ENTER IN THE SETUP
From the measures visualization, press at the same time the 

A

 and 

C

 keys, the message 

SeT Up

 will appear on the 

F

 displays. 

CHOOSE THE DIGITAL OUTPUT TO PROGRAM
Press repeatedly the 

C

 key until the message 

SET DO1

 (DO1 output) or 

SET DO2

 (DO2 output) appears on the 

F

display. Press the 

A

 key to select this setting. 

SELECT THE MODALITY OF FUNCTIONING OF THE DIGITAL OUTPUT
To select the functioning mode, using the 

B

 and 

C

 keys, it’s possible to select: 

PULSE

 (pulse emission), 

ALR SYS 

3PH

, (alarm on three phase value), 

ALR  PH_  123

 (alarm on minimum and maximum single phase value) and 

BY_ REMOTE

 (the digital output is managed using serial output). Press 

A

 key to confirm. 

CHOOSE THE PARAMETER TO LINK TO THE DIGITAL OUTPUT
With an alarm modality set, it’s necessary to select the parameters associated to the alarm output; by pressing the 

B

and

C

 keys until the parameter choice appears on the third part (L3) of 

F

 display and the glowing the corresponding 

led on the 

D

 bar. Press 

A

 key to confirm the set. 

SET THE HIGH AND THE LOW THRESHOLDS
On

F

 display will appear the message 

ALR Hi

 with the high threshold value; confirming with the 

A

 key on the same 

display will appear the message 

ALR LO

 with low threshold value. The 

B

 (to increase) and 

C

 (to decrease) keys are 

used to set the high and the low thresholds values. The range depends by the parameter and it is linked to the CT and 
VT ratios. Pressing 

A

 key to confirm. 

The threshold set is linked with CT and VT ratios, for this reason it’s necessary to make this operation after the 
programming of the CT and VT. The end scale value must be confirmed when CT and VT ratios are modified. 
The low threshold will be lower than high threshold. If the high threshold is set as OFF the low threshold will have the 
range of the high threshold. 
SET THE DELAY TO THE DIGITAL OUTPUT ACTIVATION
Now it’s possible to set the delay that will pass between the alarm condition set and the activation of digital output. On 

F

 display will appear 

ALR DLY

 and the value expressed in seconds (range 1÷900). The modification of the value is 

done in the same way of the threshold set. With the confirmation (

A

 key) the set is complete. 

The programming will be referred to the digital output indicated on 

G

 display (

DO1

 o 

DO2

).

www.fanox.com

[email protected]

Tel: 0034 94 471 14 09

Fax: 0034 94 471 05 92

Pag 9

Summary of Contents for EMM-7

Page 1: ...tion digital output serial output RS485 insulated current inputs neutral current input digital input alternative to analog Output option MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N 6 V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 6 V L L phase and three phase currents A kA A L1...

Page 2: ...0 60Hz 1 3 20 60Vac 24 72Vdc 1 3 85 230Vac 90 250Vdc It s possible for example to take the auxiliary power supply between phase and neutral in a 4 wires system or phase phase in a 3 wires system without neutral or from a VT in a medium voltage application measure voltage inputs 4 terminals are available for the connection to the 3 phase and neutral of the network of measure the maximum voltage pha...

Page 3: ...ires without neutral or with neutral not supplied the N terminaln must not be connected INSERTION ON THREE PHASE LINE WITH 4 WIRES EMM EMM imeasure voltage inputs Voltage insertion with 3 VT N L1 L2 L3 VL1 VL2 VL3 N P1 P2 S1 S2 S2 S1 In EMM with internalCT with Ineutral option CT connection to read the neutral current Digital Outputs DO1 output if used as PULSE is linked to the ACTIVE ENERGY count...

Page 4: ...energy counters Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x 1000 Using the C key the display indicates the type of the energy displayed Using the A and B keys the disp...

Page 5: ...output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with serial output seT ID ADR Increase Set address of network from 001 to 247 Decrease seT SER BDR Set baud rate 19200 baud 19 2 serial interface 9600 baud 9 60 version with serial output 48...

Page 6: ...ing of the average time seT AVG T After the programming phase previously described pressing another time the A key on the F display will appear the message AVG T and the average time settable from 1 to 30 minutes To increase the value press the B key To decrease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximu...

Page 7: ...is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instrument at the enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page of Setup SETUP It s always possible to come back to measures visualiza...

Page 8: ...ital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the minimum threshold set ALR LO The activation of the alarm output will come after some seconds of delay set ALR DL In the REMOTE mode the output status will be decided from the status of the corr...

Page 9: ...OLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with low threshold value The B to increase and C to decrease keys are used to set the high and the low thresholds values The range depends by the parameter and it is linked to the CT and VT ratios Pressing A key to confirm The threshold set is ...

Page 10: ...ll appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will appear the parameter to link to the analog output and selectable pressing more time the B key Pressing the A key to confirm the parameter selected SET THE HIGH AND THE LOW THRESHOLD Now it s necessary to set the end scale value high limit ...

Page 11: ...part L1 the status of digital input on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output DO2 The visualization of the digital input status activated that is supplied and deactivated that is not supplied depends of the type of energy visualization NORMAL TOT PAR e TB1 TB2 With NORMAL the digital input will be indicated with ON...

Page 12: ... of the three phase system the frequency is of the L1 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in correspondence of the kWh and KVArh on the front panel turn on to indicate the visualization of the active and reactive energy counters The led...

Page 13: ... max avg I L3 max avg I N max avg phase and neutral currents maximum of average phase and neutral currents max demand max maxD avg 6 W max avg 6 VAr max avg 6 VA max avg three phase power maximum of average three phase powers maximum demand max maxD avg I L1 avg I L2 avg I L3 avg I N avg phase and neutral currents average phase and neutral currents max maxD avg 6 W avg 6 Var avg 6 VA avg three pha...

Page 14: ...the manual of EMI1 serial converter EIA485 INTERFACE COMUNICATION RS485 It is possible to exchange information between the instrument and a PC PLC or other compatible system through the asynchronous serial line RS485 The interface EIA485 allows a multi drop connection in order to connect various instruments in the same network The maximum suggested length for a RS485 connection is 1200m For longer...

Page 15: ...instruction manual IM442 EU F v0 4 pag 15 DIMENSIONS 96 96 81 14 9 90 92 92 R3 cut out panel flush mounting for panel DIN 43700 www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 15 ...

Page 16: ...with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse Pulse duration 100 200 300 400 500 milliseconds selectable DO1 active energy pulse output accumulated Tb1 Tb2 DO2 reactive energy pulse output accumulated Tb1 Tb2 digital Input Changing time band function or reset partial counters Opto isolated input Insulation 2500 V...

Reviews: