DISCONNECT POWER BEFORE SERVICING

DESUNA LA ELECTRICIDAD ANTES DE HACER REPARACIONES

WARNING:

INSTALLATION INSTRUCTIONS

1.  Remove cover by removing (2) tamper proof-screws using security wrench  

 

 

supplied. Pull cover directly toward you. 

IMPORTANT

: Save security wrench.

2.   Dryers should be placed at least 2 feet (61cm) apart and at least 12” (30cm) from wash-

basin. Do not install dryer over washbasin. Automatic dryers should be at least 18” (46cm) 
above any projection which may interfere with the operation of the automatic sensor.

 

 Hold the backplate to the wall at the suggested 

MAXIMUM

 mounting height. Measure 

from bottom edge of 

backplate

 to the 

floor (Ref. Dimension “A”, Fig. 1):

 

 

 

 

CHILDREN

 

 

MEN 

WOMEN 

(depends on age) 

DISABLED

 

 

44” (112cm) 

42” (107cm) 

32 to 42” (81-107cm) 

36” (91cm)

3.   Mark the locations of the four mounting holes and the conduit entrance location on the 

wall. (The conduit entrance is the proper hole diameter for 1/2 inch (13mm) conduit.)

4.   Fasten the backplate to the wall where previously marked.

 

RECOMMENDATION:

 

Wood wall – 

No. 14 (M6) wood screws, 2 3/4” (70mm) long

 

Cement or brick – 

1/4” (M6) stud expansion bolts, 3” (76mm) long

 

Hollow wall – 

1/4” (M6) toggle bolts, length depends on wall thickness

5.  Run service wire to the dryer location and connect to lead wires.
 

 IMPORTANT: All units must be supplied with 3 wire service. Use No. 12 or 14 wire as 
required by local electrical code. The ground wire must be connected to the dryer ground 
screw. Unit must be installed by a qualified licensed electrician.

 

CONNECT TO A DEDICATED CIRCUIT NOT TO EXCEED 20 AMPS.

 

 Dryers located in shower rooms or other wet locations should be equipped with ground 
fault interrupter(s).

6.   

Carefully 

replace the cover using (2) tamper-proof screws supplied. Apply a bead of caulk 

around edges of cover to wall.

Revised September 2008

O

wner

s

 M

anual

 

e

X

treme

A

ir

®

 

H

and

 D

ryers

F

igure

 1 - 

D

ryer

 M

ounting

(48mm)

(208mm)

6 3/16

7/8 (22mm) DIA. IN-WALL 
& SURFACE CONDUIT 
ENTRANCES 

MOUNTING HOLES FOR
1/4” (M6) DIA. SCREWS

(227MM)

8 15/16

7/16

(11mm)

7/16

(11mm)

“A”

8 7/16
(214mm)

FLOOR

Reviews: