background image

Burner

Natural

Propane

Main

é2.1mm

Amal 180

Pilot

SIT No. 36

SIT No. 19

mbar inches w.g.

8

14.8

20
37

NATURAL

PROPANE

mbar inches w.g.

16

6

37

14.8

Supply Pressure

Burner Pressure

1.8 INJECTOR SIZES -

NATURAL and PROPANE GAS

1.9 GAS PRESSURE

NATURAL and PROPANE GAS

Pressure test point is located behind front facia panel.

An adjustable governor Rc

1

/

2

(

1

/

2

" BSP) is provided

on Natural Gas models.

1.10 BURNER ADJUSTMENTS
1.10.1 Aeration Adjustment - Natural Gas
Burners are fitted with fixed injectors. Aeration

adjustment is set by manufacturer by means of a

screw in burner throat. After setting pressure, flame

cone height should be approximately 12mm.
1.10.2 Low Flame Setting
The gas control is provided with a low flame setting.

Low flame adjustment has been set and sealed by

manufacturer by means of a bypass screw in gas tap

to approximately one third full rate.

SECTION 2 - ASSEMBLY and

COMMISSIONING

2.1 ASSEMBLY
Place unit in position, and level using feet adjusters.

If unit requires to be mounted upon a stand, refer to

details supplied with stand.
Remove any packing material and ensure that

burners are correctly located over injectors.

2.2 CONNECTION TO GAS SUPPLY
The unit is furnished with a compression elbow fitting,

terminating in an R

1

/

2

thread for connecting to mains.

The gas supply piping and connection to unit must be

installed in accordance with the regulations listed on

the cover of this manual.
On Natural Gas appliances, the adjustable governor

must be fitted in supply, being securely fixed in a

position enabling adjustment to be made during

commissioning. DO NOT fit a governor to Propane

models.
A gas isolating cock must be fitted in supply, in a

position readily accessible to operator.

2.3 CONNECTION TO AN ELECTRICITY SUPPLY
Not applicable to these appliances.

2.4 CONNECTION TO A WATER SUPPLY
Not applicable to these appliances.

2.5 PRE-COMMISSIONING CHECK
2.5.1 Setting Gas Pressure (Natural Gas Only)
Connect a suitable pressure gauge to test point

located behind facia panel. Light burners in

accordance with procedure detailed in User

Instructions and set gas pressure as specified in

Section 1.9.
2.5.2 Aeration Adjustment
Check by observing through inspection aperture and

window, that burner cone lengths are in accordance

with Section 1.10.1.
2.5.3 Low Flame Check
Check by observing through inspection aperture and

window, that flame reduces when control is turned to

low flame setting in accordance with Section 1.10.2.

Further observe that flame is stable.
2.5.4 Gas Tightness
After installation, the engineer responsible should

check gas tightness and ensure unit operates

satisfactorily before hading over to user.

2.6 INSTRUCTION TO USER
After installing and commissioning the appliance,

hand the User's Instructions to the user or purchaser

and ensure that the person(s) responsible

understands the instructions for lighting, cleaning

and correct use of the appliance. It is important to

ensure that location of gas isolating cock is made

known to user, and the procedure for its operation in

an emergency be demonstrated.

All manuals and user guides at all-guides.com

Summary of Contents for G350/7P

Page 1: ...with the Engineer in Charge for reference during servicing Further to this The Users Instructions should be handed over to the User having had a demonstration of the operation and cleaning of the appliance IT IS MOST IMPORTANT THAT THESE INSTRUCTIONS BE CONSULTED BEFORE INSTALLING AND COMMISSIONING THIS APPLIANCE FAILURE TO COMPLY WITH THE SPECIFIED PROCEDURES MAY RESULT IN DAMAGE OR THE NEED FOR ...

Page 2: ...al supply external to unit Light bulbs Re installing vacuum in kettle jackets Replacement of grill burner ceramics when damage has been clearly caused by misuse Where an engineer finds no fault with a product that has been reported faulty Re setting or adjustment of thermostats when unit is operating to specification Cleaning and unblocking of fryer filter systems due to customer misuse Lubricatio...

Page 3: ... any mechanical extraction system or outside air Siting appliance under a ventilated canopy is the ideal arrangement 1 4 GAS SUPPLY The incoming service must be of sufficient size to supply full rate without excessive pressure drop A gas meter is connected to service pipe by Gas Supplier Any existing meter should be checked preferably by Gas Supplier to ensure that the meter is of adequate capacit...

Page 4: ...able governor must be fitted in supply being securely fixed in a position enabling adjustment to be made during commissioning DO NOT fit a governor to Propane models A gas isolating cock must be fitted in supply in a position readily accessible to operator 2 3 CONNECTION TO AN ELECTRICITY SUPPLY Not applicable to these appliances 2 4 CONNECTION TO A WATER SUPPLY Not applicable to these appliances ...

Page 5: ...debris clear or if possible blowing it away with compressed air When replacing burner ensure that rear locating pins are properly located Check flame cone lengths in accordance with Section 1 10 1 Replace all parts in reverse order and check for gas tightness 3 3 2 Pilot Assembly To remove proceed as follows a Remove griddle plate burner and facia panel as previously described b Release thermocoup...

Page 6: ...verse order Take care with central pin assembly i e Fit spring to pin first then brass washer and finally rubber sealing washer When inserting assembly into plug ensure sealing washer fits snugly into recess at bottom of hole in plug When re assembling operating spindle ensure that niting pin engages in the plug slot Adjusting Low Flame Setting Low flame setting is adjustable by means of a screw o...

Reviews: