Operating Manual
38
In case of an external charger, check that it charges the batteries with a voltage
suitable for the IUPS101.
7.13
(021) Message: Maximum Current of the source (Input limit)
exceeded; transfer prohibited
The power output of the consumers exceeds the one specified for the source, and
the transfer relay cannot be activated. The IUPS101 operates in inverter mode.
•
This situation occurs only if you have deactivated the parameter {1436} Solution:
•
Check that the configuration of the maximum current for the source {1107}
corresponds to the maximum current of the source connected at AC In.
•
Reduce the number or power output of the consumers.
In this case, the transfer relay is not activated and the recharging of the
batteries cannot take place. If this situation continues, you might discharge
your batteries.
7.14
(022) Error: Voltage at AC Out
An unwanted voltage is present at AC Out.
Solution:
•
. check that you have not reversed the cabling of AC input and output.
•
. no source must be connected to the IUPS101 output (AC-Out).
•
. check the cabling of the installation.
7.15 (023) Error: Phase not defined
The jumper of phase selection (L1, L2 ou L3) is missing on the IUPS101.
The IUPS101 cannot operate without the phase being defined.
Solution: Check the phase definition jumper in the cable connection zone.
Refer to the IUPS101 manual for more information.
7.16 (024) Message: Control the battery of the clock
The maintenance battery is discharged. To avoid the clock goes back to zero in case
of a blackout, its replacement is necessary. Refer to the IUPS101 manual for this
replacement.
7.17 (041) Alarm: Overtemperature TR
The temperature of the IUPS101 is excessive and the output power is limited.
This message can also occur after a long operation in a too hot environment.
7.18
(042) Stop: Source at the output
A source of energy has been detected at the AC-Out output and supplies current to
the IUPS101.
Method: check that you do not have a source of energy connected to the output.
Summary of Contents for iUPS101
Page 1: ...Installation Operating Manual iUPS101...
Page 55: ...Operating Manual 55...
Page 59: ...Operating Manual 59 11 5System Assembly Details...
Page 62: ...Operating Manual 62 14 Certification 14 1Atex Label...
Page 63: ...Operating Manual 63 14 2Atex Certificate...
Page 64: ...Operating Manual 64...
Page 65: ...Operating Manual 65...
Page 66: ...Operating Manual 66...
Page 67: ...Operating Manual 67...
Page 68: ...Operating Manual 68 14 3iUPS101 EC Declaration of Conformity...
Page 69: ...Operating Manual 69 14 4UPS System EC Declaration of Conformity...