Hold on switched (Deadman) control:

Automatic / Semiautomatic:

Open and Close operations are achieved "by holding a switch on" (no relay
self-holding is involved) therefore a phisical attendance is required to keep
the gate opening or closing until either the button or key is released.

Automatic Operation

: any pulse opens the gate, the gate stays open

as long as the Dwell time expires as set by T2 trimmer, then it closes
automatically, no pulsing is required.

3

DIP-SWITCH N

°

3

ON=  Automatic Closing

OFF= No Automatic. Semi-
       automatic closing by pulse

6

DIP-SWITCH N

°

6=ON

ON= Deadman Control. Dip-switch 4=OFF
         and Dip-switch 3=OFF

OFF= Standard Operations

Pedestrian Opening:

Trimmer T4

-

+

from 3 to 30s. It can be activated

by any pulse (eg. by remote control)

superior to 2s

4

3

COMMON

COMMON

OPEN

NO

How it works: Set the clock to the required times. On the pre-set time the gate is automatically opened and held
open. Any further pulsing (even by remote control) is not accepted by the system until the time pre-set by the
clock has expired. On expiring and after the pre-set dwell time the gate is closed automatically.
T4 trimmer on to zero, Dip-Switch 3=ON.

Time clock
installation:

DIP-SWITCH No.3=ON Automatic Closing

3

ON= Automatic Closing

OFF= No Automatic. Semi-automatic
          closing by pulse

-

+

Pedestrian Trimmer T4

set on to zero

COMMON

OPEN

4

3

External Time Clock

OPERATING MODES

PLUS

15

GB

7

4136

Drwg. No.

SINGLE-PHASE CONTROL PANEL WITH
MICROPROCESSOR FOR GIRRI 130 SLIDING GATE OPERATOR

Semi-automatic Operation

: any pulse opens the gate that stays open.

A second pulse to Close is required for the gate to close.

®

Summary of Contents for Elpro 15 Plus

Page 1: ... SLIDING GATE OPERATOR PLUS 15 GB page 1 5 6 7 PROGRAMMATORE A MICROPROCESSORE MONOFASE PER SCORREVOLE GIRRI 130 LIBRETTO DI ISTRUZIONI PLUS 15 I MONOPHASE POUR PORTAILS COULISSANT GIRRI 130 EINPHASIGE STEUERUNG MIT MIKROPROZESSOR FÜR SCHIEBETORANTRIEB GIRRI 130 STEP BY STEP OPERATIONS PEDESTRIAN OPENING HOLD ON SWITCHED DEADMAN CONTROL GATE STATUS INDICATION TIME CLOCK OPTION FONCTION PAS A PAS O...

Page 2: ...and persons PLEASE NOTE The control panel is fitted inside Girri 130 Make sure that the power supply to the electronic programmer is 230V 10 Make sure that the power supply to the Electric Motor is 230V 10 For distances of over 50 metres we recommend using electric cables with bigger sections Fit the mains to the control panel with a 0 03A high performance circuit breaker Use 1 5mm2 section wires ...

Page 3: ...hile opening OFF Any pulse reverses the gate DIP SWITCH 2 and 5 NEVER set BOTH of them ON at the same time Limit switch LIMIT SWITCH CLOSE COMMON 10 8 9 LIMIT SWITCH OPEN Flashing lamp 230V max 25W Power supply Capacitor and Single phase Motor T1 MOTOR RUN TIME OPEN CLOSE from 2 up to 255s T2 DWELL TIME from 2 up to 255s 230V 10 MOTOR 23 24 EXT Capacitor 20µF fitted COMMON M 16 14 15 17 18 19 20 P...

Page 4: ...activated by any pulse eg by remote control superior to 2s 4 3 COMMON COMMON OPEN NO How it works Set the clock to the required times On the pre set time the gate is automatically opened and held open Any further pulsing even by remote control is not accepted by the system until the time pre set by the clock has expired On expiring and after the pre set dwell time the gate is closed automatically ...

Page 5: ...canica Fadini Vor der Montage durch einen Fachmann wird es empfohlen die Anleitung zur Sicherheitsnormen die Meccanica Fadini zur Verfügung stellt nachzulesen Antes de la instalación por el personal técnico calificado se recomienda leer detenidamente el Folleto de la Reglamentación de Seguridad que la empresa Meccanica Fadini pone a su disposición Voordat de installatie door gekwalificeerd technis...

Reviews: