Express ASX-31003-C Installation, Operating And Maintenance Instructions Download Page 5

5

Range Setting

Duct Pressure 

Range (in. WC)

Setpoint Controller 

(c16) Value

LOW

0-1

1.0

MID

0-2

2.0

HIGH

0-4

4.0

Operating Range:

As mentioned in the pressure transducer section, the Pressure Control system can be con

fi

 gured to operate in one 

of three pressure ranges. Changing the range to better match your system’s actual pressure range can make the 
systems pressure changes more accurate and can prevent errors in the transducer’s readings.

To change the pressure range you must make adjustments to both the pressure transducer and to the setpoint 
controller.
 

•  In the pressure transducer, choose which one of the three ranges best suits your system. Slide the 

 

 

corresponding switch to the ON position and make sure all other switches are in the OFF position.

 

• 

In the setpoint control, enter the programming menu and scroll to parameter “c16.” Change the value to 

 

 

that which corresponds to the range you chose for the pressure transducer in the table above. Exit the 

 

 

programming menu to save the setting.

Reverse/Direct acting mode:

The pressure control system is capable of maintaining negative or positive pressure in a duct system. The typical 
application is a negative duct pressure as monitored at the inlet of an exhaust fan. An application where positive 
duct pressure may be experienced would be at the outlet side of a fan. 
 

• 

For systems operating with a Negative duct pressure, the setpoint controller must be in “Reverse Acting” 

 

 

mode. This mode is active when a           appears on the display. This mode is active when shipped from 

 

 

the factory. To activate reverse acting mode, enter the programming menu and scroll to “c0.” Change 

 

 

the value to 2, and then exit to save the change.

 

•  For systems operating with a Positive duct pressure, the setpoint controller must be in “Direct Acting” 

 

 

mode. This mode is active when a          appears on the display. This mode is not active when shipped 

 

 

from the factory. To activate direct acting mode, enter the programming menu and scroll to “c0.” Change 

 

 

the value to 1, and then exit to save the change.

Summary of Contents for ASX-31003-C

Page 1: ... NOTE The ACU can be used to manually control the output of the motor independently from the rest of the pressure control system This is beneficial for system balancing as well as for fine tuning of the setpoint control system Refer to the ASX ECM ACU Control Specification Sheet for details on how to operate the ACU controller A direct drive ASX fan with Eco Drive motor and Automation Control Unit...

Page 2: ...hat the tube is perpendicular to the airstream Attach flexible tubing to the outlet of the pressure tap Follow any applicable codes or requirements when choosing a flexible tube to use Pressure Transducer The purpose of the pressure transducer is to translate the duct pressure reading from the static pressure tap into a 0 10VDC signal The transducer can be field configured to operate within three ...

Page 3: ...his is intended to aide in the system balancing process More details on how to utilize the startup mode can be found in the ACU Control Specification Sheet If you wish to get the ACU out of startup mode simply power cycle the ACU 5 times while there is a positive voltage between 0 1 and 10 VDC present across the Signal and Common tabs Setpoint Control The purpose of the Setpoint control is to rece...

Page 4: ...er a passcode To access the Programming menu press and hold both the Prg muteand the Setbuttons until a 0 appears on the display Next press the arrow until the number 77 is displayed Finally press the Set key to enter the Programming menu By pressing the or arrows you can scroll through all of the parameters that are in the programming menu Pressing the Set button will allow you to enter and chang...

Page 5: ... for the pressure transducer in the table above Exit the programming menu to save the setting Reverse Direct acting mode The pressure control system is capable of maintaining negative or positive pressure in a duct system The typical application is a negative duct pressure as monitored at the inlet of an exhaust fan An application where positive duct pressure may be experienced would be at the out...

Reviews: