background image

4

Pneumatic Connection

Clean all pipelines to remove dirt and scale before installation. 

Apply a minimum amount of pipe compound to the male threads 

of the fitting only.  

Do Not use teflon tape as a sealant. 

 Start 

with the third thread back and work away from the end of the fitting 

to avoid contaminating the transducer.  Install the transducer in 

the air line. The inlet and outlet ports are labeled on the ends of 

the transducer.  Tighten connections securely.  Avoid undersized 

fittings that will limit the flow through the transducer and cause 

pressure drop down stream.

Electric Connection

Make connections as shown in Figure 9.

NOTE:

Oil free air  is required.  Use a filter to remove dirt 

and liquid in the air line ahead of the transducer.  

If an air line lubricator is used, it MUST be located 

downstream to avoid interference with transducer 

performance.
The  user  is  responsible  for  insuring  that  the 

environment in which the unit  will be installed and 

the operating gas are compatible with the materials 

in the transducer.

CAUTION:  

Effective November 1997 (DATE CODE NE),  the 

DIN Connector terminal connections have been changed.  The 

ground connection has been moved from terminal  #3 to the (    ) 

terminal.  When replacing an existing unit, correct wiring on the 

mating connector.

   

1.

2.

3.

Shut off the valve that is supplying air to transducer.  

It  is  not  necessary  to  remove  the  Transducer 

from the air line.

Remove the Orifice Assembly from the unit.  For  

detailed information see Figure 1  “T6000 Calibration 

Configuration on page 1.

Clean with alcohol and dry with compressed air.

To clean the Orifice, use the following procedure:

MAINTENANCE

Parts must be completely dry before reassembling.

If the standard maintenance procedure does not 

correct the trouble, install the appropriate Service 

Kit below:

16798-1 

  (3-15, 3-27 & 6-30 psig 

                    Standard Range)

18238-1   

(0-30 psig Extended Range)

18239-1  

(0-60 psig Extended Range)

18240-1

  (0-120 psig Extended Range)

18039-1 

 (Explosion-Proof Base)

Service  Kits  also  include  Gasket,  O-Rings,  and  

Membranes to replace "W" Option product.

NOTES:

TROUBLE-SHOOTING

WARNING: 

Failure  of  Transducer  could  result  in  output 

pressure increasing to supply pressure possibly 

causing personal injury or damage to equipment.

Table 1.  

Trouble-Shooting

Problem

Solution 

(check)

No Output

Supply Pressure 

Clogged Orifice

Input Signal

No Output

Pneumatic Connections

Low or Improper 

Span Adjust

Zero and Span Adjust

Supply Pressure Low

Output Leakage

Erratic Operation

DC Signal 

Loose Wires or Connections

Liquid in Air Supply

Dirt in Magnet Gap

Summary of Contents for T6000

Page 1: ... 39 64 117 2 1 2 12 7 1 25 4 25 32 19 7 25 64 9 8 Use two 10 32 Screws for Mounting 3 7 16 87 2 3 3 64 77 5 2 1 4 57 2 1 33 64 38 7 Orifice Do Not Remove Plugs typ Do Not Remove Plugs typ 1 4 NPT Outlet Port 2 typical 1 4 NPT Inlet Port 2 typical Vent ZERO SPAN OUT OUT OUT OUT IN IN IN IN 3 43 64 93 3 3 7 64 79 0 1 59 64 49 0 Extended Range OUT OUT IN IN 3 3 32 78 7 1 33 64 38 7 5 11 64 131 5 1 4 ...

Page 2: ... NPT Intlet Port typical COVER 3 15 64 82 2 1 55 64 47 4 57 2 2 1 4 TERMINAL 2 59 64 74 25 4 1 12 7 1 2 9 8 25 64 19 7 25 32 49 1 59 64 VENT MM INCH ECL 16752 FOR CATALOG 6 5 64 154 5 5 15 64 133 1 1 2 14 NPTF 81 7 3 7 32 57 2 2 1 4 25 4 1 12 7 1 2 19 7 25 32 9 8 25 64 49 1 59 64 87 2 3 7 16 Use two 10 32 Screws for Mounting VENT MM INCH ECL 16752 FOR CATALOG Figure 4 TR6000 Outline Dimensions Fig...

Page 3: ... Included with Unit 9 32 7 1 2 7 16 61 9 Mounting Kit 16799 1 Includes the following Two 10 32 x 5 16 Screws Mounting Bracket Two 1 4 NPT Pipe Plugs Two 7 16 Thick Spacers not used on T6000 17 64 6 6 5 8 15 9 1 8 3 0 1 25 4 3 4 19 1 2 1 4 57 2 2 7 8 73 2 1 1 2 38 1 1 25 4 9 32 7 1 3 8 9 5 3 4 19 0 4 1 2 114 3 4 55 64 123 4 1 25 7 Use two 1 4 20 Screws for Mounting not included in mounting kit ZERO...

Page 4: ...from terminal 3 to the terminal When replacing an existing unit correct wiring on the mating connector 1 2 3 Shut off the valve that is supplying air to transducer It is not necessary to remove the Transducer from the air line Remove the Orifice Assembly from the unit For detailedinformationseeFigure1 T6000Calibration Configuration on page 1 Clean with alcohol and dry with compressed air To clean ...

Page 5: ...heSpan screw for maximum output pressure Turn screw clockwisetoincreasepressureandcounterclockwise to decrease pressure Reverse Acting Mode Adjustment 5 Reverse Acting Calibration Zero 6 Apply the minimum input signal and adjust the Zero screw for maximum output pressure Turn screw clockwisetoincreasepressureandcounterclockwise to decrease pressure Forward Acting Calibration Span 3 8 Reverse Actin...

Page 6: ...ically Safe TAFI6000 TDFI6000 CL I II III Div 1 Grps ABCDEFG I 0 AEx ia IIC T4 Ga Ta 40 C to 80 C Type 3R Enclosure Nonincendive CL I Div 2 Grps ABCD T4 Ta 40 C to 80 C Installation Entity IS and NI System Drawing 16984 Intrinisically Safe TTFI6000 TRFI6000 CL I II III Div 1 Grps ABCDEFG T4 Ta 40 C to 80 C I 0 AEx ia IIC T4 Ga Ta 40 C to 80 C Nonincendive CL I Div 2 Grps ABCD T4 Ta 40 C to 80 C In...

Page 7: ...icularly if the equipment is installed in a zone 0 or Class I DIV 3 location 4 The enclosure of devices TD_I6000 TJ_I6000 TA_I6000 series are capable of withstanding only low level 4 J of mechanical impact and hence additional protection shall be provided to ensure equipment cannot be subjected to higher level mechanical impact 5 The DIN socket connected to the TD_I6000 series shall comply with IP...

Page 8: ...4 38 7 Orifice Do Not Remove Plugs typ Do Not Remove Plugs typ 1 4 NPT Outlet Port 2 typical 1 4 NPT Inlet Port 2 typical Vent ZERO SPAN OUT OUT OUT OUT IN IN IN IN 3 43 64 93 3 3 7 64 79 0 1 59 64 49 0 Erweiterter Bereich OUT OUT IN IN 3 3 32 78 7 1 33 64 38 7 5 11 64 131 5 1 4 NPT Inlet Port 2 typical Do Not Remove Plugs typical 1 4 NPT Outlet Port 2 typical 4 53 64 122 8 ZERO SPAN _ _ 3 21 64 8...

Page 9: ...NCH ECL 16752 FOR CATALOG 6 5 64 154 5 5 15 64 133 1 1 2 14 NPTF 81 7 3 7 32 57 2 2 1 4 25 4 1 12 7 1 2 19 7 25 32 9 8 25 64 49 1 59 64 87 2 3 7 16 Use two 10 32 Screws for Mounting VENT MM INCH ECL 16752 FOR CATALOG Abbildung 4 Außenabmessungen TR6000 Abbildung 5A Außenabmessungen TJ6000 STANDARD VERSION Abbildung 5B Außenabmessungen TJ6000 ERWEITERTE VERSION Klemmleiste TJ6000 STANDARD Entlüftun...

Page 10: ... 9 1 8 3 0 1 25 4 3 4 19 1 2 1 4 57 2 2 7 8 73 2 1 1 2 38 1 1 25 4 9 32 7 1 3 8 9 5 3 4 19 0 4 1 2 114 3 4 55 64 123 4 1 25 7 Use two 1 4 20 Screws for Mounting not included in mounting kit ZERO SPAN OUT OUT IN IN DIN EN 50045 3 7 16 87 1 DIN EN 50022 DIN EN 50035 39 64 15 6 53 64 20 9 19 32 14 9 3 13 32 86 6 3 5 16 84 3 Din Rail Mounting Configuration shown with Model TD6000 Din EN 50045 2 Pipe M...

Page 11: ...belungzumpassenden Stecker korrigiert werden 1 Schließen Sie das Ventil welches den Wandler mit Luft versorgt Der Wandler muss nicht von der Luftzufuhrleitung getrennt werden 2 Entfernen Sie den Düseneinsatz vom Gerät Nähere Angaben finden Sie in Abbildung 1 T6000 Kalibrierkonfiguration auf Seite 1 3 ReinigenSiedenDüseneinsatzmitAlkoholundtrocknen Sie ihn mit Druckluft Die Düse muss folgendermaßen...

Page 12: ... Rückwärts Kalibrierung Nullpunkt 6 Schließen Sie das Mindesteingangssignal an und stellen Sie die Nullpunktschraube auf maximalen Ausgangsdruck ein Drehen Sie die Schraube im Uhrzeigersinn um den Druck zu erhöhen und entgegen dem Uhrzeigersinn um den Druck zu reduzieren Rückwärts Kalibrierung Spannweite 7 Schließen Sie das maximale Eingangssignal an und stellen Sie die Spannweitenschraube auf Min...

Page 13: ... C Ex ia IIIC T135 C Da Ta 40 C nach 70 C TAEI6000 TDEI6000 TTEI6000 TREI6000 Serie Ex ia IIC T4 Ga Ta 40 C nach 70 C FM Eigensichere Ausführung TAFI6000 TDFI6000 CL I II III Div 1 Grps ABCDEFG I 0 AEx ia IIC T4 Ga Ta 40 C nach 80 C Gehäusetyp 3R Nicht zündfähig CL I Div 2 Grps ABCD T4 Ta 40 C nach 80 C Installationseinheit IS und NI Systemzeichnung 16984 Eigensichere Ausführung TTFI6000 TRFI6000 ...

Page 14: ...ort der Zone 0 oder der Klasse I DIV 3 installiert ist 4 Das Gehäuse der Geräteserien Baureihe TD_I6000 TJ_I6000 und TA_I6000 kann nur einem geringen Maß 4 J an mechanischer Einwirkung standhalten Daher muss für zusätzlichen Schutz gesorgt werden um sicherzustellen dass die Vorrichtung keinem höheren Maß an mechanischer Einwirkung ausgesetzt wird 5 Die aus der Geräteserie Baureihe TD_I6000 Serie v...

Page 15: ...t Remove Plugs typ Do Not Remove Plugs typ 1 4 NPT Outlet Port 2 typical 1 4 NPT Inlet Port 2 typical Vent ZERO SPAN OUT OUT OUT OUT IN IN IN IN 3 43 64 93 3 3 7 64 79 0 1 59 64 49 0 Gamma estesa OUT OUT IN IN 3 3 32 78 7 1 33 64 38 7 5 11 64 131 5 1 4 NPT Inlet Port 2 typical Do Not Remove Plugs typical 1 4 NPT Outlet Port 2 typical 4 53 64 122 8 ZERO SPAN _ _ 3 21 64 84 6 3 43 64 93 3 OUT OUT IN...

Page 16: ...7 25 32 49 1 59 64 VENT MM INCH ECL 16752 FOR CATALOG 6 5 64 154 5 5 15 64 133 1 1 2 14 NPTF 81 7 3 7 32 57 2 2 1 4 25 4 1 12 7 1 2 19 7 25 32 9 8 25 64 49 1 59 64 87 2 3 7 16 Use two 10 32 Screws for Mounting VENT MM INCH ECL 16752 FOR CATALOG Figura 4 Dimensioni esterne TR6000 Figura 5A Dimensioni esterne TJ6000 standard Figura 5B Dimensioni esterne ESTESE TJ6000 Ne pas retirer les bouchons stan...

Page 17: ...4 19 1 2 1 4 57 2 2 7 8 73 2 1 1 2 38 1 1 25 4 9 32 7 1 3 8 9 5 3 4 19 0 4 1 2 114 3 4 55 64 123 4 1 25 7 Use two 1 4 20 Screws for Mounting not included in mounting kit ZERO SPAN OUT OUT IN IN DIN EN 50045 3 7 16 87 1 DIN EN 50022 DIN EN 50035 39 64 15 6 53 64 20 9 19 32 14 9 3 13 32 86 6 3 5 16 84 3 Din Rail Mounting Configuration shown with Model TD6000 Din EN 50045 2 Pipe Mounting Configuratio...

Page 18: ...al terminale Durante la sostituzione di un unità esistente correggere i cablaggi sul connettore associato 1 Spegnere la valvola che alimenta l aria verso il trasduttore Non è necessario rimuovere il trasduttore dalla linea dell aria 2 Togliere il gruppo orifizio dall unità Per informazioni dettagliate vedere la Figura 1 Configurazione della taratura T6000 a pagina 1 3 Pulire con alcol e asciugare ...

Page 19: ...egnale di ingresso al trasduttore come mostrato nella Figura 9 Taratura azionamento indietro Zero 6 Applicare il segnale di ingresso minimo e regolare la vite Zero per la pressione di uscita massima Ruotare la vite verso destra per aumentare la pressione e verso sinistra per diminuirla Taratura azionamento indietro Span 7 Applicareilsegnalediingressomassimoeregolarela vite Span per la pressione di...

Page 20: ...000 Séries Ex ia IIC T4 Ga Ta 40 C to 70 C FM Intrinsecamente sicuro TAFI6000 TDFI6000 CL I II III Div 1 Grps ABCDEFG I 0 AEx ia IIC T4 Ga Ta 40 C to 80 C Alloggiamento di tipo 3R Non incendive CL I Div 2 Grps ABCD T4 Ta 40 C to 80 C Entità di installazione e disegno del sistema 16984 Intrinsecamente sicuro TTFI6000 TRFI6000 CL I II III Div 1 Grps ABCDEFG T4 Ta 40 C to 80 C I 0 AEx ia IIC T4 Ga Ta...

Page 21: ...pparecchio è installato in una Zona 0 o Classe I DIV 3 4 L alloggiamento dei dispositivi delle serie TD_I6000 TJ_I6000 e TA_I6000 è in grado di sopportare solo impatti meccanici di livello basso 4 J e pertanto deve essere fornita una protezione aggiuntiva che garantisca che l apparecchio non possa essere soggetto a impatti meccanici di più alto livello 5 La presa DIN collegata alla serie TD_I6000 ...

Page 22: ...Not Remove Plugs typ 1 4 NPT Outlet Port 2 typical 1 4 NPT Inlet Port 2 typical Vent ZERO SPAN OUT OUT OUT OUT IN IN IN IN 3 43 64 93 3 3 7 64 79 0 1 59 64 49 0 Gamme complète OUT OUT IN IN 3 3 32 78 7 1 33 64 38 7 5 11 64 131 5 1 4 NPT Inlet Port 2 typical Do Not Remove Plugs typical 1 4 NPT Outlet Port 2 typical 4 53 64 122 8 ZERO SPAN _ _ 3 21 64 84 6 3 43 64 93 3 OUT OUT IN IN ZERO SPAN 1 31 6...

Page 23: ...25 32 49 1 59 64 VENT MM INCH ECL 16752 FOR CATALOG 6 5 64 154 5 5 15 64 133 1 1 2 14 NPTF 81 7 3 7 32 57 2 2 1 4 25 4 1 12 7 1 2 19 7 25 32 9 8 25 64 49 1 59 64 87 2 3 7 16 Use two 10 32 Screws for Mounting VENT MM INCH ECL 16752 FOR CATALOG Figure 4 Dimensions TR6000 Figure 5A Dimensions TJ6000 STANDARD Figura 5B Dimensiones generales de los transductores TJ6000 gama ampliada Ne pas retirer les ...

Page 24: ...8 73 2 1 1 2 38 1 1 25 4 9 32 7 1 3 8 9 5 3 4 19 0 4 1 2 114 3 4 55 64 123 4 1 25 7 Use two 1 4 20 Screws for Mounting not included in mounting kit ZERO SPAN OUT OUT IN IN DIN EN 50045 3 7 16 87 1 DIN EN 50022 DIN EN 50035 39 64 15 6 53 64 20 9 19 32 14 9 3 13 32 86 6 3 5 16 84 3 Din Rail Mounting Configuration shown with Model TD6000 Din EN 50045 2 Pipe Mounting Configuration shown with Model TT6...

Page 25: ...bornedeterre Lors du remplacement del unité existante modifiezlecâblagesurleconnecteurhomologue 1 Fermez la vanne qui alimente le transmetteur en air Il n est pas nécessaire de retirer le transmetteur du conduit d air 2 Retirez l assemblage de l orifice de l unité Pour plus de détails voir la figure 1 Configuration d étalonnage T6000 sur la page 1 3 Nettoyez avec de l alcool et séchez à l air comp...

Page 26: ...versée 5 Connecter le signal d entrée au transducteur représenté sur la figure 9 Étalonnage de l action inversée Zéro 6 Appliquezlesignald entréeminimaletréglezlavisde réglage du zéro pour la pression de sortie maximale Tournez la vis dans le sens horaire pour augmenter la pression et dans le sens antihoraire pour la diminuer Étalonnage de l action inversée Étendue 7 Appliquezlesignald entréemaxim...

Page 27: ...C to 70 C TAEI6000 TDEI6000 TTEI6000 TREI6000 Séries Ex ia IIC T4 Ga Ta 40 C to 70 C FM Sécurité intrinsèque TAFI6000 TDFI6000 CL I II III Div 1 Grps ABCDEFG I 0 AEx ia IIC T4 Ga Ta 40 C to 80 C Enveloppe Type 3R Non incendiaire CL I Div 2 Grps ABCD T4 Ta 40 C to 80 C Entité d installation et schéma du système 16984 Sécurité intrinsèque TTFI6000 TRFI6000 CL I II III Div 1 Grps ABCDEFG T4 Ta 40 C t...

Page 28: ...lation en particulier si l équipement est installé dans un lieu de type Zone 0 ou Classe 1 DIV 3 4 L enveloppe des dispositifs TD_I6000 TJ_I6000 et TA_I6000 n est capable de supporter qu un faible niveau 4 J de choc mécanique Une protection additionnelle doit être fournie pour garantir que l équipement ne fasse pas l objet de chocs mécaniques plus importants 5 La prise DIN connectée à la série TD_...

Page 29: ... 3 64 77 5 2 1 4 57 2 1 33 64 38 7 Orifice Do Not Remove Plugs typ Do Not Remove Plugs typ 1 4 NPT Outlet Port 2 typical 1 4 NPT Inlet Port 2 typical Vent ZERO SPAN OUT OUT OUT OUT IN IN IN IN 3 43 64 93 3 3 7 64 79 0 1 59 64 49 0 Gama ampliada OUT OUT IN IN 3 3 32 78 7 1 33 64 38 7 5 11 64 131 5 1 4 NPT Inlet Port 2 typical Do Not Remove Plugs typical 1 4 NPT Outlet Port 2 typical 4 53 64 122 8 Z...

Page 30: ...5 64 154 5 5 15 64 133 1 1 2 14 NPTF 81 7 3 7 32 57 2 2 1 4 25 4 1 12 7 1 2 19 7 25 32 9 8 25 64 49 1 59 64 87 2 3 7 16 Use two 10 32 Screws for Mounting VENT MM INCH ECL 16752 FOR CATALOG Figura 4 Dimensiones generales de los transductores TR6000 Figura 5A Dimensiones generales de los transductores TJ6000 gama estándar Figura 5B Dimensiones generales de los transductores TJ6000 gama ampliada Resp...

Page 31: ...n T6000 17 64 6 6 5 8 15 9 1 8 3 0 1 25 4 3 4 19 1 2 1 4 57 2 2 7 8 73 2 1 1 2 38 1 1 25 4 9 32 7 1 3 8 9 5 3 4 19 0 4 1 2 114 3 4 55 64 123 4 1 25 7 Use two 1 4 20 Screws for Mounting not included in mounting kit ZERO SPAN OUT OUT IN IN DIN EN 50045 3 7 16 87 1 DIN EN 50022 DIN EN 50035 39 64 15 6 53 64 20 9 19 32 14 9 3 13 32 86 6 3 5 16 84 3 Din Rail Mounting Configuration shown with Model TD60...

Page 32: ...stituir una unidad si es necesario corrijaelcableadoenelconectorcorrespondiente 1 Cierre la válvula de suministro de aire al transductor No es necesario desmontar el transductor de la tubería de aire 2 Desmonteelconjuntodelorificiodelaunidad Paraobtener más información consulte la figura 1 Configuración de calibración de los transductores T6000 en la página 1 3 Limpie el orificio con alcohol y séq...

Page 33: ...alibración del cero en el modo inverso 6 Aplique la señal de entrada mínima y ajuste el tornillo del cero para obtener la presión de salida máxima Gire el tornillo en sentido horario para aumentar la presión y en sentido anti horario para reducir la presión Calibración de la amplitud en el modo inverso 7 Apliquelaseñaldeentradamáximayajusteeltornillo de la amplitud para obtener la presión de salid...

Page 34: ...C Da Ta 40 C to 70 C TAEI6000 TDEI6000 TTEI6000 TREI6000 serie Ex ia IIC T4 Ga Ta 40 C to 70 C FM Intrínsecamente seguros TAFI6000 TDFI6000 CL I II III Div 1 Grps ABCDEFG I 0 AEx ia IIC T4 Ga Ta 40 C to 80 C Carcasa de tipo 3R Nonincendive CL I Div 2 Grps ABCD T4 Ta 40 C to 80 C Entidad de instalación y plano del sistema 16984 Intrínsecamente seguros TTFI6000 TRFI6000 CL I II III Div 1 Grps ABCDEF...

Page 35: ...s por impacto o fricción que pueden actuar como fuentes de ignición Esto debe tenerse en cuenta durante la instalación en especial si el equipo se instala en un área clasificada como zona 0 o de clase I y división 3 4 La carcasa de los dispositivos de las familias TD_I6000 TJ_I6000 y TA_I6000 solo es capaz de resistir impactos mecánicos de baja intensidad 4 J por lo tanto es necesario incluir prot...

Reviews: