detector can hear if anyone “hides” behind the archive
shelfs and the lighting remains activated for maximum
four times the time set on potentiometer “Timer”. If the
timer is set on 5 minutes the lighting remains on for 4 x
5 minutes = 20 minutes. The detection must take place
within that time.

When the presence has ceased the lighting is reduced
to approx. 2 per cent. After two hours without any
presence the lighting is completely switched off to
eliminate no-load losses.

7. Accessories

Field indication diode BL-1

Used for adjusting detection area. Art. No. 13035.

For further information see

handbook

“Presence

Detection”

Protective Grille

For mounting in exposed premises as for indoor sports.
There is also one model that can be used for mounting
a detector in 45º with angel plate to a wall.

For further information see

handbook

“Presence

Detection”

Universal bracket

BR1, BR2, BR3 can be used when the detector cannot
be mounted directly in the corner. With the bracket the
detector can be moved out a short distance and still
give maximum coverage.

Use with precaution.

Contact Extronic for further advice and information
when a bracket is used.

Logic modules

As for manually switched on lighting.

EX-11: Two channels i.e. one channel for main lighting
and one for board lighting.

EX-13: Four + One channel i.e. in a divided Gym with
two levels of lighting in each half and air-condition.

EX-22: Like EX-11 but guided by DSI-protocol and
constant-lighting with compensation for lights from
windows.

For further information see handbook “Presence
Detection”

Level control

Level switches NV2 / NV2-DSI:

Are intended for

use on HF fittings with 1-10 V low-level input,
dimmable 1-100%, and for control by presence
sensors. Using the level switch, one can switch
between two preset lighting levels.

Level switches NV2T / NV2T-DSI:

As NV2 / NV2-DSI

but they also have a built-in timer for control of the
supply voltage. Push-buttons, photocells etc. can also
be connected.

Acoustic detectors

Detector AD-500 / AD-600 has an input for PIR
presence detector.

Lens-library

See lens-library in handbook for a great number of
changeable lenses.

Rectifier EXE-2000 (13,65 VDC)

A Rectifier for mounting on DIN rail and suitable for
NORM box.

It has current limitation / short-circuit proof, max. 1,5 A
and suitable as power supply for PD-2210HF.

Handbook

Handbook “Presence Detection”.

Extronic AB • 08-771 26 00

5

08 04 29

12 VDC to any
other system

Presence

PD-2210HF

detector

EXTRONIC

2A

30

VDC

NO

NC

C

+ TP

Rectifier
EXE-2000

1

8

7

6

5

4

3

13

12

11

10

9

2

17

16

15

14

21

20

19

18

22

24

23

25

Stabilized power supply EXE-2000

Short circuit protection, current limited

Extronic AB • Stockholm • Sweden

Secondary

Voltage: 13,65

Current: Max 1,5 A

Primary

Voltage: 230 V ~

Current: Max 0,2 A

15 & 17=IN 230 V~
10 & 12 = 
11 & 13 = OUTPUT -

Indication of

secodary voltage

EXTRONIC

Security

+ +

12 13 14 15 16

11

10

9

1

6

8

5

7

4

3

2

For 1-10 V regulating of luminaires
with dimmable HF ballasts and
timer for 230V regulating

Extronic AB • Stockholm • Sweden

Level switch NV-2T

Version 1.0

Current for low level
regulating: Max. 100 mA
Two 1 - 10 V-levels
Timer: 1 - 120 min.

Incoming

phases

N

L1

L2

L3

L1 N

1 -10 V

C NO

+

1 -10 V

The contactor

should be adapted

to the load.

1 x 4 x 0.25 mm

2

Level selector

NV-2T

Wiring diagram for applcation example with “Dynamic lighting

control” and dimmable HF ballasts.

Reviews: