background image

Inspection

Pass

Fail

The cable lifeline should extract and retract completely and without faltering and should remain taut under tension without sagging.
Extract the cable lifeline several inches and apply a firm pull to confirm the SRD locks. The locking should be certain and without 

skidding. Repeat this lockup at additional places along the lifeline length to confirm the SRD is operating correctly.
Examine the load indicator on the Energy Absorber to be certain that it has not been loaded, impacted or activated. (see Figure 12 if 

needed)
Inspect the entire length of the constituent line up. Review the cable lifeline closely for broken strand wires, welding spatter burns, 

welding slag, birdcaging, kinks and bent strands. Also examine for rust, dirt, paint, grease or oil. Check for damage caused by chem

-

ical corruption or excessive heat as evident with discoloration. See Figure 14 for examples. If any of these conditions exist, remove 

the SRD from service.

If during your line inspection defined above, you extract the line past the Green Indicator and ultimately expose a secondary Red 

Indicator on the line, you must remove the SRD from service immediately. This Secondary Red Visual Indicator signals the SRD unit’s 

Reserve Line has been deployed or the SRD has experienced a fall event and is no longer in working order.
Check for any missing or loose screws or nuts and any deformed or damaged components.
Examine the external housing for cracks, breaks or warping.
Check the external Connector Eye and the Anchorage Carabiner for damage and deformation. The 

Anchorage Carabiner Gate should open and snap shut easily and smoothly.
Examine the overall SRD unit for any indications of deterioration or damage.
All labels must be intact and totally legible (see Section 8).

Table 1 - Guidelines for Cable SRD Inspection

Extract all of the cable and check the entire working length for damage caused by 

chemical corrosion or excessive heat as evident by discoloration (A), birdcaging (B), 

broken wire strands (C), kinks and bent strands (D), see Figure 14. The cable should 

retract completely without faltering and should remain taut under tension without 

sagging.  

Figure 14: Inspection of Cable

7.0  Inspection

7.1  

Pre-Use User Inspection:

  Perform an inspection before each use in accordance with the recommendations in Table 1 below.

7.2 

Inspection Frequency:

 Inspection by a competent person at regular intervals is required. The competent person will use the information    

 

in Table 2: SRD Inspection Recommendations, to determine the inspection frequency. Use Table 2 to determine the inspection frequency.   

 

Inspection by a factory authorized inspection entity at regular intervals is also required.

Table 2 - SRD Inspection Frequency Recommendations

Type of Use

Application Examples

Conditions of Use

Inspection Frequency

Competent Person

Infrequent to 

Light Use

Rescue and Confined 

Space, Factory

 Maintenance

Good Storage Conditions, 

Indoor or Infrequent 

Outdoor use, Room 

Temperature, Clean 

Environments

Annually

Moderate to 

Heavy Use

Transportation, 

Residential 

Constrution, Utilities, 

Warehouse

Fair Storage Conditions, 

Indoor and extended 

outdoor use, All 

temperatures, Clean or 

dusty 

environments

Semi-annually to 

Annually

Severe to 

Continuous Use

Commercial 

Construction, Oil and Gas, 

Mining

Harsh Storage Condtions, 

Prolonged or Continuous 

outdoor Use, all 

temperatures, Dirty 

environments

Quarterly to 

Semi-annually

MSRD20 Rev B

110421

14

Summary of Contents for FT-R SRL

Page 1: ...el 800 719 4619 Fax 323 752 5613 This manual is intended to meet the Manufacturer s Instructions as required by the American National Standards Institute ANSI Z359 and Canadian Standards Association C...

Page 2: ...6 8 13 14 16 17 19 For purposes of this manual the FT RTM SRL Leading Edge in all iterations may be referred to collectively as the FT R the SRL LE the SRD Leading Edge SRD LE the self retracting dev...

Page 3: ...xperience more risk of serious injury or death due to falls because of increased fall arrest forces placed on the user s body In addition the onset of suspension trauma after a fall even may be accele...

Page 4: ...g or formwork sections are placed formed or constructed The shape and texture of a leading edge may vary see Figure 11 As shown in Figure 1 below the SRD has a glass reinforced nylon housing with an i...

