background image

- 1 -

LE-03d

Electric energy meter,

3-phase

Directive MID 

2014/32/EU

Certificate number 

0120/SGS0119

The LE-03d is a static (electronic) calibrated electricity meter of 

three-phase alternating current in a semidirect system.

A special electronic system under the influence of flowing cu-

rrent and applied voltage in each phase generates pulses pro-

portional to the energy drawn in the respective phase. Energy 

consumption in the phase is indicated by a flashing of correspon-

ding LED (A, B, C). The sum of the three phase pulses is indicated 

by a flashing LED and converted into energy absorbed througho-

ut the three-phase system. Its value is displayed by the segment 

LCD display. 

The fractional digit represent the decimal (.1 kWh = 100 Wh).

Compliance

Purpose

Functioning

F&F Filipowski sp. j.

Konstantynowska 79/81, 95-200 Pabianice, POLAND

phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71

www.fif.com.pl; e-mail: [email protected]

Do not dispose of this device in the trash along with other waste! 

According to the Law on Waste, electro coming from households free of charge and can 

give any amount to up to that end point of collec� on, as well as to store the occasion of 

the purchase of new equipment (in accordance with the principle of old-for-new, regard-

less of brand). Electro thrown in the trash or abandoned in nature, pose a threat to the 

environment and human health.

Summary of Contents for LE-03d

Page 1: ...into energy absorbed througho ut the three phase system Its value is displayed by the segment LCD display The fractional digit represent the decimal 1 kWh 100 Wh Compliance Purpose Functioning F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48 42 227 09 71 www fif com pl e mail biuro fif com pl Donotdisposeofthisdeviceinthetrashalongwithotherwaste Accord...

Page 2: ...o connect a pulse meter reading pulses generated by the counter For proper operation of the indicator is not required to connect additional devices The meter has sealable input and output terminal covers to pre vent any attempts to bypass the meter Measured value Pulse output Sealing ...

Page 3: ... 3 The meter is marked with individual serial number allowing its unambiguous identification The marking is laser engraved and cannot be removed Meter number Front description ...

Page 4: ...terminals 1 L1 3 L2 5 L3 4 Connect the measured circuit or a single receiver to the termi nals in accordance with the markings to the terminals 2 L1 4 L2 6 L3 5 N wire connect to terminal 7 6 Additional pulse receiver connected optional to terminals 9 and 8 Additional pulse receiver is not required 7 Put the meter terminals covers Dimensions Mounting ...

Page 5: ... 5 1 power input L1IN 2 power output L1OUT 3 power input L2IN 4 power output L2OUT 5 power input L3IN 6 power output L3OUT 7 neutral N wire 8 pulse output 9 pulse output Wiring diagram ...

Page 6: ...erial own power consumption 10 VA 0 2 W indication range 0 999999 9 kWh constant 1000 pulses kWh current consumption signalling A B C phases 3 red LED read out signalling red LED pulse output type open collector maximum voltage 27 V DC maximum current 27 mA pulse time 35 80 ms working temperature 20 55 C terminal 25 mm screw terminals dimensions 7 modules 122 mm mounting on TH 35 rail ingress prot...

Page 7: ... j declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE and MID Declaration of Conformity along with the refe rences to the standards in relation to which conformity is decla red can be found www fif com pl on the product subpage Warranty CE declaration ...

Page 8: ...sure that all cables are connected correctly It is essential to observe the operating conditions of the meter supply voltage humidity temperature To avoid electric shock or damage to the meter turn off the power supply whenever the connection is changed Do not make any changes to the unit yourself Doing so can result in damage to or improper operation of the device which in turn can pose a threat ...