- 2 -

The correct power supply voltage is indicated by a green LED. 

Voltage drop below 320 V or increase above 480 V for at least 

one phase or voltage asymmetry above the set value is signaled 

by the green LED going off.

Both of the above anomalies (exceeding the voltage threshold, 

asymmetry) cause the relay of the device to be switched off and, 

as a result, the motor to be disconnected. 

Disconnection is carried out with a set delay in order to avoid 

accidental shutdowns in case of temporary interferences  in the 

power supply network. 

If the voltage drops below 320 V or rises above 480 V, the discon-

nection is carried out after 1 sec. The countdown to shutdown is 

indicated by the green diode flashing.

The relay is switched on again automatically when the correct 

network parameters return (voltage hysteresis is approx. 5 V).

If the phase sequence is changed before the sensor causing an 

unwanted change of the motor rotation direction, the sensor 

will not allow the motor to start (the red LED is on and the relay 

is off). Re-activation is possible after the correct phase sequence 

has been restored.

Functioning

Summary of Contents for CKF-318 TRMS

Page 1: ...true rms value of the voltage TrueRMS even when the power supply voltage is disturbed distorted Purpose F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48...

Page 2: ...ental shutdowns in case of temporary interferences in the power supply network If the voltage drops below 320 V or rises above 480 V the discon nection is carried out after 1 sec The countdown to shut...

Page 3: ...3 Front panel...

Page 4: ...current state of the output Asymmetry or exceeding of the voltage threshold Relay switched off voltage value of any of the phases below 150 V or above 280 V or asymmetry above the set value Incorrect...

Page 5: ...5 Voltage waveforms Legend T1 1 10 sec T2 1 60 sec...

Page 6: ...erminals of the device the relay will be switched off immediately The red LED will be on to indicate a phase sequence error When the correct phase sequence returns the relay will be switched on with a...

Page 7: ...1 Swap the 2 phases for example L2 with L3 12 Switch on the power supply the motor can be started 13 In any other case than those described in points 8 and 9 see the signaling table page 4 Wiring diag...

Page 8: ...t separated 2 NO NC maximum load current AC 1 2 6 A power supply control 2 LED minimum phase voltage 320 V maximum phase voltage 480 V voltage asymmetry of activation 20 80 V voltage hysteresis 5 V sw...

Page 9: ...nly with proof of purchase Contact your dealer or directly with us F F Filipowski sp j declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 3...

Page 10: ...ltage circuit breakers Before connecting the power supply make sure that all cables are connected correctly It is essential to observe the operating conditions of the sensor supply voltage humidity te...