Page 5: ...rating a fall clearance table and a diagram of the axes shown on the table These labels shall be affixed to the product The FT R Leading Edge includes these labels in the Energy Absorber Please see Se...

Page 6: ...s to inadvertently open regardless of how they become oriented Contact FallTech if you have any questions about compatibility Connectors must be compatible with the anchorage or other system component...

Page 7: ...dorsal D ring of the FBH PFAS components used in conjunction with this SRD should comply with ANSI Z359 requirements and applicable OSHA regulations 4 6 Average Arrest Force and Arrest Distance Table...

Page 8: ...ing or a non overhead anchor i e below the user s FBH dorsal D ring A non overhead anchor may be as low as foot level but no more than a maximum of 5 1 5m below the user s FBH dorsal D ring Non overhe...

Page 9: ...13 5 4 1 15 0 4 6 17 0 5 2 18 5 5 6 20 5 6 2 5 ft 1 5 m 6 0 1 8 6 5 2 0 7 5 2 3 9 0 2 7 10 5 3 2 12 5 3 8 14 0 4 3 16 0 4 9 18 0 5 5 20 0 6 1 22 0 6 7 24 0 7 3 0 ft 0 m 6 0 1 8 8 0 2 4 10 0 3 0 12 0...

Page 10: ...2 17 0 5 2 18 0 5 5 18 5 5 6 19 5 6 0 21 0 6 4 22 0 6 7 23 5 7 2 25 0 7 6 26 5 8 1 28 5 8 7 20 ft 6 1 m 16 5 5 0 17 0 5 2 17 0 5 2 17 5 5 3 18 0 5 5 19 0 5 8 20 0 6 1 21 0 6 4 22 5 6 9 23 5 7 2 25 0 7...

Page 11: ...l a radius and or severely abrade or otherwise compromise the lifeline Do not work with the leading edge above the anchorage Figure 10 Leading Edge Angle of Lifeline Redirect 5 4 Edge Conditions Leadi...

Page 12: ...s shifting footing such as sand gravel grain or a sloped surface may not allow the lifeline to reach sufficient speed to activate the lock mechanism A clear path is required to assure positive locking...

Page 13: ...all A fall event over an edge may require special rescue equipment and measures Ensure a written rescue plan method and system is in place and readily available to all users for rapid response Ensure...

Page 14: ...p shut easily and smoothly Examine the overall SRD unit for any indications of deterioration or damage All labels must be intact and totally legible see Section 8 Table 1 Guidelines for Cable SRD Insp...

Page 15: ...ate maintenance or activated fall indicators remove the equipment from service 7 5 Inspection Document Record inspection results on the Inspection Record provided below or on a similar document Inspec...

Page 16: ...Clearance From Working Surface head Anchorage 721530LE FT R 30 Class 2 SRL 0 2 4 6 8 10 12 14 16 18 20 22 30 Feet 6 0 6 5 6 5 7 0 7 5 8 0 8 5 9 5 10 0 11 0 12 5 13 5 25 Feet 6 0 6 5 6 5 7 0 7 5 8 0 9...

Page 17: ...fall protection program who through training and knowledge is capable of identifying evaluating and addressing existing and potential fall hazards and who has the employer s authority to take prompt c...

Page 18: ...sitioning The act of supporting the body with a positioning system for the purpose of working with hands free Positioning Lanyard A lanyard used to transfer forces from a body support to an anchorage...

Page 19: ...ance ANSI Performance Requirements Part Anchorage Condition SRD Class Arrest Distance Average Arrest Force Maximum Arrest Force Maximum Arrest Distance Average Arrest Force Conditioned Maximum Arrest...

Page 20: ...ss 2 CSA SRL LE 1 800 lbs Leading Edge Condition Foot Level with 5 1 5m Setback N A N A 721530LE 30 FT R Leading Edge Overhead Non Leading Edge CSA SRL LE 0 6 m 2 1 ft 4 2 kN 934 lbs 7 0 kN 1 564 lbs...

Reviews: