background image

5

                                                 

CB20-EU-EN-V1.2    5/13 

Tips

 

for

 

automatic

 

scanning

 

The

 

receiver

 

works

 

by

 

comparing

 

the

 

strength

 

of

 

the

 

signal

 

received

 

from

 

one

 

breaker

 

to

 

the

 

next.

 

Observe

 

the

 

following

 

for

 

best

 

results.

 

 

Important:

 

The

 

first

 

strong

 

signal

 

encountered

 

may

 

not

 

be

 

the

 

strongest

 

there

 

is.

 

Do

 

not

 

stop

 

scanning

 

when

 

a

 

strong

 

signal

 

is

 

first

 

encountered.

 

It

 

is

 

essential

 

to

 

continue

 

scanning

 

until

 

all

 

the

 

breakers

 

are

 

tested

 

to

 

insure

 

the

 

correct

 

breaker

 

is

 

located.

 

 

Do

 

not

 

let

 

the

 

scanning

 

head

 

wander

 

around.

 

To

 

operate

 

well,

 

the

 

automatic

 

scanning

 

memory

 

needs

 

a

 

consistent

 

signal.

 

 

Keep

 

the

 

red

 

scanning

 

head

 

at

 

the

 

same

 

angle

 

relative

 

to

 

the

 

breaker

 

or

 

fuses

 

for

 

the

 

duration

 

of

 

the

 

test.

 

 

Keep

 

the

 

head

 

in

 

contact

 

with

 

the

 

breaker

 

during

 

each

 

sweep

 

to

 

ensure

 

consistency

 

in

 

the

 

proximity

 

of

 

the

 

head

 

to

 

the

 

breaker.

 

 

Test

 

only

 

the

 

same

 

side

 

of

 

each

 

breaker

 

during

 

a

 

test.

 

Pay

 

particular

 

attention

 

to

 

this

 

when

 

testing

 

a

 

vertically

 

hung

 

panel

 

which

 

may

 

have

 

neighboring

 

breakers

 

mounted

 

in

 

opposite

 

directions.

 

 

Always

 

reset

 

the

 

receiver

 

(away

 

from

 

the

 

distribution

 

board)

 

before

 

changing

 

any

 

test

 

condition.

 

Alternate

 

Scanning

 

Techniques

 

Due

 

to

 

the

 

differing

 

designs

 

of

 

circuit

 

breakers

 

it

 

may

 

sometimes

 

be

 

unclear

 

from

 

the

 

above

 

procedure

 

which

 

of

 

two

 

breakers

 

the

 

strongest

 

signal

 

comes

 

from,

 

particularly

 

if

 

it

 

appears

 

to

 

come

 

from

 

a

 

boundary

 

area

 

between

 

two

 

adjacent

 

breakers.

 

In

 

the

 

event

 

of

 

this

 

occurring,

 

one

 

of

 

the

 

following

 

variations

 

should

 

enable

 

clear

 

identification.

 

A:

 

Reset

 

the

 

receiver

 

and

 

scan

 

the

 

breakers

 

on

 

the

 

opposite

 

side

 

of

 

the

 

switch.

 

The

 

strongest

 

signal

 

may

 

be

 

found

 

at

 

the

 

top

 

of

 

the

 

breaker.

 

B:

 

Reset

 

the

 

receiver

 

and

 

scan

 

the

 

breakers

 

at

 

a

 

90°

 

angle

 

to

 

the

 

original

 

scan.

 

At

 

some

 

point

 

a

 

stronger

 

signal

 

will

 

be

 

found;

 

scan

 

at

 

the

 

new

 

angle.

 

 

Summary of Contents for CB20

Page 1: ...USER GUIDE Circuit Breaker Finder Receptacle Tester Model CB20 ...

Page 2: ...ormal use hazardous voltages may be present Double insulation Safety Note Remove the battery if the device is to be stored for longer than 60 days Cautions If the equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired This product is designed for use by suitably qualified personnel familiar with electrical supply systems Before usin...

Page 3: ...ED is ON and Red 2 The Low Battery LED is OFF If either of these conditions does not exist replace the battery Plug the transmitter into a live socket and move the receiver scanning head over the face of the transmitter The frequency of the beeping should become very rapid or change to a continuous tone The Indicating LED should turn Green when the scanning head is detecting a signal hotspot this ...

Page 4: ...the sensing tip in contact with the face of the circuit breaker or fuses The sensing tip must be flat against the circuit breaker at all times during the test Any tilt in the angle in one direction or another will affect the sensor s ability to pick up the signal 4 Slowly run the sensing tip along the row of circuit breakers Maintain a constant angle to the breakers as shown The frequency of the b...

Page 5: ...of the head to the breaker Test only the same side of each breaker during a test Pay particular attention to this when testing a vertically hung panel which may have neighboring breakers mounted in opposite directions Always reset the receiver away from the distribution board before changing any test condition Alternate Scanning Techniques Due to the differing designs of circuit breakers it may so...

Page 6: ...ceptacle GFCI Test 1 Before using the tester press the TEST button on the installed GFCI receptacle the GFCI should trip If it does not trip do not use the circuit and call a qualified electrician If it does trip press the RESET button on the receptacle 2 Plug the Transmitter Receptacle tester into the outlet Verify that the wiring is correct as described above 3 Press and hold the test button on ...

Page 7: ...ollection points or wherever batteries accumulators are sold Disposal in household trash or refuse is prohibited Disposal Follow the valid legal stipulations in respect of the disposal of the device at the end of its lifecycle Other Battery Safety Reminders Never dispose of batteries in a fire Batteries may explode or leak Never mix battery types Always install new batteries of the same type Pleas...

Page 8: ...at 40ºC 104ºF Storage Humidity 80 Operating Altitude 2000 meters 7000ft maximum Weight Transmitter 91g 3 2oz Receiver 136g 4 8oz Dimensions Transmitter 118 x 60 x 35mm 4 6 x 2 4 x 1 4 Receiver 196 x 55 x 36mm 7 7 x 2 2 x 1 4 Approvals UL CE UL Listed The UL mark does not indicate that this product has been evaluated for the accuracy of its readings Copyright 2013 FLIR Systems Inc All rights reserv...

Reviews: