3 - 5%

Max 3 mt

10

ENGLISH

ExAMPlEs of coRREcT connEcTion To ThE chiMnEy

In the presence of type B gas appliances with intermittent operation not intended for heating, they must have their own aeration and/or 

ventilation opening. 
The air inlets must meet the following requirements:

 

Š

they must be protected with grids, metal mesh, etc., but without reducing the net useful section;

 

Š

they must be made so as to make the maintenance operations possible;

 

Š

positioned so that they cannot be obstructed;

The clean and non-contaminated air flow can also be obtained from a room adjacent to that of installation (indirect aeration and 

ventilation), as long as the flow takes place freely through permanent openings communicating with the outside.

The adjacent room cannot be used as a garage, or to store combustible material or for any other activity with a fire hazard, bathroom, 

bedroom or common room of the building.

Flue gas eXhaust

The heat generator works in depression and is equipped with an outlet fan for flue gas extraction. There must be a single exhaust system for 

the generator. Using a flue that is shared with other devices is not allowed.

The components of the flue gas exhaust system must be chosen in relation to the type of appliance to be installed in compliance with:

 

Š

UNI/ TS 11278 in the event of metal chimneys, with particular attention to that stated in the specification; 

 

Š

UNI EN 13063-1 and UNI EN 13063-2, UNI EN 1457, UNI EN 1806 in the event of non-metallic chimneys.

 

Š

The length of the horizontal section must be minimal and, in any case, no longer than 3 metres, with a minimum upward slope of 3%

 

Š

There must not be more than 4 direction changes including the one due to the use of the "T" element.

 

Š

A “T” fitting with a condensation collection cap must be provided at the base of the vertical section.

 

Š

If the exhaust is not inserted in an existing flue, a vertical section with a windproof end piece is required (UNI 10683).

 

Š

The vertical duct can be inside or outside the building. If the smoke duct is inserted in an existing flue, it must be certified for solid fuel.

 

Š

If the smoke duct is outside the building, it must always be insulated.

 

Š

The smoke ducts must have at least one airtight inlet for flue gas sampling.

 

Š

All the sections of the flue gas duct must be accessible to inspection.

 

Š

Inspection openings must be provided for cleaning.

 

Š

If the generator has a fume temperature lower than  160°C+ ambient temperature caused by the high yield (contact technicians) it 

MUST be resistant to humidity.

 

Š

A flue system that does not respect the previous points or, in general, that does not comply with the regulations, may cause condensation 

phenomena inside it.

ChIMneY CaP

The chimney caps must meet the following requirements:

 

Š

they must have a useful outlet section no less than double that of the chimney/ducted system on which it is installed;

 

Š

they must be adapted in order to prevent the penetration of rain and snow in the chimney/ducted system;

 

Š

they must be built so that, in the event of winds coming from all directions and from any angle, the expulsion of combustion products 

is in any case ensured;

Protection from rain 

and wind

Condensation-proof 

"T" fitting with 

inspection plug 

Insulated flue

Insulated "T" 

fitting with 

inspection plug

Protection from rain and wind

"T" fitting with 

i n s p e c t i o n 

plug

COnneCtIOn tO the MaIns eleCtrIC suPPlY

The generator is supplied with an electric power cable to be plugged into a 230V 50 Hz socket, possibly with a circuit breaker switch. The 

socket must be easily accessible.

The electrical system must be compliant with standards. The efficiency of the earthing circuit must be checked. Unsuitable earthing of the 

system can cause malfunctioning for which the manufacturer will not be held liable. 

Power supply variations beyond 10% can cause faulty operation of the product.

FOr gerManY OnlY

the product can be connected to a shared flue

 (multi-connection) provided that the requirements of the regional and national regulations, 

amongst which DIN EN 13384-2, DIN V 18160-1, DIN 18896 and of the MFeuV-2007 (Muster-Feuerungsverordnung) are strictly complied with, 

and that the local chimney sweep has checked and approved the installation conditions. 

Please also remember the following indications, which the end user must comply with:

• 

The device can be operated only with the doors closed.

• 

The doors and all setting devices must remain closed when the device is not on (except for cleaning and maintenance operations).

Summary of Contents for GABRIELLA PLUS

Page 1: ...MADE IN ITALY design production GABRIELLA PLUS 004280494 Rev 000 UK pellet stoves USER MANUAL...

Page 2: ...2 ENGLISH APPLY TECHNICAL DATA LABEL...

Page 3: ...ENABLING DISABLING THE CHRONO 24 SETTINGS 26 Display 26 STAND BY 26 OPERATION WITH ADDITIONAL THERMOSTAT OPTIONAL 26 ADDITIONAL THERMOSTAT 27 ADDITIONAL THERMOSTAT INSTALLATION 27 DELTA T 27 FIRST LOA...

Page 4: ...retirer les pi ces en fa ence pierre naturelle ou m tal de la partie sup rieur du produit In den ersten Betriebsstunden k nnen durch den normalen Prozess des Temperatureinlaufs D mpfe und Ger che ent...

Page 5: ...ance has been installed as well as the instructions contained in this manual The use of the appliance must comply with all local regional national and European regulations The Manufacturer cannot be h...

Page 6: ...IF IT IS DISCONNECTED FROMTHE MAINS It is advised to position the power supply cable so that it does not come into contact with hot parts ofthe appliance The power supply plug must be accessible afte...

Page 7: ...clean the majolicas it is recommended to use a soft dry cloth If a detergent or liquid is used the latter could penetrate inside the crackles highlighting them SINCE THE PRODUCT CAN TURN ON AUTOMATICA...

Page 8: ...pace heating energy efficiency Space heating emissions at nominal heat output Space heating emissions at minimum heat output Nominal heat output Minimum heat output indicative Useful efficiency at nom...

Page 9: ...mestichotwaterproductionandinadjacentandcommunicating rooms 3 where the depression measured in situ between the external and internal environment is greater than 4 Pa N B Watertight appliances can als...

Page 10: ...always be insulated The smoke ducts must have at least one airtight inlet for flue gas sampling All the sections of the flue gas duct must be accessible to inspection Inspection openings must be prov...

Page 11: ...tension and rear closure 5 Install rear cover 6 Insert upper discharge UPPER FUMES OUTLET ASSEMBLY FOLLOW THE ASSEMBLY INSTRUCTIONS CAREFULLY ALWAYS FOLLOW THE ASSEMBLY INSTRUCTIONS IN COMPLETE SAFETY...

Page 12: ...This means that it is ideal for passive houses because it does not take air in from within the house combustion air To ensure the stove remains hermetically sealed the connection pipe for the combust...

Page 13: ...haust Fuse C Access to combustion chamber 230 V power supply D Lateral ducting K Serial input E Room probe Additional thermostat input F Room air outlet Ducting thermostat input G Display L Rear ducti...

Page 14: ...rmostat will allow for the duct motor to be controlled regardless of stove operation At this point simply set the desired temperature on the thermostat the thermostat will command the operation of the...

Page 15: ...CLOSE HOPPER STOVE DOOR This indication means that you have 60 seconds to close the hatch door and the pellet lid After the 60 seconds during ignition the stove will go into DEPR ALARM mode while dur...

Page 16: ...OTHER MATERIAL DAMAGES THE FUNCTIONS OF THE GENERATOR AND MAY INVALIDATE THE WARRANTY AND RELIEVE THE MANUFACTURER OF ALL RESPONSIBILITY PELLET HOPPER During stove operation the pellet hopper lid mus...

Page 17: ...ck keyboard 3 On off stove hold for 3 seconds 9 Degrees Celsius Fahrenheit 4 Set power 10 Press the button once to enable or disable the chrono 5 Set switch off delay The button allows to set the swit...

Page 18: ...gnal receiver Handle the remote control with care When it is not being used place it on the special base supplied The remote control must not be left in a place where it is exposed to direct sunlight...

Page 19: ...ed contact the contact of the external additional thermostat is closed Open contact the contact of the external additional thermostat is open Icon visible only if SET THERMOSTAT is set to LOW TA WI FI...

Page 20: ...nded to Ventilate the room well If present remove any majolica or natural stone parts from the top part of the product Activate the product at the maximum power and temperature Avoid remaining in the...

Page 21: ...Select the language using keys 4 or 5 Press key 6 to confirm and key 1 to scroll back through the menus until the initial page DEGREES This menu allows you to set the unit of measurement for the temp...

Page 22: ...ed modulation LOW TA HOT If the Set Thermostat is LOW TA set under the 7 threshold temperature checking is entrusted to the additional thermostat contact thus bypassing the on board temperature probe...

Page 23: ...E RANGE SECOND INCREASE RANGE IF THE FIRST IS INSUFFICIENT THIRD INCREASE RANGE IF THE FIRST TWO ARE INSUFFICIENT Controls procedure Press key 6 Press key 3 until EASY SETUP appears and confirm by pre...

Page 24: ...T Set thermostat PRG3 POWER PRG3 1 5 Set power PRG3 PRG4 START PRG4 OFF 00 00 Ignition time PRG4 STOP PRG4 OFF 00 00 Switch off time PRG4 MONDAY SUNDAY On off Enable disable days PRG4 SET PRG4 LOW TA...

Page 25: ...0 23 00 08 00 16 30 t 22 18 2 1 25 ENGLISH Time slot 1 start 02 00 stop 23 00 power 3 SET THERMOSTAT 22 C Time slot 2 start 08 00 stop 16 30 power 1 SET THERMOSTAT 18 C stove operation TIME SLOT SET P...

Page 26: ...HERMOSTAT DELTA T OFF value then the stove switches off after a preset factory delay and STAND BY will be displayed on the screen When the room temperature is lower than the SET THERMOSTAT DELTA T ON...

Page 27: ...round equal to 1 50 m Stove operation with the external thermostat connected in the TA terminal may differ depending on whether or not the STAND BY function is enabled ADDITIONAL THERMOSTAT INSTALLATI...

Page 28: ...function allows you to lock the display keys similar to mobile phones With the function active each time a key is pressed the message KEYS LOCKED will appear To lock the keypad press keys 1 and 5 simu...

Page 29: ...ions may lead to damage to the generator surfaces and invalidate the warranty CLEANING THE CERAMIC GLASS Never use abrasive or chemically aggressive detergents for cleaning The ceramic glass must be c...

Page 30: ...ush it towards the hearth wall C Reposition the ash conveyor making sure that it rests on the burn pot correctly and not on another surface of the combustion chamber Keep the burn pot clean using the...

Page 31: ...ER TOP PART Remove the deflector and eliminate any ash that may have deposited in the top part of the heat exchanger using the pipe cleaner supplied Pay attention to any ash that may have deposited on...

Page 32: ...ance must be performed at least once a year Giventhatthegeneratorusespelletsassolidfuel itrequiresannualroutinemaintenance whichmustbeperformedbyaQualifiedtechnician using only original spare parts Fa...

Page 33: ...1 2 3 4 5 33 ENGLISH HEAT EXCHANGER...

Page 34: ...s B Gaskets pellet hopper inspections ash drawer and door replace and apply silicone where indicated C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complet...

Page 35: ...ts B Gaskets pellet hopper inspections ash drawer and door replace and apply silicone where indicated C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper comple...

Page 36: ...ndicates the presence of an alarm On indicates the presence of an alarm The alarm can only be reset if the fumes motor has stopped and 15 minutes have passed since the alarm was displayed by pressing...

Page 37: ...kindly asked to separate this equipment and or batteries or accumulators included from other types of waste and to arrange for disposal by the municipal waste service It is possible to ask your local...

Page 38: ...38 ENGLISH...

Page 39: ...39 ENGLISH...

Page 40: ...39 0445 865911 39 0445 865912 info extraflame it www lanordica extraflame com TO FIND THE SERVICE CENTRE NEAREST TO YOU CONTACT YOUR DEALER OR CONSULT THE SITE WWW LANORDICA EXTRAFLAME COM The manufac...

Reviews: