Fantech DBF110 Installation And Operation Manual Download Page 4

4

fantech

Installation guidelines

Fan and Switch Mounting 

The DBF110 is to be mounted a minimum of 5 linear (not equivalent) feet 
from the dryer outlet. A secondary lint trap (DBLT 4W) is recommended 
if the fan is installed between 5 and 15 linear (not equivalent) feet from 
the dryer outlet in applications, where excessive dryer lint generation is 
likely or to increase the time interval between routine maintenance of the 
Dryer Booster Fan (See illustration to left). An NB mounting bracket 
attached to a rafter or joist should be used to stabilize the fan. Although 
not recommended, a vertical rigid duct may support the fan if the duct is 
securely stabilized. (Consult local codes prior to supporting the fan in the 
duct alone.) Duct work should be attached to the inlet and outlet of the 
fan by means of FC vibration isolation clamps (not included) or duct tape. 
The duct connection should be properly sealed to prevent leakage and 
loss of fan performance. Flex duct connections between the dryer duct 
connection and exhaust duct should be stretched as smooth as possible.

Calculating Duct Run

To calculate the length of your planned duct run, measure from the dryer 
to external venting point in roof or wall. For each bend or elbow add 5-7 
feet to your total duct run calculations. The DBF110 can be used on runs 
up to 108 feet.

Pressure Sensor Switch Operation 

Fantech’s DBF110 is equipped with Fantech's Patented DB10 pressure 
switch. The DB10 is a positive pressure sensing switch which  
recognizes dryer operation and activates the booster fan from an  
independent electrical circuit. This eliminates connections through the 
dryer circuit which may void the manufacturers’ warranty as well as 
manual systems which require the attention of the operator or costly 
current/temperature sensing systems. 
The electricity to the booster fan is connected in series through a  
normally open terminal on the switch. A pressure tap is connected to a 
fitting on the side of the switch. When the dryer begins operation, 
positive pressure in the duct causes the switch diaphragm to expand, 
closing the circuit to the booster fan. An integral delay-on-break timer in 
the switch will cycle the fan on for intervals of 10 minutes. This will con-
tinue until the dryer has stopped and the timer delay period has lapsed. 
Drying cycles, the booster fan, the delay timer and the pressure switch 
are not adversely affected by the starting/stopping intervals.

Dimensional Data

121/2”

111/4”

91/2”

91/2”

37/8”

Illustration 1

DBF110

Alternative Location

Secondary Lint Trap

12-o-clock

2-o-clock

10-o-clock

Sensitivity Adjustment Instruction

a. Disconnect power to the booster fan.
b. Looking from the inlet (dryer side), the switch should be at the 

12-o-clock position.

c. Remove the 2 mounting screws holding the switch to the fan.
d. Rotate the switch to the 

10-o-clock position for less sensitivity

 or 

2-o-clock position for more sensitivity

 then secure it there, you may 

have to adjust (bend) the bracket to fit. Secure the switch with the 
2 screws previously removed.

e. Apply power to the fan and check for operation.

Dimensions are in inches.

Summary of Contents for DBF110

Page 1: ...icateur de s choir Booster Secadora DBF110 Kit Includes Dryer Booster Fan 1 pc Fan Mounting Bracket and Hardware 1 pc Small Wall Sign Indicating Proper Operation Procedure 1 pc La trousse du DBF110 in...

Page 2: ...a unidad tiene piezas rotativas hay que tomar precauciones de seguridad durante la instalaci n operaci n y mantenimiento 3 PRECAUCION S lo para Ventilaci n en General No trate de Utilizarse como Extra...

Page 3: ...ements Suivez les instructions donn es et les normes de s curit communiqu es par le fabricant telles que celles publi es par l Association nationale de protection contre les incendies National Faire P...

Page 4: ...itive pressure sensing switch which recognizes dryer operation and activates the booster fan from an independent electrical circuit This eliminates connections through the dryer circuit which may void...

Page 5: ...isolate any vibration and prevent the transmission of sound through the structure Be careful not to overtighten Fan mounting can be in any angle see ill 2 however vertical mounting is recommended to...

Page 6: ...do this the capacitor and pressure switch must be disconnected do not test the capacitor it will not meter continuity If motor leads show continuity rewire the fan capacitor and pressure switch 4 Turn...

Page 7: ...u rupteur de d tection de la pression Le DBF110 est equipep avec le mano contact DB10 brevet de Fantech Le DB10 de Fantech est un rupteur de d tection de pression positive qui identifie le fonctionnem...

Page 8: ...ire l accumulation de condensation dans le ventilateur Si un montage vertical s av re n cessaire et que l accumulation de condensation se r v le tre un probl me potentiel le per age d un trou d enviro...

Page 9: ...ra mesur e Si les fils d amen e indiquent une continuit rec blez le ventilateur le capaciteur et le rupteur de pression 4 Rebranchez l alimentation lectrique et red marrez le cycle du s choir V rifiez...

Page 10: ...nexiones deben sellarse adecuadamente para impedir fugas y p rdida de rendimiento del ventilador Las conexiones flexibles del conducto entre la conexi n de la secadora y el conducto de escape se deben...

Page 11: ...servicio Vea las ilustraciones anteriores Paso 2 Soporte para Montaje Utilice los tornillos tirafondo para fijar el soporte de montaje a una viga en el sitio seleccionado El soporte est provisto de an...

Page 12: ...los contactos del motor del ventilador Para esto hay que desconectar el capacitor y el interruptor de presi n No compruebe el capacitor ya que el mismo no da continuidad Si los contactos del motor ti...

Page 13: ...allation for any breach of warranty WARRANTY VALIDATION The user must keep a copy of the bill of sale to verify purchase date These warranties give you specific legal rights and are subject to an appl...

Page 14: ...un d faut d usine en mati re de qualit d ex cution ou de mat riau Il sera peut tre n cessaire de retourner le produit l usine Fantech accompagn d une copie du contrat de vente et du num ro d autorisat...

Page 15: ...talaci n o reinstalaci n por incumplimiento de la garant a VALIDACI N DE LA GARANT A El usuario debe conservar una copia de la constancia de compraventa para verificar la fecha de compra Estas garant...

Page 16: ...net Fantech Fantech se r serve le droit de faire des changements techniques Pour de la documentation jour s il vous pla t se r f rer au www fantech net Fantech se reserva el derecho de hacer modifica...

Reviews: