Advanced Programming: 

To access ADVANCED PROGRAMMING, press and hold key F 
and then press key +:

•  Release key +, the unit displays the name of the first 

function.

•  Release key F, modify the value of the function with keys 

+ and -.

•  Press and hold key F, the unit displays the name of the 

next function, and if you release it, the value that can be 
modified with keys + and -.

•  When you reach the last function, press F to exit the pro-

gram, the unit resumes monitoring input status.

The following table shows the sequence of functions 
accessible in ADVANCED PROGRAMMING:

ADVANCED PROGRAMMING

MAXIMUM TORQUE AT INITIAL THRUST:

The motors operate at maximum torque 
(ignoring the torque setting) at start of 
movement. Useful for heavy leaves.

 = Active 

= Disabled

LAST STROKE AT CLOSING:

The motors are activated at full speed for 1 
second to facilitate locking of the electric lock.

 = Active 

=Disabled

REVERSING STROKE:

Before opening, while the gate is closed, 

the motors thrust to close for 2 seconds thus 
facilitating release of the electric lock.

 = Active 

 = Disabled

LEAF 2 OPENING DELAY (2 s):

Enables delayed start (at opening) of leaf 2, 
avoiding interference between leaves.

 = Active 

 = Disabled

OPENING FAIL SAFE:

If this function is activated, it enables the 
monitoring of the opening safety photocell 
before the opening movement. If the test fails  

the gate does not open.

 

= Active 

 = Disabled

PRE-FLASHING (5 s):

Activates the flashing lamp for 5 seconds before 
start of movement.

 = Active 

 = Disabled

ELECTRIC LOCK ON LEAF 2:

For using the electric lock on leaf 2 instead 
of on leaf 1.

 = Active 

 = Disabled

INDICATOR-LIGHT:

 : the output functions as a standard indicator-

light (ON at opening and pause, flashing at 
closing, and OFF when gate is closed). 
     : the output is ON when the gate is open or 

in pause. OFF in all other conditions. 

  the output is ON when the gate is closed. 

OFF in all other conditions.
All other values correspond to the extra time 
compared to normal work time (opening or 
closing) when the output can be used - via a 
relay - to power a courtesy light. Time can be 
adjusted from   to 

 sec. in 1 sec. steps, 

and from    to 

 min. in 10 sec. steps.

CLOSING PHOTOCELLS REVERSE AT RELEASE:

Enable this function if you want the closing 

photocells to stop movement and reverse at 

release. Default setting is immediate reverse.

 = Active 

 = Disabled

ASSISTANCE REQUEST (combined with next 
function):

If activated, at the end of countdown (settable 
with the next function i.e. “Cycle programming”) 
it affects 8 s of pre-flashing at every Open 
pulse (job request).  Can be useful for setting 
scheduled maintenance jobs.

 = Active 

 = Disabled

CYCLE PROGRAMMING:

For setting countdown of system operation 
cycles. Settable (in thousands) from   to 
thousand cycles. The displayed value is updated 
as cycles proceed.
This function can be used to check use of the 
board or to exploit the “Assistance request”.

OPENING No. 2 FAIL SAFE:

When enabled the STOP input can be used 

for the connection of a second  monitored  
opening safety device 

 = Active 

 = Disabled

Exit from programming and return to inputs 
status monitoring.

NOTE

: Parameter modifications take effect immediately. 

Exit out of programming to save changes. If the equipment 

is powered down before returning to normal status monitor-
ing, any unsaved modifications will be lost.

To restore programming defaults, press and hold the 

three b, -, F simultaneously for 5 seconds.

EXTRA WORK TIME:

If reversing occurs, and if the leaf does not 
reach its end contact point, you can activate 
this function to increase work time.

    = Active 

 

  = Disabled

Display

Function

Default

Display

Function

Default

Summary of Contents for 750 Bi

Page 1: ...te Operator FAAC International Inc Headquarter East Coast Operations 3160 Murrell Road Rockledge FL 32955 Tel 800 221 8278 www faacusa com FAAC International Inc West Coast Operations 357 South Acacia...

Page 2: ...nnection 9 2 5 Air Bleed Operations 10 2 5 Installing The Gate 11 3 FINAL OPERATIONS 12 3 1 Adjusting the By Pass Valves 12 4 MANUAL OPERATION 12 5 MAINTENANCE 12 455D CONTROL BOARD 1 General Descript...

Page 3: ...an usage Locate the gate such that persons will not come in contact with the vehi cular gate during the entire path of travel of the vehicular gate c The gate must be installed in a location so that e...

Page 4: ...ipment may reach high thermal temperatures during normal operation therefore use caution when touching the external housing of the gate operator Use the manual release mechanism according to the proce...

Page 5: ...factory or loa ding dock area or other locations not accessible by or intended to service the general public CLASS IV RESTRICTED ACCESS VEHICULAR GATE OPERATOR A vehicular gate operator or system int...

Page 6: ...P OIL Operating ambient temperature 4 F 131 F 20 C 55 C Protection class IP 55 Weight 16 5 lb 7 5Kg Pump capacity 0 75 l min Max leaf length 13 ft 4 m Min leaf length 8 ft 2 4 m 1 Exposure to direct s...

Page 7: ...keep a minimum distance between the rotation axis of the hinge and the post of 2 4 in 60mm fig 6 a Insure that the cavity where the drive unit is located is well drained by means of pipes gravel drai...

Page 8: ...r the two hydraulic lines that run from the drive unit to the power unit 8 Weldtheboxhalvestothefoundationplateandtooneanother so as to enclose the drive unit on four sides Be sure to protect the driv...

Page 9: ...hydraulic control unit fig 13 C A B D CLOSE OPEN INT EXT 12 1 2 3 4 A B C D E 13 The control unit fitting beside the green by pass screw must be connected to the drive unit fitting that is within the...

Page 10: ...and loosen the air bleed screw for the closing movement fig 12 ref C as shown in fig 16 7 release any air from the hydraulic circuit until non emulsified oil appears 8 tighten the air bleed screw befo...

Page 11: ...e rotation axis fig 18 Spot weld the bushing to the U section Check that the system setup is correct by manually simulating complete opening Carefully weld the bushing to the section fig 19 Close the...

Page 12: ...ed to set of the bypass valve tripping threshold The red screw adjusts the closing pressure of the leaf The green screw adjusts the open pressure of the leaf To increase pressure turn the screws clock...

Page 13: ...This page is intentionally left blank 13...

Page 14: ...n be excluded Thrust Force Adjustable on 50 levels for each motor Terminal Board Inputs Open Open Free Leaf Stop Limit switch Opening Safety Devices Closing Safety Devices Power Supply Earth Terminal...

Page 15: ...connected to this input See the next paragraph on how to connect a monitored device If this input is active when the gate is open it will prevent the leaf closing movement OP FSW Opening safety devic...

Page 16: ...e connected for the system to work 1 2 5 4 3 1 2 RX CL TX CL 9 10 11 12 13 14 15 16 17 18 19 OPEN A B STP CL OP FSW 24V TX FSW 20 21 W L LOCK 1 2 5 4 3 1 2 RX OP TX OP 1 2 5 4 3 1 2 RX CL TX CL 9 10 1...

Page 17: ...act Typically these photocells work in combination with other monitored photocell pro tecting closing or opening entrapment zones In that case they can t be monitored so they can only protect against...

Page 18: ...ill display the param eter s current value Value can be modified with keys and Press and hold F again the unit will display the name of the next function parameter When you reach the last function pre...

Page 19: ...nd OFF when gate is closed the output is ON when the gate is open or in pause OFF in all other conditions the output is ON when the gate is closed OFF in all other conditions All other values correspo...

Page 20: ...and black wires on the 455 D control board 7 Check force setting of the motors modify if necessary Note For hydraulic operators like the 400 force should be programmed to maximum level 50 8 Stop leaf...

Page 21: ...2 stops at opening and immediately begins its closing movement 5 Slow down at closing of leaf 2 6 Leaf 2 stops at closing and leaf 1 begins its closing movement 7 Slow down at closing of leaf 1 8 Leaf...

Page 22: ...i t n o c e s a e l e r n o d n a s k c o L g n i n e p o D E K C O L 3 f a e l e h t s e s o l C t c e f f e o N d e l b a s i d N E P O t c e f f e o N t c e f f e o N d e l b a s i d N E P O E c i...

Page 23: ...diately stops operation NB Effects on other active pulse inputs in brackets P A c i g o L S E S L U P S U T A T S E T A G A N E P O B N E P O P O T S S E C I V E D Y T E F A S G N I N E P O S E C I V...

Page 24: ...OR 1 MOTOR 2 CL COM OP 1 2 3 4 5 6 7 8 20 21 FCA1 FCA2 FCC2 FCC1 F J2 J6 J4 J5 J3 N L MAIN OP CL 24 V FSW B STOP A TX FSW 9 10 11 12 13 14 15 16 17 18 19 J1 PHOTO OP OPEN DEVICES PHOTO CL 24VDC RX PHO...

Page 25: ...prewired enclosure comes with dedicated terminal blocks for the connection of safety photocells that can be monitored by the control board for presence and correct operation One closing and one openi...

Page 26: ...ections If using non FAAC relay make sure the minimum switch volt age is less than 12Vac SHADOW INPUT Line Voltage MOTOR ON 24 VDC SHADOW LOOP 120V or 230 AC SHADOW KIT OPTION 8 7 10 1 2 5 Shadow Loop...

Page 27: ...This page is intentionally left blank 27...

Page 28: ...325 750 Complete Box 18 17 16 24 13 19 1 2 3 5 23 22 7 6 5 14 16 17 12 9 11 10 12 24 14 19 18 20 20 13 25 24 26 4 8 24 24 Part Part Number Description 13 63003324 750 Leveling Plate And Bolt 14 736624...

Page 29: ...Spring 30 pc pack 14 4180225 Manual Release 15 7049135 Valve Retainer 16 4404065 Inlet Valve Part Part Number Description 17 4404085 Lock Valve 18 7102055 Ferrule Fitting 19 4180395 Brass Bypass Valve...

Page 30: ...________________________________________________________ _________________________________________________________________________________________ _____________________________________________________...

Page 31: ...sume for them any other liability in connection with the sale or use of the products of beyond that extended herein The warranty hereinabove set forth shall not be deemed to cover maintenance parts in...

Page 32: ...2021 FAAC International Inc All Rights Reserved Published in September 2021 750 732028 Rev E US...

Reviews: