2
FX Supervisory Controllers LON Card Installation Instructions
Installation
Parts Included
Unpack the LON Option Card and inspect the contents
of the package for damaged or missing components. If
any components are damaged, notify the appropriate
carrier and return them for repair or replacement.
Included in this package are the following items:
•
one LON Option Card, along with connector end
plate
•
one 2-position terminal plug for wiring to a
L
ON
W
ORKS
Twisted Pair/Free Topology
(TP/FT)-10 network
•
FX Supervisory Controller LON Card Installation
Instructions (Part No. 24-10174-34)
Special Tools Needed
The following supplies and tools are required for
installation:
•
#2 Phillips screwdriver: used to install the LON
card
•
small flat-blade screwdriver: used for making
wiring connections to the L
ON
W
ORKS
network
Safety Precautions
The following information relates to the installation and
startup of the LON Option Card.
!
WARNING:
Risk of Electric Shock.
Disconnect power supply before making electrical
connections. Contact with components carrying
hazardous voltage can cause electric shock and
may result in severe personal injury or death.
AVERTISSEMENT: Risque de décharge
électrique
Débrancher l'alimentation avant de
réaliser tout branchement électrique. Tout contact
avec des composants conducteurs de tensions
dangereuses risque d'entraîner une décharge
électrique et de provoquer des blessures graves,
voire mortelles
IMPORTANT:
Be careful to plug any option card
into its connector properly (pins aligned).
IMPORTANT:
Avoid hot plug-in or removal of any
option card from the FX Supervisory Controllers; that
is, do not remove any card with power applied. If the
unit switches to battery operation, wait for all Light
Emitting Diodes (LEDs) to go out.
Mounting
Mount the LON Option Card in either of the option
slots on the FX Supervisory Controller, as available.
Follow these instructions:
1.
If a station is running, stop the station using the
platform Application Director view.
2.
Remove power from the FX Supervisory
Controller.
3.
Remove the FX Supervisory Controller cover or
covers. Press in the four tabs on both ends of the
controller and lift off the cover.
Note:
If accessory modules are plugged into
the FX Supervisory Controller, you may need to
slide them away from the unit to access the cover
tabs.
4.
If the battery assembly is installed, remove it by
taking out the four screws holding it in place. Set
the screws aside for later.
5.
Unplug the battery from the connector on the FX
Supervisory Controller (see Figure 3).
Battery Assembly
(includes cable and
bracket)
Blanking
End Plate
Opt ion Slot 1
Area
Opt ion Slot 2
Area
Screws (4)
FX Super visor y
Controller
Figure 3: Removing Battery Assembly
6.
Remove the blanking end plate for the slot into
which you are installing the Option Card. Retain
the blanking end plate in case you need to
remove the Option Card at a later date.