4. PROGRAMMING

To program operation of automation, use the microswitches as
shown  below.

Ü

You must press the RESET push-button after every program-
ming job.

Function logics

The following are available:
A1/A2 = “Automatic”

S1/S2 = “Safety”

E1/E2/B  = “Semi-automatic”

C = “Dead man”

Operation of automation in the different logics is indicated in
Tables 4-5-6-7-8-9-10-11.

Pause time

Pause time is waiting time in open position before re-closing when
an automatic logic was selected.
Pause times include pre-flashing if any

Operation of warning light

Used to change the appearance of the warning light at closing
by making it flash.

Pre-flashing

Flashlight pre-flashing time of 5 sec before any movement can be
selected. This warns anyone near the gate that it is about to
move.

(1) OPEN B input commands partial opening.
(2) With pre-flashing selected, movement begins after 5 sec.
(3) If the pulse is sent during pre-flashing, counting is restarted.
(4) OPEN B input commands closing.
(5) Push-button must be kept pressed to activate gate movement.  When the

push-button is released, the gate stops.

1

2

3

4

5    6     7

Operation of warning light

Gate status

SW6

Closed

Opening/Open

Closing

ON

OFF

Light

Flashing

Light

Off

Steady light

Pre-flashing (2)

SW7

Yes

ON

No

OFF

 Logic

SW1

SW2

SW3

E1

ON

ON

ON

B

OFF

ON

ON

S2

ON

OFF

ON

E2

OFF

OFF

ON

A1

ON

ON

OFF

C

OFF

ON

OFF

S1

ON

OFF

OFF

A2

OFF

OFF

OFF

Pause time (sec) (1)

       Logic

A1-A2-S2

S1

SW4 SW5

5

15

ON

ON

10

30

OFF

ON

30

60

ON

OFF

120

180

OFF

OFF

ON

OFF

(1) Pause times include pre-flashing if any

(2) Pre-flashing begins 5” before every movement.

PULSES

LOGIC  A1

SAFETY DEVICES

no effect

freezes pause until

disengagement

reverses motion

no effect
no effect

STOP

no effect

stops the count

stops

stops

no effect

GATE STATUS

CLOSED

OPEN ON PAUSE

CLOSING

OPENING

STOPPED

OPEN A - OPEN B (1)

opens and  closes

after pause time (2)

re-closes after 5" (3)

reverses motion

no effect

re-closes (2)

TABLE 4

 LOGIC A1 (AUTOMATIC)

TABLE 5

 LOGIC A2 (AUTOMATIC PLUS)

PULSES

LOGIC  A2

SAFETY DEVICES

no effect

when disengaged,

re-closes after 5”

stops and reverses

at disengagement (2)

no effect

no effect

STOP

no effect

stops the count

stops

stops

no effect

GATE STATUS

CLOSED

OPEN FOR PAUSE

CLOSING

OPENING

STOPPED

OPEN A - OPEN B (1)

opens and  closes

after pause time (2)

re-closes after 5" (3)

reverses motion

no effect

re-closes (2)

TABLE 8

  LOGIC E1 (SEMI-AUTOMATIC)

SAFETY DEVICES

no effect

no effect

reverses motion

no effect

no effect

GATE STATUS

CLOSED

OPEN

CLOSING

OPENING

STOPPED

OPEN A - OPEN B (1)

opens (2)

re-closes (2)

reverses motion

stops

re-closes (when safety devices

engaged,  it re-opens) (2)

STOP

no effect

no effect

stops

stops

no effect

PULSES

LOGIC  E1

LOGIC  S1

PULSES

GATE STATUS

CLOSED

OPEN FOR PAUSE

CLOSING

OPENING

STOPPED

OPEN A - OPEN B (1)

opens and  closes

after pause time (2)

closes

immediately (2-3)

reverses motion

reverses motion

re-closes (2)

STOP

no effect

stops the count

stops

stops

no effect

SAFETY DEVICES

no effect

when disengaged,

re-closes after 5”

reverses motion

no effect
no effect

TABLE 6 

 LOGIC S1 (SAFETY)

LOGIC  S2

PULSES

STOP

no effect

stops the count

stops

stops

no effect

GATE STATUS

CLOSED

OPEN FOR PAUSE

CLOSING

OPENING

STOPPED

OPEN A - OPEN B (1)

opens and  closes

after pause time (2)

closes immedi-

ately (2-3)

reverses motion

reverses motion

re-closes (2)

SAFETY DEVICES

no effect

freezes pause until

disengagement

stops and reverses at

disengagement (2)

no effect
no effect

TABLE 7

  LOGIC S2 (SAFETY PLUS)

TABLE 11 

 LOGIC C (DEAD MAN)

TABLE 9 

 LOGIC E2 (SEMI-AUTOMATIC PLUS)

SAFETY DEVICES

no effect

no effect

s t o p s   a n d   r e v e r s e s

a t   d i s e n g a g e m e n t   ( 2 )

no effect

no effect

GATE STATUS

CLOSED

OPEN

CLOSING

OPENING

STOPPED

OPEN A - OPEN B (1)

opens (2)

re-closes (2)

reverses motion

stops

re-closes (when safety devices

engaged,  it re-opens) (2)

STOP

no effect

no effect

stops

stops

no effect

PULSES

LOGIC  E2

TABLE 10

  LOGIC B (SEMI-AUTOMATIC)

GATE STATUS

CLOSED

OPEN

CLOSING

OPENING

STOPPED

LOGIC  B

PULSES

OPEN A

opens ( (2)

no effect

no effect
no effect

completes

 opening (2)

OPEN B (4)

no effect

closes(2)

no effect
no effect

completes

closing (2)

STOP

no effect

no effect

stops movement
stops movement

no effect

SAFETY DEVICES

no effect

prevents closing

stops movement

no effect

prevents

closing

GATE STATUS

CLOSED

OPEN

CLOSING

OPENING

STOPPED

LOGIC  C

OPEN A (5)

opens

no effect

no effect

completes

 opening

OPEN B (4 e 5)

no effect

closes

no effect

completes

closing

SAFETY DEVICES

no effect

prevents closing

stops movement

no effect

prevents

closing

STOP

no effect

no effect

stops movement
stops movement

no effect

CONTROLS HELD DOWN CONTINUOUSLY