HFE-1 Soft Start User Manual 
MAN-HFE-01. Version 01. 16/08/2016 

 

 

 

4

 

 

 

The soft starter is normally inserted into the circuit between the motor and whatever switchgear is normally 
used for isolation or switching. The unit can also be fitted before switchgear so that it can be installed in the 
supply to equipment which has its own mechanical control. This feature allows for easy installation on 
equipment such as refrigeration where the need to disturb internal wiring is avoided.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
The terminations are made with industry standard cage clamp screw terminals directly onto the circuit  
board on all units.  
The incoming power supply is connected to the terminals marked ‘1/N’ and ‘3/L’. For EMC compliance it is 
important that the live circuit is connected to 3/L and the neutral circuit to 1/N. 
Outgoing connections from the HFE are taken from the terminals marked ‘4/T’ and ‘2/N’ to the motor or 
load input terminals (see diagram). Ensure that a good connection is made to the earth terminals provided. 
Fuses or other type of short-circuit protection are required for protection against a cable or motor terminal 
box fault. These must be fitted externally and on the supply side of the unit. See “Specifications” section for 
recommended fuse type and cut-out device. 
 
 
 
 
 
Set the ramp time potentiometer to midway to approx. 2 seconds and start the system. If the motor turns 
instantly when the soft starter is energised and accelerates satisfactorily then no further adjustment is 
required. If the rate of acceleration is too great, stop the unit and turn the ramp time potentiometer 
clockwise then restart. Adjust anti–clockwise for a shorter ramp time setting to increase the rate of 
acceleration. 

*

The motor should turn instantly when the soft starter is energised. If not, rearrange the 

connection of the starting capacitor as described above. For running currents up to and including 10 Amps 
the unit is rated for continuous duty. 
Start currents must never exceed 60A 

Start 
Cap   
 

Run 
Cap   
 

Live 110/230Vac 

Neutral 

Earth/Ground 

Electrical Wiring 
 

Ea

rth/

G

ro

und
 

Su

pply

 Liv

Su

pply

 N

eut
ra

Ea

rth/

G

ro

und
 

M

ot

or

 N

eut
ra

M

ot

or

 Liv

1/N  3/L   2/N  4/T 

Motor connected for 
capacitor Start - Run   
 

Centrifugal or voltage 
switch controls start  
Capacitor   
 

*

Connect Start Capacitor to 

Supply Live for High Torque or 
Heavy starting 
 

Extra starting torque may be needed for loads which have a particularly ‘sticky’ starting  
characteristic. This can be achieved by rearranging the internal connection of the starting capacitor, 
bringing the connection out and to the supply side of the starter as shown. 
 

Ea

rth/

G

ro

und
 

Su

pply

 Liv

Su

pply

 N

eut
ra

Ea

rth/

G

ro

und
 

M

ot

or

 N

eut
ra

M

ot

or

 Liv

N    L     M

N

    M

L

 

Note: 
On some HFE-1 
variants, 
terminals may 
have alternative 
markings 
(see diagram) 

Operation 
 

Reviews: