Facility Explorer FX Series Installation Instructions Download Page 2

 

 

2

  FX Supervisory Controllers LON Card Installation Instructions 

Installation 

Parts Included 

Unpack the LON Option Card and inspect the contents 
of the package for damaged or missing components. If 
any components are damaged, notify the appropriate 
carrier and return them for repair or replacement. 

 

Included in this package are the following items: 

 

one LON Option Card, along with connector end 
plate 

 

one 2-position terminal plug for wiring to a 
L

ON

W

ORKS

 Twisted Pair/Free Topology  

(TP/FT)-10 network 

 

FX Supervisory Controller LON Card Installation 
Instructions (Part No. 24-10174-34)

 

Special Tools Needed 

The following supplies and tools are required for 
installation: 

 

#2 Phillips screwdriver: used to install the LON 
card 

 

small flat-blade screwdriver: used for making 
wiring connections to the L

ON

W

ORKS

 network 

Safety Precautions 

The following information relates to the installation and 
startup of the LON Option Card. 

!

  WARNING:

 

Risk of Electric Shock. 

Disconnect power supply before making electrical 
connections. Contact with components carrying 
hazardous voltage can cause electric shock and 
may result in severe personal injury or death. 

AVERTISSEMENT: Risque de décharge 
électrique  

Débrancher l'alimentation avant de 

réaliser tout branchement électrique. Tout contact 
avec des composants conducteurs de tensions 
dangereuses risque d'entraîner une décharge 
électrique et de provoquer des blessures graves, 
voire mortelles

 

 

IMPORTANT: 

Be careful to plug any option card 

into its connector properly (pins aligned). 

 

IMPORTANT: 

Avoid hot plug-in or removal of any 

option card from the FX Supervisory Controllers; that 
is, do not remove any card with power applied. If the 
unit switches to battery operation, wait for all Light 
Emitting Diodes (LEDs) to go out. 

Mounting 

Mount the LON Option Card in either of the option 
slots on the FX Supervisory Controller, as available. 
Follow these instructions: 

1. 

If a station is running, stop the station using the 
platform Application Director view. 

2. 

Remove power from the FX Supervisory 
Controller. 

3. 

Remove the FX Supervisory Controller cover or 
covers. Press in the four tabs on both ends of the 
controller and lift off the cover.  

Note: 

If accessory modules are plugged into 

the FX Supervisory Controller, you may need to 
slide them away from the unit to access the cover 
tabs. 

4. 

If the battery assembly is installed, remove it by 
taking out the four screws holding it in place. Set 
the screws aside for later. 

5. 

Unplug the battery from the connector on the FX 
Supervisory Controller (see Figure 3). 

Battery Assembly

(includes  cable and

bracket)

Blanking

End Plate

Opt ion Slot  1

Area

Opt ion Slot  2

Area

Screws (4)

FX Super visor y

Controller

 

Figure 3: Removing Battery Assembly 

6. 

Remove the blanking end plate for the slot into 
which you are installing the Option Card. Retain 
the blanking end plate in case you need to 
remove the Option Card at a later date. 

Reviews: