Rating Table 

Load 

Amps 

(Ie) 

Utilisation 

Category 

Start 

Duty 

Up to  

Starts/Hr 

Current 

(Amps) 

Time 

(Secs) 

30 

AC53a 

90 

99% 

60 

 
 

IEC Rating Index 
 

 

 

 

 

Specifications 

Pedestal Voltage: 
Start Time: 
Terminations: 
 
Ambient Temperature: 
Enclosure: 
Rated Operational Voltage: 
Recommended cut–out device: 
Rated insulation voltage: 
Rated impulse withstand voltage: 
Short circuit co–ordination: 
Fuse Type: 
Form designation: 
Pollution Degree: 
EMC Emissions: 
EMC Immunity: 
Design standards:  

Fixed at ~15%. 
Continuously variable from 0.5S -5S. 
Cage clamp terminals suitable for 1.50mm2 (12awg) 
to 25mm

2

 (4 awg) solid or stranded wire 

0°C to 40°C without derating. 
IP20 with standard cover: 
Ue: 110 to 230V ac (–15% +10%), 50/60Hz 
32A rated MCB, Trip Characteristic “C“. Form 1 
Ui: 250V 
Uimp: 4kV (1.2 / 50μs) 
Type 1 , Iq: 5kA when protected by recommended Fuse 
Bussman 170M3113 or Ferraz 6,6 URD 30 D098A 0125 
Form 1 

EN 55011 Environment Class B 
EN 60947-4-2 
IEC 60947–4–2: “AC Semiconductor Motor Controllers and 
Starters”. 

 
 

 

Ratings and Specifications 
 

Duty Cycle (F-S)

 

99-10 = 99% duty cycle - 60  cycles/hr

 

Rated Operational Current (Ie)

 

30A = Rated Operational Current 

 

Overload Current Profile (X-Tx)

 

4-3 = 3 times rated current (Ie) for 3s

 

Utilization Category

 

AC-53a = controller semiconductors provide squirrel-cage motor Start, Run, and Stop  control

 

     30A    :  AC-53a: 3 

 3 : 99-60

 

Reviews: