For large battery banks that have more than 4 batteries, or have multiple strings configurations, the circuit protection
(fuses or circuit breakers) should be installed close to the battery bank’s positive terminal of each string before
connecting to the common bus bar. The fuse rating is based on the maximum continuous discharge rate of each string
of the battery bank. For instance, if the maximum continuous discharge rate of two strings of parallel-connected batteries
is 800 A with 400 Ah on each string, the battery bank should be paired with a 400 A DC fuse on each string. The cables
connecting the two strings to the inverter must be sized properly for the maximum 800 A current.