MTPX Plus Twisted Pair Matrix Switchers • Installation
2-2
Installation
Mounting the Switcher
UL guidelines
The following Underwriters Laboratories (UL) guidelines pertain to the installation
of the MTPX Plus into a rack.
1
.
Elevated operating ambient temperature
— If the equipment is installed in a
closed or multi-unit rack assembly, the operating ambient temperature of the
rack environment may be greater than room ambient temperature. Therefore,
install the MTPX Plus in an environment compatible with the maximum
ambient temperature (Tma = +122 °F, +50 °C) specified by Extron.
2
.
Reduced air flow
— Install the equipment in a rack so that the amount of air
flow required for safe operation of the equipment is not compromised.
3
.
Mechanical loading
— Mount the equipment in the rack so that a hazardous
condition is not achieved due to uneven mechanical loading.
4
.
Circuit overloading
— Connect the equipment to the supply circuit and
consider the effect that circuit overloading might have on overcurrent
protection and supply wiring. Appropriate consideration of equipment
nameplate ratings should be used when addressing this concern.
5
.
Reliable earthing (grounding)
— Maintain reliable grounding of rack-
mounted equipment. Pay particular attention to supply connections other
than direct connections to the branch circuit (e.g. use of power strips).
Mounting instructions
The MTPX Plus switchers are housed in a rack-mountable, 2U high (matrix sizes
1616 and smaller) or 3U high (matrix sizes 1632 and larger)
metal enclosures with
mounting flanges for standard 19" racks. If desired, rack mount the unit as follows:
1
.
Insert the switcher into the rack, aligning the holes in the mounting ears with
those in the rack (figure 2-1).
2
.
Secure the switcher to the rack using the supplied bolts.
N
Extron recommends that you allow 1U of rack space above and below the
switcher for ventilation.
Figure 2-1 — Installing the switcher in a rack
Summary of Contents for MTPX Plus Series
Page 1: ...MTPX Plus Series Mini Twisted Pair Matrix Switcher 68 1383 01 Rev B 09 08 ...
Page 4: ......
Page 20: ...Introduction cont d MTPX Plus Twisted Pair Matrix Switchers Introduction 1 10 ...
Page 32: ...Installation cont d MTPX Plus Twisted Pair Matrix Switchers Installation 2 12 ...
Page 92: ...Operation cont d MTPX Plus Twisted Pair Matrix Switchers Operation 3 60 ...
Page 94: ...Operation cont d MTPX Plus Twisted Pair Matrix Switchers Operation 3 62 ...
Page 178: ...Ethernet Connection cont d MTPX Plus Twisted Pair Matrix Switchers Ethernet Connection A 8 ...