7.3.7. Fault reports menu
7.3.8. LDP menu
From the standby mode screen, press the “OK” key to
acces
s the first line of menus. Use the “▲” and “▼” keys
to position the cursor over the “FAULT REPORT” screen.
Press "OK" and use the “▲” and “▼” keys to position the
cursor over the faults.
Once it is a
ccessed to a fault report, press “OK”, to
visualize the cause which has originated the fault report.
Pressing “OK” again it is accessed to the registered
events that are related with that fault report. The first
event is the activation of the fault report. To visualize the
rest events, use “▼” key.
How to delete fault reports
To delete the fault reports from the relay it is necessary to
insert the password 5555 from the fault report menu.
SIA-B relay provides the demand of current (LDP
– Load
Data Profiling) with the following characteristics:
•
Number of records: 168
•
Recording mode circular
•
Sampling rate (interval): configurable through
communications: 1
– 60 min
•
Record format:
Date/Time; IMAX (in interval); IMAX (actual)
IA; IB; IC; IN
From the standby mode screen, press the “OK” key to
acces
s the first line of menus. Use the “▲” and “▼” keys
to position the cursor over the “LDP” screen. Press "OK"
and use the “▲” and “▼” keys to position the cursor over
the faults.
How to delete the Load data profiling
To delete the demand from the relay it is
necessary to insert the password 5555 from the
demand menu.