir

before  transport  or  storage.  Turn  off  the

power and allow the plugged in dehumidifier

to rest 5 minutes before the final purge.

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, 
fire, or electrical shock.

WARNING

Place dehumidifier inside area to be dried. Make sure all win-

dows and doors are closed to the outside and seal off the wet

area from any unaffected areas. Route condensate hose into

a  drain,  or  a  very  large  container.  Press  the  On/Off  button

(Fig. 1) to activate the dehumidifier.

OPERATION

Fig. 1

Fig. 2

Digital Hour Counter (Fig. 3)

The counter will accumulate and display the total running hours

of the unit in 1/10 of an hour. 

Hour Button (Fig. 4)

Press the HOURS button when the dehu-

midifier cannot be plugged in and the hour

meter  needs  to  be  read.  The  digital  hour

meter will display the last saved cumulative

time for ten seconds.

Defrost Indicator (Fig. 5)

The defrost indicator will light to indicate the

dehumidifier is in defrost cycle. During this

period, the compressor is not running.

Defrost Cycle

When ice builds up on the coils, a thermistor activates the elec-

tronic control and defrost light. The compressor is turned off by

the thermistor temperature measurement. The blower will contin-

ue to run, causing air to flow through the evaporator coil and melt

the ice. When the ice is melted, the thermistor will end the defrost

cycle and the compressor will be started.

Disconnect dehumidifier from power supply. The hour meter uses

a battery backup for display when the dehumidifier is unplugged

and the hour button is depressed. To change the battery, it is nec-

essary  to  remove  the  four  (4)  screws  from  the  control  panel.

Disconnect the old battery and replace with new battery. Replace

control panel and screws. Do not overtighten screws.

Water Removal

The dehumidifier is equipped with an internal condensate pump

to remove the water that is collected from the air. This allows the

water to be pumped 20 feet with the attached hose. If the water

needs to be pumped more than 20 feet above the unit, a second

pump must be added to relay the water. The condensate pump

automatically purges for 20 seconds every four minutes.

Fig. 3

Fig. 4

Fig. 5

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.

WARNING

Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,

fire, or electrical shock.

Battery Replacement

(1)

Risque de choc électrique

Brancher sur une prise à 3 alvéoles reliée à la terre.
Ne pas enlever la broche de liaison à la terre.
Ne pas utiliser un adaptateur.
Ne pas utiliser un câble de rallonge.
Le non-respect de ces instructions peut causer un décès, un 

incendie ou un choc électrique.

Alimentation

Pour le fonctionnement sous une tension de 115 V, une prise 

mise  à  la  terre  ordinaire  d’un  circuit  de  15  ampères  est 

nécessaire. S’il est utilisé dans une aire humide, l’usage d’un 

disjoncteur de fuite de terre (DFT) est nécessaire.

Dispositif de sécurité électrique intégré

Dans le but d'assurer votre sécurité et votre protection, cet

appareil est muni d’un cordon d’alimentation avec fiche mise 

à la terre. Le cordon d’alimentation doit être branché dans 

une prise convenablement mise à la terre. S’il n’y a pas de 

prise mise à la terre, faites-en installer une par un électricien 

agréé. Ne coupez pas et n’enlevez pas la broche de mise à 

la terre de la fiche du cordon d'alimentation s'il y en a une. 

Nous recommandons d’utiliser ce circuit électrique ou cette 

prise avec un disjoncteur ou un fusible distinct.

Si  une  rallonge  électrique  doit  être  utilisée,  elle  doit 

comporter des conducteurs d’un calibre minimum de 14 si 

elle fait 25 pieds de long ou moins et des conducteurs de 

calibre 12 si elle fait plus de 25 pieds.

Limitations d'usage

Limitations d'usage

Température: 4ºC à 35'C (40ºF à 95ºF)

Humidité relative: 20 à 80%

Enlèvement de l'eau

Le déshumidificateur est équipé d’une pompe à condensats 

interne servant à enlever l’eau retirée de l’air. Elle permet de 

pomper l’eau à vingt pieds avec le tuyau fixé à l’appareil. Si 

l’eau doit être pompée à plus de vingt pieds au-dessus de 

l’unité, il faut ajouter une seconde pompe à laquelle l’eau est 

envoyée. La pompe à condensats se purge automatiquement 

pendant vingt secondes toutes les quatre minutes.

FONCTIONNEMENT

Placez  le  déshumidificateur  à  l’intérieur  de  l’aire  à  sécher. 

Assurezvous que toutes les fenêtres et les portes sont fermées 

et isolez l’aire humide des  ires non touchées. Faites aboutir le 

tuyau  à  condensats  à  un  drain  ou  à  un  très  gros  contenant. 

Appuyez  sur  le  bouton  On/Off  (Fig.  1) 

pour activer le déshumidificateur.

Bouton de mise en marche (Fig. 1)

On allume ou éteint le déshumidificateur 

en  appuyant  sur  le  bouton  de  mise  en 

marche. Lorsque le déshumidificateur se 

met  en  marche,  le  compteur  d’heures 

affiche le total cumulé des heures. 

Bouton de purge de la pompe (Fig. 2)

 

En  fonctionnement  normal,  la  pompe 

videra automatiquement le réservoir. En 

appuyant  sur  ce  bouton,  on  peut  vider 

manuellement  le  réservoir.  Si  vous 

appuyez une fois, la pompe fonctionnera 

pendant vingt secondes. Si vous appuyez 

sur le bouton et le maintenez enfoncé, la pompe sera activée 

pendant  trente  secondes. 

Purgez  toujours  manuellement  le 

réservoir  d’eau  avant  de  transporter  ou  d’entreposer  la 

pompe.  Coupez  l’alimentation  et  laissez  le  déshumidificateur 

branché reposer pendant cinq minutes avant la purge finale. 

Compteur d’heures numérique (Fig. 3)

Le compteur comptabilise et affiche le total des heures de 

fonctionnement de l’unité en dixièmes d’heure.

Built in Electrical Safety

For your safety and protection this appliance is manufactured

with a grounded plug on its power cord. The power cord must

be plugged into a properly grounded receptacle. If a ground-

ed receptacle does not exist, have one installed by a certified

electrician. Do not cut or remove the grounding prong on the

power cord plug if equipped. We recommend that this electri-

cal  circuit/receptacle  operate  under  a  separate  breaker  or

fuse.
If an extension cord is required, it must have a minimum of

14  gauge  conductors  if  25  feet  long  or  less  and  12  gauge

conductors if greater than 25 feet long.

Electrical Requirements

For 115V operation, a common grounded outlet on a 15 amp

circuit is required. The dehumidifier draws approx. 8 amps at

80°F,  60%  RH.  If  used  in  a  wet  area,  a  ground  fault  inter-

rupter (GFI) is required.

Power Button (Fig. 1)

The  dehumidifier  is  turned  on  or  off  by

pressing  the  power  button.  When  the

dehumidifier is started, the hour meter will

display the cumulative hours. 

Pump Purge Button (Fig. 2)

In normal operation, the pump will automat-

ically empty the reservoir. Pressing this but-

ton allows manual emptying of the reservoir.

Press once, and the pump will operate for

20 seconds. Press and hold the button and

the pump will activate for 30 seconds.

Always manually purge the water reservoir

before  transport  or  storage.  Turn  off  the

power and allow the plugged in dehumidifier

to rest 5 minutes before the final purge.

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, 
fire, or electrical shock.

WARNING

Place dehumidifier inside area to be dried. Make sure all win-

dows and doors are closed to the outside and seal off the wet

area from any unaffected areas. Route condensate hose into

a  drain,  or  a  very  large  container.  Press  the  On/Off  button

(Fig. 1) to activate the dehumidifier.

OPERATION

Fig. 1

Fig. 2

Digital Hour Counter (Fig. 3)

The counter will accumulate and display the total running hours

of the unit in 1/10 of an hour. 

Hour Button (Fig. 4)

Press the HOURS button when the dehu-

midifier cannot be plugged in and the hour

meter  needs  to  be  read.  The  digital  hour

meter will display the last saved cumulative

time for ten seconds.

Defrost Indicator (Fig. 5)

The defrost indicator will light to indicate the

dehumidifier is in defrost cycle. During this

period, the compressor is not running.

Defrost Cycle

When ice builds up on the coils, a thermistor activates the elec-

tronic control and defrost light. The compressor is turned off by

the thermistor temperature measurement. The blower will contin-

ue to run, causing air to flow through the evaporator coil and melt

the ice. When the ice is melted, the thermistor will end the defrost

cycle and the compressor will be started.

Disconnect dehumidifier from power supply. The hour meter uses

a battery backup for display when the dehumidifier is unplugged

and the hour button is depressed. To change the battery, it is nec-

essary  to  remove  the  four  (4)  screws  from  the  control  panel.

Disconnect the old battery and replace with new battery. Replace

control panel and screws. Do not overtighten screws.

Water Removal

The dehumidifier is equipped with an internal condensate pump

to remove the water that is collected from the air. This allows the

water to be pumped 20 feet with the attached hose. If the water

needs to be pumped more than 20 feet above the unit, a second

pump must be added to relay the water. The condensate pump

automatically purges for 20 seconds every four minutes.

Fig. 3

Fig. 4

Fig. 5

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.

WARNING

Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,

fire, or electrical shock.

Battery Replacement

(1)

Fig. 3

Bouton des heures (Fig. 4)

Appuyez sur le bouton HEURES lorsque 

le  déshumidificateur  ne  peut  être 

branché  et  qu’il  faut  lire  l’affichage  du 

compteur  d’heures.  Le  compteur 

d’heures numérique affichera le dernier 

total  cumulé  des  heures  sauvegardé 

pendant dix secondes.

Remplacement de la pile

Built in Electrical Safety

For your safety and protection this appliance is manufactured

with a grounded plug on its power cord. The power cord must

be plugged into a properly grounded receptacle. If a ground-

ed receptacle does not exist, have one installed by a certified

electrician. Do not cut or remove the grounding prong on the

power cord plug if equipped. We recommend that this electri-

cal  circuit/receptacle  operate  under  a  separate  breaker  or

fuse.
If an extension cord is required, it must have a minimum of

14  gauge  conductors  if  25  feet  long  or  less  and  12  gauge

conductors if greater than 25 feet long.

Electrical Requirements

For 115V operation, a common grounded outlet on a 15 amp

circuit is required. The dehumidifier draws approx. 8 amps at

80°F,  60%  RH.  If  used  in  a  wet  area,  a  ground  fault  inter-

rupter (GFI) is required.

Power Button (Fig. 1)

The  dehumidifier  is  turned  on  or  off  by

pressing  the  power  button.  When  the

dehumidifier is started, the hour meter will

display the cumulative hours. 

Pump Purge Button (Fig. 2)

In normal operation, the pump will automat-

ically empty the reservoir. Pressing this but-

ton allows manual emptying of the reservoir.

Press once, and the pump will operate for

20 seconds. Press and hold the button and

the pump will activate for 30 seconds.

Always manually purge the water reservoir

before  transport  or  storage.  Turn  off  the

power and allow the plugged in dehumidifier

to rest 5 minutes before the final purge.

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, 
fire, or electrical shock.

WARNING

Place dehumidifier inside area to be dried. Make sure all win-

dows and doors are closed to the outside and seal off the wet

area from any unaffected areas. Route condensate hose into

a  drain,  or  a  very  large  container.  Press  the  On/Off  button

(Fig. 1) to activate the dehumidifier.

OPERATION

Fig. 1

Fig. 2

Digital Hour Counter (Fig. 3)

The counter will accumulate and display the total running hours

of the unit in 1/10 of an hour. 

Hour Button (Fig. 4)

Press the HOURS button when the dehu-

midifier cannot be plugged in and the hour

meter  needs  to  be  read.  The  digital  hour

meter will display the last saved cumulative

time for ten seconds.

Defrost Indicator (Fig. 5)

The defrost indicator will light to indicate the

dehumidifier is in defrost cycle. During this

period, the compressor is not running.

Defrost Cycle

When ice builds up on the coils, a thermistor activates the elec-

tronic control and defrost light. The compressor is turned off by

the thermistor temperature measurement. The blower will contin-

ue to run, causing air to flow through the evaporator coil and melt

the ice. When the ice is melted, the thermistor will end the defrost

cycle and the compressor will be started.

Disconnect dehumidifier from power supply. The hour meter uses

a battery backup for display when the dehumidifier is unplugged

and the hour button is depressed. To change the battery, it is nec-

essary  to  remove  the  four  (4)  screws  from  the  control  panel.

Disconnect the old battery and replace with new battery. Replace

control panel and screws. Do not overtighten screws.

Water Removal

The dehumidifier is equipped with an internal condensate pump

to remove the water that is collected from the air. This allows the

water to be pumped 20 feet with the attached hose. If the water

needs to be pumped more than 20 feet above the unit, a second

pump must be added to relay the water. The condensate pump

automatically purges for 20 seconds every four minutes.

Fig. 3

Fig. 4

Fig. 5

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.

WARNING

Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,

fire, or electrical shock.

Battery Replacement

(1)

AVERTISSEMENT

Built in Electrical Safety

For your safety and protection this appliance is manufactured

with a grounded plug on its power cord. The power cord must

be plugged into a properly grounded receptacle. If a ground-

ed receptacle does not exist, have one installed by a certified

electrician. Do not cut or remove the grounding prong on the

power cord plug if equipped. We recommend that this electri-

cal  circuit/receptacle  operate  under  a  separate  breaker  or

fuse.
If an extension cord is required, it must have a minimum of

14  gauge  conductors  if  25  feet  long  or  less  and  12  gauge

conductors if greater than 25 feet long.

Electrical Requirements

For 115V operation, a common grounded outlet on a 15 amp

circuit is required. The dehumidifier draws approx. 8 amps at

80°F,  60%  RH.  If  used  in  a  wet  area,  a  ground  fault  inter-

rupter (GFI) is required.

Power Button (Fig. 1)

The  dehumidifier  is  turned  on  or  off  by

pressing  the  power  button.  When  the

dehumidifier is started, the hour meter will

display the cumulative hours. 

Pump Purge Button (Fig. 2)

In normal operation, the pump will automat-

ically empty the reservoir. Pressing this but-

ton allows manual emptying of the reservoir.

Press once, and the pump will operate for

20 seconds. Press and hold the button and

the pump will activate for 30 seconds.

Always manually purge the water reservoir

before  transport  or  storage.  Turn  off  the

power and allow the plugged in dehumidifier

to rest 5 minutes before the final purge.

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, 
fire, or electrical shock.

WARNING

Place dehumidifier inside area to be dried. Make sure all win-

dows and doors are closed to the outside and seal off the wet

area from any unaffected areas. Route condensate hose into

a  drain,  or  a  very  large  container.  Press  the  On/Off  button

(Fig. 1) to activate the dehumidifier.

OPERATION

Fig. 1

Fig. 2

Digital Hour Counter (Fig. 3)

The counter will accumulate and display the total running hours

of the unit in 1/10 of an hour. 

Hour Button (Fig. 4)

Press the HOURS button when the dehu-

midifier cannot be plugged in and the hour

meter  needs  to  be  read.  The  digital  hour

meter will display the last saved cumulative

time for ten seconds.

Defrost Indicator (Fig. 5)

The defrost indicator will light to indicate the

dehumidifier is in defrost cycle. During this

period, the compressor is not running.

Defrost Cycle

When ice builds up on the coils, a thermistor activates the elec-

tronic control and defrost light. The compressor is turned off by

the thermistor temperature measurement. The blower will contin-

ue to run, causing air to flow through the evaporator coil and melt

the ice. When the ice is melted, the thermistor will end the defrost

cycle and the compressor will be started.

Disconnect dehumidifier from power supply. The hour meter uses

a battery backup for display when the dehumidifier is unplugged

and the hour button is depressed. To change the battery, it is nec-

essary  to  remove  the  four  (4)  screws  from  the  control  panel.

Disconnect the old battery and replace with new battery. Replace

control panel and screws. Do not overtighten screws.

Water Removal

The dehumidifier is equipped with an internal condensate pump

to remove the water that is collected from the air. This allows the

water to be pumped 20 feet with the attached hose. If the water

needs to be pumped more than 20 feet above the unit, a second

pump must be added to relay the water. The condensate pump

automatically purges for 20 seconds every four minutes.

Fig. 3

Fig. 4

Fig. 5

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.

WARNING

Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,

fire, or electrical shock.

Battery Replacement

(1)

Risque de choc électrique

Débranchez l'alimentation avant de remplacer la pile.
Le fait de ne pas suivre ces instructions peut entraîner la mort, 

un incendie ou un choc électrique.

Débranchez le déshumidificateur de son alimentation électrique. 

Le compteur d’heures utilise une pile de secours pour l’affichage 

lorsque le déshumidificateur est débranché et que le bouton des 

heures  est  enfoncé.  Pour  changer  la  pile,  il  est  nécessaire 

d’enlever les quatre (4) vis du panneau de contrôle. Débranchez 

l’ancienne pile et remplacez-la par une nouvelle. Remettez en place 

le panneau de contrôle et les vis. Ne serrez pas trop les vis.

Cycle de dégivrage

Lorsque de la glace s’accumule sur les serpentins, une thermistance 

active  le  contrôle  électronique  et  la  lumière  de  dégivrage.  Le 

compresseur est éteint par la mesure de la température par la 

thermistance.  Le  ventilateur  continue  de  fonctionner,  ce  qui  fait 

circuler à travers le serpentin de l’évaporateur l’air qui fait fondre 

la glace. Lorsque la glace est fondue, la thermistance met fin au 

cycle de dégivrage et le compresseur est mis en marche.

Indicateur de dégivrage (

Fig.

 5)

L’indicateur  de  dégivrage  s’allume  pour 

indiquer que le déshumidificateur est en 

cours  de  cycle  de  dégivrage.  Au  cours 

de  cette  période,  le  compresseur  ne 

fonctionne pas.

Fig. 1

Built in Electrical Safety

For your safety and protection this appliance is manufactured

with a grounded plug on its power cord. The power cord must

be plugged into a properly grounded receptacle. If a ground-

ed receptacle does not exist, have one installed by a certified

electrician. Do not cut or remove the grounding prong on the

power cord plug if equipped. We recommend that this electri-

cal  circuit/receptacle  operate  under  a  separate  breaker  or

fuse.
If an extension cord is required, it must have a minimum of

14  gauge  conductors  if  25  feet  long  or  less  and  12  gauge

conductors if greater than 25 feet long.

Electrical Requirements

For 115V operation, a common grounded outlet on a 15 amp

circuit is required. The dehumidifier draws approx. 8 amps at

80°F,  60%  RH.  If  used  in  a  wet  area,  a  ground  fault  inter-

rupter (GFI) is required.

Power Button (Fig. 1)

The  dehumidifier  is  turned  on  or  off  by

pressing  the  power  button.  When  the

dehumidifier is started, the hour meter will

display the cumulative hours. 

Pump Purge Button (Fig. 2)

In normal operation, the pump will automat-

ically empty the reservoir. Pressing this but-

ton allows manual emptying of the reservoir.

Press once, and the pump will operate for

20 seconds. Press and hold the button and

the pump will activate for 30 seconds.

Always manually purge the water reservoir

before  transport  or  storage.  Turn  off  the

power and allow the plugged in dehumidifier

to rest 5 minutes before the final purge.

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, 
fire, or electrical shock.

WARNING

Place dehumidifier inside area to be dried. Make sure all win-

dows and doors are closed to the outside and seal off the wet

area from any unaffected areas. Route condensate hose into

a  drain,  or  a  very  large  container.  Press  the  On/Off  button

(Fig. 1) to activate the dehumidifier.

OPERATION

Fig. 1

Fig. 2

Digital Hour Counter (Fig. 3)

The counter will accumulate and display the total running hours

of the unit in 1/10 of an hour. 

Hour Button (Fig. 4)

Press the HOURS button when the dehu-

midifier cannot be plugged in and the hour

meter  needs  to  be  read.  The  digital  hour

meter will display the last saved cumulative

time for ten seconds.

Defrost Indicator (Fig. 5)

The defrost indicator will light to indicate the

dehumidifier is in defrost cycle. During this

period, the compressor is not running.

Defrost Cycle

When ice builds up on the coils, a thermistor activates the elec-

tronic control and defrost light. The compressor is turned off by

the thermistor temperature measurement. The blower will contin-

ue to run, causing air to flow through the evaporator coil and melt

the ice. When the ice is melted, the thermistor will end the defrost

cycle and the compressor will be started.

Disconnect dehumidifier from power supply. The hour meter uses

a battery backup for display when the dehumidifier is unplugged

and the hour button is depressed. To change the battery, it is nec-

essary  to  remove  the  four  (4)  screws  from  the  control  panel.

Disconnect the old battery and replace with new battery. Replace

control panel and screws. Do not overtighten screws.

Water Removal

The dehumidifier is equipped with an internal condensate pump

to remove the water that is collected from the air. This allows the

water to be pumped 20 feet with the attached hose. If the water

needs to be pumped more than 20 feet above the unit, a second

pump must be added to relay the water. The condensate pump

automatically purges for 20 seconds every four minutes.

Fig. 3

Fig. 4

Fig. 5

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.

WARNING

Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,

fire, or electrical shock.

Battery Replacement

(1)

Fig. 2

Built in Electrical Safety

For your safety and protection this appliance is manufactured

with a grounded plug on its power cord. The power cord must

be plugged into a properly grounded receptacle. If a ground-

ed receptacle does not exist, have one installed by a certified

electrician. Do not cut or remove the grounding prong on the

power cord plug if equipped. We recommend that this electri-

cal  circuit/receptacle  operate  under  a  separate  breaker  or

fuse.
If an extension cord is required, it must have a minimum of

14  gauge  conductors  if  25  feet  long  or  less  and  12  gauge

conductors if greater than 25 feet long.

Electrical Requirements

For 115V operation, a common grounded outlet on a 15 amp

circuit is required. The dehumidifier draws approx. 8 amps at

80°F,  60%  RH.  If  used  in  a  wet  area,  a  ground  fault  inter-

rupter (GFI) is required.

Power Button (Fig. 1)

The  dehumidifier  is  turned  on  or  off  by

pressing  the  power  button.  When  the

dehumidifier is started, the hour meter will

display the cumulative hours. 

Pump Purge Button (Fig. 2)

In normal operation, the pump will automat-

ically empty the reservoir. Pressing this but-

ton allows manual emptying of the reservoir.

Press once, and the pump will operate for

20 seconds. Press and hold the button and

the pump will activate for 30 seconds.

Always manually purge the water reservoir

before  transport  or  storage.  Turn  off  the

power and allow the plugged in dehumidifier

to rest 5 minutes before the final purge.

