Oil Class 2 

In each cubic metre of compressed air, not more than 0.1mg of oil is allowed. This is a total level for liquid oil, 
oil aerosol and oil vapour. 
When an inert gas is being used to supply the purge system, risk of asphyxiation exists. Refer to Application 
Suitability section. 
Before connection of the air supply to the purge system, the supply pipe work should be flushed through 
with instrument quality air to remove any debris that may remain in the pipes. This must be carried out for at 
least 10 seconds for every meter of supply pipe. 
Unless a supply shut-off valve has been fitted to the air isolation unit

 

system, an external shut-off valve with 

the same, or larger, thread size as the Control Unit inlet fitting should be fitted by the installer to prevent any 
restriction of purge flow. 
The purge air from the air isolation unit

 

should be piped within the pressurized enclosure to ensure 

purging of potential dead air spots. 
The purge system is fitted with an internal regulator factory set to 3 bar feeding the logic. 
 
When an inert gas is being used to supply the air isolation unit, risk of asphyxiation exists. Refer to Application 
Suitability section. Before connecting the air supply to the Air supply isolator, the supply pipe work should be 
flushed through with instrument quality air to remove any debris that may remain in the pipes. This must be 
carried out for at least 10 seconds for every metre of supply pipe. 
 

Instrument Air Quality 

Solid Particles 0.5 μm < particle size ≤ 1 μm, maximum 1000 particles / m3 
Residual Water 1μm maximum density, +3

o

C* pressure dewpoint 

Oil Content ≤ 0.01 mg / m3 concentration total oil 

 

 

Summary of Contents for ML576

Page 1: ...s apply only to the Pressurizing system It is the responsibility of the manufacturer of the Pressurized Motor Enclosure to provide appropriate instructions for the Enclosure Contents 1 ASU 0000 009 Ge...

Page 2: ......

Page 3: ...installed by a competent engineer in accordance with relevant standards and any local codes or practice Ensure the system is installed according to the full instructions in the Installation of the Sys...

Page 4: ...both small two way valves located at the bottom of each filter should be normally closed 5 Main Components Air Supply Filter The unit is provided with x2 40 liquid dust filter elements The user of th...

Page 5: ...r isolation unit system an external shut off valve with the same or larger thread size as the Control Unit inlet fitting should be fitted by the installer to prevent any restriction of purge flow The...

Page 6: ...llowing checks are also recommended at that time Check the condition of the air supply filter element Clean or replace it as necessary At least every two years the following additional checks are reco...

Page 7: ...re Copyright Expo Technologies Limited They are to be treated as confidential and are returnable upon request They are not to be copied or communicated in part or in whole without written consent from...

Page 8: ...KET 1 23 S0015 018 PRESURE GAUGE 2 24 HTS A200 803 2 S STEEL PIPE THREAD BOTH ENDS 1 25 RLCI 04025 J NUTSERT CLOSED M4 9 26 HF1 A01N 006 2 INCH FILTER 2 27 TPE 106M 0P0 STUD ELBOW 1 8 BSPT x 6 OD PUSH...

Page 9: ...This Page Intentionally Left Blank...

Page 10: ...This Page Intentionally Left Blank...

Page 11: ...This Page Intentionally Left Blank...

Page 12: ...Technologies UK Expo Technologies Ltd Unit 2 The Summit Hanworth Road Sunbury On Thames TW16 5DB UK T 44 20 8398 8011 F 44 20 8398 8014 E sales expoworldwide com Expo Technologies China Qingdao Expo...

Reviews: