Fairchild 63 Installation, Operation And Maintenance Instructions Download Page 2

IS-10000063
Litho  in  USA
Rev.  A   11/02

To remove entrained liquids from the Dripwell, open
the Drain Plug on the bottom of the Dripwell Assembly.
The flow through the regulator and the amount of
entrained oil or water in the air determine how often you
should empty the Dripwell.  For more information, see
Figure 2.

If the standard maintenance procedure
does not correct the problem, install the
service kit.

MAINTENANCE

Troubleshooting

Figure  2.  

Model 63 Exploded Drawing

Source

Problem

•  If contaminated,
   clean the
   source.

Solution

High
Bleed

Leakage

Tighten the
Body Screw.

•  Relief Pintle
•  Relief Seat

Body Screw

NOTE:

Standard

• EA-19798-1
• EA-19798-2

Difficult to
Adjust

•   Adjustment Screw •  Lubricate the

   Adjustment
   Screw threads
   and end.

NOTE: The presence of some diester oils in the air

lines can accelerate elastomer deteriora-
tion and decrease the life span of this unit.

  Pressure Ranges

• 0.5-30 psig
• 1-60 and 2-120 psig