FAAST 8251BPI Nstallation And Maintenance Instructions Download Page 10

 

FAAST 8251BPI and 8100  
INSTALLATION AND MAINTENANCE INSTRUCTIONS

  

10 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Figure 11a: 8125BPI Address Blink Mode 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Figure 10: 8000 Series User Interface Buttons

 

 
 
 
 
 
 
 
 

 

Figure 11b: 8100 Address Blink Mode 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Address Blink Mode 

-  8251BPI 

User Button Alternate Functions

 

Passcode Access 

The  user  interface  has  an  option  that  requires  users  to 
enter  a  security  code  before  the  front  panel  functions 
become  active.  All  passcodes  must  be  4  digits  in  length 
using numbers 1 through 9 (0 cannot be used). 
Passcodes may only be changed using PipeIQ software. 
PipeIQ is also capable of locking out buttons individually, 
so  that  certain  buttons  may  be  accessed  without  a 
passcode, if desired. 
The default passcode is ‘1111’. 
The TEST button enters digits, the 

MODE

/

RESET

 button 

is  used  to  enter  the  unlock  mode  and  the  ISOLATE 
button increments the current digit. 
To  enter  the  passcode  mode,  press  and  hold  the 

MODE

/

RESET

  button  for  8  seconds  -  the  first  segment 

on the flow indicator first illuminates yellow, then green. 
When  the  segment  illuminates  green,  release  the 

MODE

/

RESET

  button.  The  first  segment  on  the  airflow 

display  blinks  green,  indicating  the  device  is  ready  to 
accept the first digit.

 

To  enter  the  passcode,  use  the  ISOLATE  and  TEST 
buttons, shown in Figure 10. 
The  ISOLATE  button  is  used  to  increment  the  current 
digit. As the current digit is incremented the segments of 
the Particulate Bar Graph illuminate accordingly. 
To complete entry of the digit, press the TEST button. As 
each digit is entered the airflow segment illuminates solid 
green  and  the  next  segment  begins  to  flash,  indicating 
the next digit is ready to be entered. After the 4th digit is 
entered,  the  Fault  indicator  illuminates  green,  if  the 
passcode  was  accepted  and  remains  green  as  long  as 
the  detector  is  “unlocked”.  If  the  passcode  was  not 
accepted,  the  Fault  indicator  illuminates  amber  for  3 
seconds  then  the  device  returns  to  its  previous  state. 
Once the passcode is accepted, the locked out button(s) 
become  active.  After  45  seconds  of  inactivity  the  Fault 
indicator  begins  to  blink  green.  After  an  additional  15 
seconds the detector re-locks the button(s) and returns to 
Normal operation. 

Note:  If the RESET button is chosen as a locked button, 

and  a  Reset  is  initiated,  the  device  requires  the 
passcode to regain access to the RESET button. 

The  FAAST  8100  has  two  types  of  addressing 
capabilities.  In  addition  to  the  IP  Address,  the  FAAST 
system  can  also  have  a  local  address  that  is  assigned 
through  the  configuration  software.  The  address  can  be 
between 1 and 255. This address can be accessed from 
the  user  interface  by  pressing  and  holding  the  RESET 
button  for  3  seconds.  After  3  seconds,  the  first  segment 
on the airflow display illuminates amber, shown in Figure 
10,  indicating  the  device  is  in  address  blink  mode. 
Release  the  RESET  button  and  the  device  shows  the  3 
digit  number  assigned  by  lighting  the  particulate  bar 
graph with the appropriate number of segments for each 
digit. The current digit displayed is indicated by the 3 left 
most indicators on the air flow graph. The first digit is the 
100’s and  illuminates for  2 seconds. Next, the tens digit 
illuminates  for  2  seconds,  followed  by  the  ones  digit 
illuminating for 2 seconds. If one of the numbers is zero, 
then  no  lights  will  illuminate  for  that  number  on  the 
particulate graph. 
The device then returns to Normal operating mode. 
 

The  FAAST  8251BPI  can  output  its’  3-digit  address 
through  the  user  interface.  This  can  be  accessed  from 
the  user  interface  by  pressing  and  holding  the  MODE 
button  for  3  seconds.  After  3  seconds  the  first  segment 
on the airflow display turns amber indicating the device is 
in  Address  Blink  mode.  Release  the  MODE  button  and 
the  device  gives  the  3-digit  address  by  lighting  the 
particulate  bar  graph  the  appropriate  number  of 
segments  for  each  digit.  The  current  digit  displayed  is 
indicated  by  the  6  left-most  indicators  on  the  airflow 
graph. The first 3 segments are the loop. 

-  8100 

Summary of Contents for 8251BPI

Page 1: ...ximum single pipe length 80m External pipe diameter 25mm Internal pipe diameter 15 21mm Specifications 1 Introduction 2 Scope of this Manual 2 Description 2 Features 2 Items Included with Unit 2 Insta...

Page 2: ...all be discerned by monitoring the user interface at either the local or remote display Features Clip intelligent protocol 8251BPI only Advanced detection using blue LED and IR laser technology Monit...

Page 3: ...xhaust pipe into the output port ensuring a snug fit DO NOT glue these pipes Wiring Before working on the FAAST system notify all required authorities that the system will be temporarily out of servic...

Page 4: ...N C T7 22 Fire 2 COM 21 Fire 2 N O 20 Fire 1 N C T6 19 Fire 1 COM 18 Fire 1 N O 17 Action 2 N C T5 16 Action 2 COM 15 Action 2 N O 14 Action 1 N C T4 13 Action 1 COM 12 Action 1 N O 11 Alert N C T3 10...

Page 5: ...he unit Table 1b FAAST 8100 Terminal Designations Notes a the Terminal Blocks are numbered with T11 to the top and T1 at the bottom b Terminal Block T2 is unused SLC Number Name Terminal Block 35 Ext...

Page 6: ...ard must be installed on the front panel of the FAAST aspirating smoke detection system For installation first slide the card into the bottom pocket then beneath each of the mounting tabs If necessary...

Page 7: ...segment is lit in amber Labels Detector faults are labelled adjacent to the indicators on the Air Flow Fault graph User Interface Buttons The User Interface has three buttons shown in Figures 9a 8251B...

Page 8: ...a configuration fault occurs during the initial configuration or the device is unable to operate due to the configuration the Urgent Fault relay will be set The device must be re configured using Pipe...

Page 9: ...the FAAST system resets the Fault and Alarm relays It then sets the Isolate relay and the ISOLATE Fault indicator illuminates on the user interface In this mode the fan switches off and the device do...

Page 10: ...ice returns to its previous state Once the passcode is accepted the locked out button s become active After 45 seconds of inactivity the Fault indicator begins to blink green After an additional 15 se...

Page 11: ...ice loses power for more than 72 hours the device sets the TIME fault indicating the time needs to be updated Logs Event Log The FAAST system is equipped with internal memory that can be configured to...

Page 12: ...of its peripherals and cannot function correctly Urgent Fault 7 Aspirator The Fan has stopped operating and requires immediate attention Urgent Fault 8 Filter 8251BPI Device Filter is clogged and requ...

Page 13: ...nt log viewer Email Notification The FAAST system has the ability to send e mail notifications to an individual or organization Up to 6 different email addresses may be stored for notification Each em...

Page 14: ...est and fans speed test retrieve and view logs in graph and tabular form control test and monitor FAAST aspirating detectors A comprehensive Help Menu is available from the Menu Bar to guide the user...

Page 15: ...ing updated ii b ii above Right click the device and select Get Configuration for an existing detector being maintained Section C CONFIGURING FAAST XM 8000 Series in PipeIQ A Configuration the followi...

Page 16: ...ces using PipeIQ software the default Password is password Caution if a Default Password is changed and then lost there may be a delay before Pertronic can identify the password so that it can be acce...

Page 17: ...Lock Out Test initiates the self test mode and simulates a Fire 2 Alarm condition The Alarm relays are also latched after the programmed delay Reset to Reset latched Alarms and Defects Isolate initiat...

Page 18: ...Target Sensitivity for each of the activation levels Alert Action 1 Action 2 Fire 1 and Fire2 the Target Sensitivity represents the sensitivity at the Sampling Point and equates to the sensitivity of...

Page 19: ...he Sensitivity settings used by VEWFD EWFD or SFD to identify appropriate settings for the system being configured then apply settings suitable to the CUSTOM constraints vi accept any advisory notices...

Page 20: ...e Day values simply by pressing the arrow viii Select the device from the tree right click and select Device Information record the following details in Section H FAAST XM System Validation Form a Fan...

Page 21: ...Configuration Sensor the Threshold Levels are converted to five Activations Levels in the panel ALERT ACTION 1 ACTION 2 FIRE 1 and FIRE2 Set the Sensitivity for each Activation Level per the Table bel...

Page 22: ...activate as a Smoke Alarm or ACTION2 FIRE 1 and one of the pre Alarm thresholds ALERT ACTION 1 or ACTION 2 may be combined on a single circuit on the F16e provided the circuit is configured for Reside...

Page 23: ...onitor Live Events as they occur Search for Live Events Produce Reports in pdf doc or xls format Clear Live Events Stored Events Retrieve Stored Events Search for Stored Events produce Reports in pdf...

Page 24: ...ual holes meets the minimum performance requirements for individual points Note that this may require reference to the approval compliance notes for the particular ASD system and should also take into...

Page 25: ...cating smoke has been detected this is the Transport Time for this Sample Point the Maximum Transport Time shall be less than the maximum time specified within the design documentation engineering spe...

Page 26: ...erify the settings are suitable for the site refer to Section C Device Details F2g System Handover During the commissioning all results shall be recorded These along with all configuration data shall...

Page 27: ...34 1 64 1 65 34 3 35 1 68 1 70 35 3 36 1 73 1 75 36 4 37 1 78 1 80 37 4 38 1 83 1 85 38 4 39 1 88 1 90 39 5 40 1 92 1 95 40 5 41 1 97 2 00 41 6 42 2 02 2 05 42 6 43 2 07 2 10 43 6 44 2 12 2 15 44 7 4...

Page 28: ...lterations occurring after the date of manufacture In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other warranty expressed or implied what...

Page 29: ...umber Loop Address Contact Person Customer Name Facility Name Facility Location Device Location Site Address Night Mode Start Time End Time Daylight Saving Starts On Ends On Time Format 12 Hour 24 Hou...

Page 30: ...Action 1 Action 2 Fire 1 Fire 2 Urgent Isolate Minor AirFlow Flow Boundary Flow Delay Sec User Interface Button Activation Passcode Button Lock Out Test Reset Isolate ModBus Passcode Address System T...

Reviews: