Operating Manual
8
3.1.2
Power Supply
The iWAP202 may only be powered from an IEEE 802.3af POE or IEEE 802.3at
POE+ power source. The equipment rating plate identifies which power supply type
is required for a specific variant.
3.1.3
Fitting the Cables
Warning! All cables should be connected to the IWAP202 via the correct cable
gland, fitted by a competent person.
Warning! If cable glands different to those supplied by Extronics are used, these
must be M20-sized cable glands meeting the requirements of
EN 60079-0:2012 for ATEX Category 2 GD equipment, and not
compromise the IP66 rating of the IWAP202 enclosure.
Warning! The installer MUST ensure that that all cables have adequate mechanical
protection to avoid damage.
3.1.4
Ethernet Cable Installation
Pass the Ethernet cable through the gland, and terminate in an RJ45 connector. Plug
into the Ethernet input socket as shown (15). Ensure the gland is correctly sized for
the cable used, and fully tight.
3.1.5
RJ45 Ethernet Cable Option
4 =Access point,
5 = Extronics iSOLATE500 or iSOLATE501 providing Ex ia RF outputs
6 = RF connectors,
15 = Ethernet surge arrestor with RJ45 connector.
22 = Option lightning surge arrestor