![F&F DMM-5T-2 Manual Download Page 14](http://html.mh-extra.com/html/fandf/dmm-5t-2/dmm-5t-2_manual_534623014.webp)
- 14 -
Current measurement cont.
power consumption
0,5 VA/phase
Voltage measurement
measurement range
58÷276 V AC (phase voltage L-N)
100÷480 V AC (phase-to-phase voltage L-L)
frequency
45÷55 Hz
Operating conditions
total power consumption
typical
≤2 VA
temporary
≤15 VA
operating temperature
-25÷55°C
storing temperature
-40÷70°C
relative humidity
0÷95%
(without condensation or aggressive gases)
class of contamination
2
housing flammability
UL94–V0
ingress protection
front
IP54
back
IP20
case size
96×96×62 mm
size of the mounting hole
92×92 mm
panel thickness
1÷5 mm
Communication
pulse outputs
2
RS-485
Modbus RTU
baud-rate
2400/4800/9600/19200/38400 bps
parity BRAK/EVEN/ODD
stop bits
1, 2
Technical data cont.