background image

 

 

       

ISO 9001:2008

 

www.fanox.com  

                SIAC116B1011AB_Rev. 05        

                                   4 / 32 

 
 

1.3. 

Powering the relay up with kitcom 

Thanks to the external battery KITCOM the powering and adjusting process of the relay is 
very easy and it allows the user to test the relay. 
 
The power comes from two AA batteries (IEC LR06)  of 1.5 Volts placed  at the  bottom of 
the kitcom. The equipment has a small Dc/Dc power supply that raises the voltage till the 
required  12  volts  to  operate  the  equipment  and  that  is  plugged  into  the  front  RS232 
communications port (KITCOM). 
Once the KITCom is connected, the relay will be switched on and a led on the right of the 
relay (led battery) will blink indicating the relay is powered on through an external battery 
(KITCOM). 

 

The  relay  is  totally  maintenance  free.  This  is,  there  is  no  need  of  batteries  to  log  events 
and fault reports and there is no need of batteries to maintain date and time. 

NOTE

:  Date  and  time  must  be  correctly  set  the  first  time  the  relay  is  operative  and 

energy must be kept at least “1 hour” to maintain the RTC for 72 hours once the energy is 
lost.  

Besides,  the  possibility  of  using  external  battery  power,  together  with  the  possibility  of 
activating the trip contact from the test menu, allows the trip circuit to be tested before the 
transformation  center  is  powered  up.  So,  it  is  clear  the  KITCOM  useful  for  cases  like 
commissioning operations, discharges and repairs to the transformation center. 

Using battery power does not block the RS232 communications port, as it can be used 
simultaneously. 

 

Once the relay is poowerd through the Kitcom, it should be checked: 

 

Model 

Directly, complete model on top line and phases/neutral current measurement 

on bottom line are displayed. Once “C” key is pressed the the name of phase and neutral 

currents (instead the complete model) is displayed on the top of LCD Standby screen. 

     

 

 Serial Number 

  

In “General Settings” menu serial number of 8 digits can be checked 

(OK - 

▼ - ▼ - ◄ - ▼ - ▼) 

 

 

 Firmware Version  

  

In “Firmware Version” menu (HOLD ▲) 

 

Summary of Contents for SIA C Series

Page 1: ...www fanox com SIAC116B1011AB_Rev 05 1 32 ISO 9001 2008 INSTALLATION COMMISSIONING GUIDE SIA C Self Dual Power O C E F Protection Relay...

Page 2: ...s 9 3 FUNCTIONAL DIAGRAM 9 4 TECHNICAL SPECIFICATIONS 10 4 1 IEC60255 151 Curves 12 4 2 IEEE Curves 13 5 OPENING MECHANISM 14 6 PROGRAMMABLE LOGIC CONTROL 15 7 FLOWCHART 16 7 1 Test menu 16 7 2 Direct...

Page 3: ...tocol is a certificate that relay has passed all factory testing process with correct results In case some fault is detected consider to put into quarantine period the relay and contact Fanox for furt...

Page 4: ...time NOTE Date and time must be correctly set the first time the relay is operative and energy must be kept at least 1 hour to maintain the RTC for 72 hours once the energy is lost Besides the possibi...

Page 5: ...1 3 2 Test menu NOTE When performing test menu protection won t be available and it will possible to open circuit breaker Only authorized personnel can do this job Press sequentially and hold OK The...

Page 6: ...cover from the battery compartment 4 Remove the battery and replace it respecting polarity facing up Battery characteristics o AA 3 6V lithium battery o Model LS14500 from SAFT o Do not use rechargea...

Page 7: ...utput for measurement power supply D13 Digital output 2 NC A5 Phase C current input for measurement power supply D14 Digital 2 common output A6 Phase C current output for measurement power supply D15...

Page 8: ...ary power Activated LED blinking if it detects the auxiliary voltage LED 2 Self power Activated LED blinking if it detects the self power current LED 3 Battery Activated LED blinking if it detects vol...

Page 9: ...Status and measurements Settings Events Permission to Change settings Download and Delete the Events buffer Permission to Execute Commands Permission to Change Configuration Permission to Change Prot...

Page 10: ...whichever is greater Function 50N G Permission yes no Operating range 0 10 to 30 x In step 0 01 x In Operating time 0 02 to 300 s step 0 01 s Activation level 100 Deactivation level 95 Instantaneous...

Page 11: ...LSES OR4_TIMERUP OR4_PULSE NOR4 AND4_LATCH NOR4_TIMERUP NOR4_PULSE AND4 AND4_PULSES AND4_TIMERUP AND4_PULSE NAND4 NAND4_TIMERUP NAND4_PULSE NOR4_PULSES Fault reports 20 fault reports 16 events in each...

Page 12: ...255 151 Inverse Curve Very Inverse Curve Extremely Inverse Curve Long time Inverse Curve There is a general mathematical equation that defines the time in seconds as a function of the current K D B Q...

Page 13: ...owing curves Inverse Curve Very Inverse Curve Extremely Inverse Curve Which relate to the parameters figuring in the following table Parameters A P B Ext Inverse 28 2 2 0 1217 Very Inverse 19 61 2 0 4...

Page 14: ...o if a lower level that the required by the striker is adjusted it may result on tripping without enough energy and not activating the striker On the other hand if a higher level that the required by...

Page 15: ...t 3 NOTE As it is described above the options NOR4_LATCH and NAND4_LATCH are not available in the relay Although using SICOM software allows the user to configure these options the relay will not reco...

Page 16: ...s can be used to navigate through the different menu items Each item can be activated or deactivated by pressing OK on it if the item is deactivated it is activated by pressing OK if the item is activ...

Page 17: ...en Use the and keys to position the cursor over the digit that you want to change and assign a value to this digit using the and keys Once the date time has been entered press OK to change the equipme...

Page 18: ...u MEASUREMENTS and press key to overview the rest of the menus in the relay To return to standby screen press C key It is also possible to access to Fault reports by pressing key From the standby mode...

Page 19: ...the setting name is its value States menu indicates the stuses of the relay activated or deactivated at real time From the standby mode screen press the OK key to access the first line of menus Use th...

Page 20: ...nction The parameters to adjust are Permission The function is available to work only if the permission is YES While this permission is NO the function will never be activated and the relay will not t...

Page 21: ...T Phase ratio and CT Neutral ratio general settings is the result given by dividing the number of turns on the primary winding by the number on the secondary winding For example With CT 500 5 the sett...

Page 22: ...sition of the event within the list Caused by activation or reset Associated measurement To delete the events from the relay it is necessary to insert the password 5555 from the events menu After the...

Page 23: ...rt the password 5555 from the demand menu From the standby mode screen press the OK key to access the first line of menus Use the and keys to position the cursor over the FAULT REPORT screen Press OK...

Page 24: ...al Standards 3xIn continuously 20xIn during 10 seconds 70xIn during 1 seconds In the following table the different injection modes are described CURRENT GENERATION INJECTION MODE INJECTION SYSTEM RELA...

Page 25: ...it for testing purpose Adjust manually current generation value without injecting current to relay for not stressing it during adjustment process Be sure that relay output contact is connected to gene...

Page 26: ...Sverker current generator with HOLD 0 1xIn and suddenly inject it to the relay as it would happened in real situation when circuit breaker is close powering network line 8 2 3 Verification of Leds Si...

Page 27: ...inject it to the relay as it would happened in real situation when circuit breaker is close powering network line From this value increase the current to achieve the function pick up and the function...

Page 28: ...d Output 2 is activated Trip flag is activated TEST 2 Settings Permission YES Curve IEC Inverse Dial 1 TAP 0 5xIn Theoretical tripping time 4 98 seconds fault current 2xIn The following information wi...

Page 29: ...fault current 1xIn The following information will be checked Trip output is activated Output 3 is activated Trip flag is activated TEST 3 Settings Permission YES Curve IEC Inverse Dial 1 TAP 0 3xIn Th...

Page 30: ...g checking OK NOK DB9 communication port OK NOK Signalling and Keypad Led 1 OK Led 2 OK Led 3 OK Trip OK Trip Output OK Output 2 OK Output 3 OK Keypad OK Self power 3P SIAC 0 1In Phase A OK Phase B OK...

Page 31: ...ISO 9001 2008 www fanox com SIAC116B1011AB_Rev 05 31 32 NOTES...

Page 32: ...ISO 9001 2008 www fanox com SIAC116B1011AB_Rev 05 32 32...

Reviews: