E3 – Classroom where lighting levels can be changed 

using pushbuttons

‟Mode - Extronic”

Normally the premises are controlled automatically using 

scenes 10, 14 and 15, and there are also the following manu-

al functions: 

•  Board lighting

 can be switched on manually with a push-

button.

• 

Projector mode

, ceiling lighting is reduced to 1% by press-

ing a pushbutton.

•  Main lighting is switched back

 to normal level with one or 

more pushbuttons.

“Mode” jumper is set to Extronic.

The low-level delay time is increased from 5 minutes to 30 min-

utes (base level).

(This can be increased to 30 minutes by removing the “Occu-

pancy Activity” jumper.)

Comments

To prevent the lighting from being switched on automatically 

when presence is detected, activate the “No start” function. This 

is done by removing the “LED indication” jumper. One or more 

pushbuttons will then be required to switch the lighting on, by 

activating scene 3.

In this example the scenes are used as follows:

Scene 1

:     Manual board lighting and main lighting.

Scene 2:

     Manual projector mode.

Scene 3:    

Main lighting is switched on manually (normal level).

Scene 10:

   Automatic level.

Scene 14:

   Low-level delay of 5 minutes at base level.

Scene 15:  

Switched off, 0% lighting when no-one is present.

Main lighting

Board lighting

Pushbutton

scene 1 (main lighting and board lighting)

Pushbutton

scene 3 (main lighting)

Pushbutton 

scene 3

Pushbutton

off 

Pushbutton

scene 2 (prjector mode)

The board lighting is programmed as follows:

Scene 1

:  0% (manual board lighting and main lighting).

Scene 2

:  0% (manual projector mode).

Scene 3:

  100% main lighting is switched on manually.

Scene 10:

  0% automatic level.

Scene 14:

  0% low-level delay of 5 minutes at base level.

Scene 15:

  0% lighting when no-one is present.

In this case the ceiling fittings are programmed as follows:

Scene 1:

  100 % (manual board lighting and main lighting).

Scene 2:

  1% (manual projector mode).

Scene 3:

  100% main lighting is switched on manually.

Scene 10:

  100% automatic level.

Scene 14:

  10% low-level delay of 5 minutes at base level.

Scene 15:

  0% lighting when no-one is present.

Extronic Elektronik AB +46 8 609 29 00

2015-12-14

Summary of Contents for PD-33 DL

Page 1: ... of activity in the premises We recommend that the LED is disconnected once adjust ment is complete see Detector settings to minimise the risk of tampering Basic terminology Broadcast Broadcast addressing means that the detector sends its DALI commands to all light fittings at the same time Groups The light fittings in a DALI system can also be con trolled using group addresses DALI supports 16 gr...

Page 2: ... delay 1 5 Groups 1 to 5 get 1 5 lighting level during low level delay F Used with level selectors NP 2T DL and NP 3T DL 6 E Not used Mode selector Selection number 0 9 A F Choice of control by broadcast or groups 1 to 15 Selection number determines which group is used Selection number 0 is used for Broadcast Selection numbers 1 to 9 send DALI commands to the re spective group Selection numbers A ...

Page 3: ...belong to the same group or are in Broadcast mode To prevent the lighting from being switched on automatical ly No start remove the LED indication jumper The lighting can be switched off using one or more push buttons that send the DALI command off The lighting can be switched on using one or more push buttons that send the DALI command recall max level A 30 minute low level delay can be selected ...

Page 4: ...ation example Mode Direct level G1 Simple example of controlling a DALI loop with PD 33 DL No programming of light fittings is needed Broadcast to all light fittings with direct control of all light fittings in the loop and without any need for programming detectors or light fittings When presence is detected the light fittings are switched on at the normal level of 100 After the presence delay th...

Page 5: ...ommand go to scene 1 5 or 10 A 30 minute low level delay can be obtained if the Occu pancy activity jumper is removed normally 5 minutes Manual scenes can be created using scenes 1 5 to pro vide lighting for cleaning or showing films for example Detectors assigned to different groups work independently of each other Manual control off Manual control No start Using scenes 1 to 5 manually Presence s...

Page 6: ...nic 0 Broadcast Selection number Mode Extronic 0 Broadcast Selection number Mode Extronic 0 Broadcast Selection number Mode Extronic 0 Broadcast Selection number Application example Mode Extronic E1 Garage with some light fittings that are never switched off Setting Mode Extronic The detectors jointly control the whole garage using scenes 10 14 and 15 The light fittings near the entrances should n...

Page 7: ...The low level delay time is increased from 5 minutes to 30 min utes by removing the Occupancy Activity jumper In this case the light fittings are programmed to Scene 10 Max light level when presence is detected normal level Scene 14 Low level no presence detected 5 base level Scene 15 0 Scene 1 100 cleaning lighting manual level that is switched on with pushbutton 230 VAC Mode Extronic Selection n...

Page 8: ...lows Scene 1 Manual board lighting and main lighting Scene 2 Manual projector mode Scene 3 Main lighting is switched on manually normal level Scene 10 Automatic level Scene 14 Low level delay of 5 minutes at base level Scene 15 Switched off 0 lighting when no one is present Main lighting Board lighting Pushbutton scene 1 main lighting and board lighting Pushbutton scene 3 main lighting Pushbutton ...

Page 9: ...italout Max 200mA Timer 0 120minutes ExtronicAB Stockholm Sweden LevelswitchNP 3TDL 100 240VAC Buspowersupplyandbuscontroller fordigitallydimmableluminaires Timerforswitchingofthelight 12345678910111213 141516171819202122232425 Timer 15m 30m 1h 2h 0 100 100h 100 100h 0 2 5 5 10 20 Slow Fast StartBlock Min Max LowLevel Light Sensor SwitchDet Off Min Max 4 5 6 78 9 10 11 15 16 19 20 22 23 24 Min Reg...

Page 10: ...circuit board is moved upwards it lowers the detection field and vice versa The vertical adjustment of the circuit board is preset at 5 The recommended installation height for best detection is 1 9 2 2 m Masking lens elements Lens elements can be masked to limit the detection area Self adhesive aluminium foil tape like that used to protect win dows will block 100 per cent of thermal radiation Acce...

Reviews: