L phase – current input (S1 terminal of the 

transformer)

 

power supply 230 V AC (phase wire)

 

power supply 230 V AC (neutral wire)

 

L phase – current output (S2 terminal of the 

transformer)

In order for the indicator to show current values, the cur-

rent transformers connected to the indicator must first be 

programmed.

The DMA-1 CT indicator is adapted for use with the following cu-

rrent transformers with 5A secondary and primary current: 20, 

25, 30, 40, 50, 70, 75, 80, 100, 120, 125, 150, 160, 200, 250, 300, 

400, 500, 600, 700, 750, 800, 900, 1000 A.

1. Press and hold down the SET button located on the facade of 

the indicator.

2. Release the button after a minimum of 5 seconds.

3. Use successive short presses of the SET button to set the de-

sired current ratio value.

4. Confirmation of the change takes place by pressing the SET 

button for a minimum of 5 seconds.

The set value of the current ratio is indicated each time 

on the display of the indicator when the power is swit-

ched on.

Configuration

Current transformer setting

Current ratio programming