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, 
fire, or electrical shock.

WARNING

Place dehumidifier inside area to be dried. Make sure all win-

dows and doors are closed to the outside and seal off the wet

area from any unaffected areas. Route condensate hose into

a  drain,  or  a  very  large  container.  Press  the  On/Off  button

(Fig. 1) to activate the dehumidifier.

OPERATION

Fig. 1

Fig. 2

Digital Hour Counter (Fig. 3)

The counter will accumulate and display the total running hours

of the unit in 1/10 of an hour. 

Hour Button (Fig. 4)

Press the HOURS button when the dehu-

midifier cannot be plugged in and the hour

meter  needs  to  be  read.  The  digital  hour

meter will display the last saved cumulative

time for ten seconds.

Defrost Indicator (Fig. 5)

The defrost indicator will light to indicate the

dehumidifier is in defrost cycle. During this

period, the compressor is not running.

Defrost Cycle

When ice builds up on the coils, a thermistor activates the elec-

tronic control and defrost light. The compressor is turned off by

the thermistor temperature measurement. The blower will contin-

ue to run, causing air to flow through the evaporator coil and melt

the ice. When the ice is melted, the thermistor will end the defrost

cycle and the compressor will be started.

Disconnect dehumidifier from power supply. The hour meter uses

a battery backup for display when the dehumidifier is unplugged

and the hour button is depressed. To change the battery, it is nec-

essary  to  remove  the  four  (4)  screws  from  the  control  panel.

Disconnect the old battery and replace with new battery. Replace

control panel and screws. Do not overtighten screws.

Water Removal

The dehumidifier is equipped with an internal condensate pump

to remove the water that is collected from the air. This allows the

water to be pumped 20 feet with the attached hose. If the water

needs to be pumped more than 20 feet above the unit, a second

pump must be added to relay the water. The condensate pump

automatically purges for 20 seconds every four minutes.

Fig. 3

Fig. 4

Fig. 5

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.

WARNING

Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,

fire, or electrical shock.

Battery Replacement

(1)

Fig. 4

Built in Electrical Safety

For your safety and protection this appliance is manufactured

with a grounded plug on its power cord. The power cord must

be plugged into a properly grounded receptacle. If a ground-

ed receptacle does not exist, have one installed by a certified

electrician. Do not cut or remove the grounding prong on the

power cord plug if equipped. We recommend that this electri-

cal  circuit/receptacle  operate  under  a  separate  breaker  or

fuse.
If an extension cord is required, it must have a minimum of

14  gauge  conductors  if  25  feet  long  or  less  and  12  gauge

conductors if greater than 25 feet long.

Electrical Requirements

For 115V operation, a common grounded outlet on a 15 amp

circuit is required. The dehumidifier draws approx. 8 amps at

80°F,  60%  RH.  If  used  in  a  wet  area,  a  ground  fault  inter-

rupter (GFI) is required.

Power Button (Fig. 1)

The  dehumidifier  is  turned  on  or  off  by

pressing  the  power  button.  When  the

dehumidifier is started, the hour meter will

display the cumulative hours. 

Pump Purge Button (Fig. 2)

In normal operation, the pump will automat-

ically empty the reservoir. Pressing this but-

ton allows manual emptying of the reservoir.

Press once, and the pump will operate for

20 seconds. Press and hold the button and

the pump will activate for 30 seconds.

Always manually purge the water reservoir

before  transport  or  storage.  Turn  off  the

power and allow the plugged in dehumidifier

to rest 5 minutes before the final purge.

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, 
fire, or electrical shock.

WARNING

Place dehumidifier inside area to be dried. Make sure all win-

dows and doors are closed to the outside and seal off the wet

area from any unaffected areas. Route condensate hose into

a  drain,  or  a  very  large  container.  Press  the  On/Off  button

(Fig. 1) to activate the dehumidifier.

OPERATION

Fig. 1

Fig. 2

Digital Hour Counter (Fig. 3)

The counter will accumulate and display the total running hours

of the unit in 1/10 of an hour. 

Hour Button (Fig. 4)

Press the HOURS button when the dehu-

midifier cannot be plugged in and the hour

meter  needs  to  be  read.  The  digital  hour

meter will display the last saved cumulative

time for ten seconds.

Defrost Indicator (Fig. 5)

The defrost indicator will light to indicate the

dehumidifier is in defrost cycle. During this

period, the compressor is not running.

Defrost Cycle

When ice builds up on the coils, a thermistor activates the elec-

tronic control and defrost light. The compressor is turned off by

the thermistor temperature measurement. The blower will contin-

ue to run, causing air to flow through the evaporator coil and melt

the ice. When the ice is melted, the thermistor will end the defrost

cycle and the compressor will be started.

Disconnect dehumidifier from power supply. The hour meter uses

a battery backup for display when the dehumidifier is unplugged

and the hour button is depressed. To change the battery, it is nec-

essary  to  remove  the  four  (4)  screws  from  the  control  panel.

Disconnect the old battery and replace with new battery. Replace

control panel and screws. Do not overtighten screws.

Water Removal

The dehumidifier is equipped with an internal condensate pump

to remove the water that is collected from the air. This allows the

water to be pumped 20 feet with the attached hose. If the water

needs to be pumped more than 20 feet above the unit, a second

pump must be added to relay the water. The condensate pump

automatically purges for 20 seconds every four minutes.

Fig. 3

Fig. 4

Fig. 5

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.

WARNING

Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,

fire, or electrical shock.

Battery Replacement

(1)

Fig. 5

Built in Electrical Safety

For your safety and protection this appliance is manufactured

with a grounded plug on its power cord. The power cord must

be plugged into a properly grounded receptacle. If a ground-

ed receptacle does not exist, have one installed by a certified

electrician. Do not cut or remove the grounding prong on the

power cord plug if equipped. We recommend that this electri-

cal  circuit/receptacle  operate  under  a  separate  breaker  or

fuse.
If an extension cord is required, it must have a minimum of

14  gauge  conductors  if  25  feet  long  or  less  and  12  gauge

conductors if greater than 25 feet long.

Electrical Requirements

For 115V operation, a common grounded outlet on a 15 amp

circuit is required. The dehumidifier draws approx. 8 amps at

80°F,  60%  RH.  If  used  in  a  wet  area,  a  ground  fault  inter-

rupter (GFI) is required.

Power Button (Fig. 1)

The  dehumidifier  is  turned  on  or  off  by

pressing  the  power  button.  When  the

dehumidifier is started, the hour meter will

display the cumulative hours. 

Pump Purge Button (Fig. 2)

In normal operation, the pump will automat-

ically empty the reservoir. Pressing this but-

ton allows manual emptying of the reservoir.

Press once, and the pump will operate for

20 seconds. Press and hold the button and

the pump will activate for 30 seconds.

Always manually purge the water reservoir

before  transport  or  storage.  Turn  off  the

power and allow the plugged in dehumidifier

to rest 5 minutes before the final purge.

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, 
fire, or electrical shock.

WARNING

Place dehumidifier inside area to be dried. Make sure all win-

dows and doors are closed to the outside and seal off the wet

area from any unaffected areas. Route condensate hose into

a  drain,  or  a  very  large  container.  Press  the  On/Off  button

(Fig. 1) to activate the dehumidifier.

OPERATION

Fig. 1

Fig. 2

Digital Hour Counter (Fig. 3)

The counter will accumulate and display the total running hours

of the unit in 1/10 of an hour. 

Hour Button (Fig. 4)

Press the HOURS button when the dehu-

midifier cannot be plugged in and the hour

meter  needs  to  be  read.  The  digital  hour

meter will display the last saved cumulative

time for ten seconds.

Defrost Indicator (Fig. 5)

The defrost indicator will light to indicate the

dehumidifier is in defrost cycle. During this

period, the compressor is not running.

Defrost Cycle

When ice builds up on the coils, a thermistor activates the elec-

tronic control and defrost light. The compressor is turned off by

the thermistor temperature measurement. The blower will contin-

ue to run, causing air to flow through the evaporator coil and melt

the ice. When the ice is melted, the thermistor will end the defrost

cycle and the compressor will be started.

Disconnect dehumidifier from power supply. The hour meter uses

a battery backup for display when the dehumidifier is unplugged

and the hour button is depressed. To change the battery, it is nec-

essary  to  remove  the  four  (4)  screws  from  the  control  panel.

Disconnect the old battery and replace with new battery. Replace

control panel and screws. Do not overtighten screws.

Water Removal

The dehumidifier is equipped with an internal condensate pump

to remove the water that is collected from the air. This allows the

water to be pumped 20 feet with the attached hose. If the water

needs to be pumped more than 20 feet above the unit, a second

pump must be added to relay the water. The condensate pump

automatically purges for 20 seconds every four minutes.

Fig. 3

Fig. 4

Fig. 5

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.

WARNING

Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,

fire, or electrical shock.

Battery Replacement

(1)

Déshumidificateur industriel

Summary of Contents for EDP150LR

Page 1: ...ateur industriel Deshumidificador industrial Owner s Manual OPERATION AND MAINTENANCE MANUAL Industrial Dehumidifier Déshumidificateur industriel Deshumidificador industrial Operating Instructions Guide d utilisation Read an The Instruc Lise conserv instruc Lea y g est instruc 1 3 Models Modèles Modelos EDP150LR EDP180CR EDP190LR EDP250CR ...

Page 2: ...es not exist have one installed by a certified electrician Do not cut or remove the grounding prong on the power cord plug if equipped We recommend that this electri cal circuit receptacle operate under a separate breaker or fuse Electrical Requirements For 115V operation a common grounded outlet on a 15 amp circuit is required The dehumidifier draws approx 8 amps at 80 F 60 RH If used in a wet ar...

Page 3: ...AUTION Do not operate unit without the front hood secured in place The serial data plate is located on the underside of the dehumid ifier For service information contact 1 800 565 3548 2 Storage Freezing temperatures and biological growth must be consid ered before storing the dehumidifier The dehumidifier should be flushed with a biofungicide before storing When storing the unit ensure that water...

Page 4: ... temperature and Relative Humidity have dropped Check levels with calibrated humidity meter and or thermostat Unit is in defrost cycle Unit will start after cycle Air filter dirty or airflow obstructed Unit should have a minimum of 10 clearance all around it Clean air filter and ensure adequate airflow space around unit Evaporator coils dirty Clean coils Restrictive or kinked exhaust ducting if us...

Page 5: ...5 WIRING DIAGRAMS EPD150LR EPD180CR EPD190LR EPD250CR ...

Page 6: ...or warranty claims Please retain bills of sale for proof 5 Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This warranty gives specific legal rights and the purchaser may have other rights which vary from state to state For more information regarding legal rights the purchaser may contact the loca...

Page 7: ...cord must be plugged into a properly grounded receptacle If a ground ed receptacle does not exist have one installed by a certified electrician Do not cut or remove the grounding prong on the power cord plug if equipped We recommend that this electri cal circuit receptacle operate under a separate breaker or fuse Electrical Requirements For 115V operation a common grounded outlet on a 15 amp circu...

Page 8: ...WARNING The dehumidifier uses a high pressure refrigerant system and high voltage circuitry which could present a health hazard resulting in death serious bodily injury and or property damage Only qualified service people should service this unit CAUTION Do not operate unit without the front hood secured in place The serial data plate is located on the underside of the dehumid ifier For service in...

Page 9: ... l air et l humidité relative ont baissés Vérifiez la température et l humidité relative avec un hygromètre calibré et ou un thermostat L appareil est en cycle de dégivrage L appareil recom mencera après le cycle Filtre à air est sale ou le passage d air est obstrué L appareil devrait avoir un espace minimum vide de 10po tout autour Nettoyez le filtre à air et assurez un passage d air adéquat espa...

Page 10: ...10 SCHÉMAS ÉLECTRIQUES EPD150LR EPD180CR EPD190LR EPD250CR ...

Page 11: ...ains États ne permettent pas l exclusion ou la limitation des dommages consécutifs ou indirects de sorte que la limitation ou l exclusion ci dessus pourrait ne pas s appliquer à vous Cette garantie donne des droits légaux particuliers à l acheteur et celuici peut avoir d autres droits qui varient d un État à l autre Pour de plus amples informations concernant ses droits l acheteur peut communiquer...

Page 12: ...grounded plug on its power cord The power cord must be plugged into a properly grounded receptacle If a ground ed receptacle does not exist have one installed by a certified electrician Do not cut or remove the grounding prong on the power cord plug if equipped We recommend that this electri cal circuit receptacle operate under a separate breaker or fuse If an extension cord is required it must ha...

Page 13: ...e circuitry which could present a health hazard resulting in death serious bodily injury and or property damage Only qualified service people should service this unit CAUTION Do not operate unit without the front hood secured in place The serial data plate is located on the underside of the dehumid ifier For service information contact 1 800 565 3548 2 Almacenamiento Considere posibles condiciones...

Page 14: ...mación de garantía será preciso contar con una prueba de compra con fecha Recuerde guardar el recibo como comprobante de venta 5 En algunos estados no se permite la exclusión o limitación de daños consecuentes o secundarios en estos casos la limitación anterior podría no aplicar a su caso Esta garantía ofrece dere chos legales específicos el comprador puede contar con otros diferentes dependiendo ...

Page 15: ...15 ...

Page 16: ...onents and specifica tions to maintain their technological leadership position United States 10048 Industrial Blvd Lenexa KS 66215 Phone 800 747 1762 913 752 6000 Fax 800 487 9915 913 752 6466 www fantech net info fantech net Canada 50 Kanalflakt Way Bouctouche NB E4S 3M5 Phone 800 565 3548 506 743 9500 Fax 877 747 8116 506 743 9600 Distributed by ...

Reviews: