- 7 -
constant
1000 pulses/kWh
communication
Modbus address
1*÷245
port RS-485
communication protocol
Modbus RTU
transmission parameters 9600*, 19200, 38400, 115200 bps
parity
NONE*, ODD, EVEN
stop bits
1*
read-out signalling
red LED
working temperature
-25÷55°C
terminal
100 A (1, 3 terminals)
25 mm² screw terminals
neutral (N terminal)
1 mm² screw terminals
communication (23, 24, 25 terminals)
1 mm² screw terminals
dimensions
1 module (18 mm)
mounting
on TH-35 rail
ingress protection
IP20
_________________
* factory settings
A detailed user manual for the meter, together with a
description of communication and a list of Modbus regi-
sters, is available for download from the product subpa-
ge at www.fif.com.pl.