6. Maintenance and troubleshooting 

6.1 Maintenance intervals

The 

exodraft

 Grease Fan is designed for prolonged use.

 

For dirty or grease-laden exhaust, inspect the

 

impeller after (3) 

months and set up a periodic inspection based on these findings.

 

Clean as required.

The fan motors are equipped with permanently lubricated sealed ball bearings.

 

They require no lubrication.

6.2 Cleaning

 

WARNING

Do not open the motor housing unless power to 

the grease fan has been disconnected

 

y

Loosen the two Phillips screws in the front of the unit.

 

y

Tilt the top of the fan by lifting on the handle.

 

Make

 

sure the 

locking arm holds the top of the fan

 

before letting go. 

 

y

If necessary, use grease remover and a high-pressure

 

cleaner 

to clean the impeller and the inside fan

 

base.

 

 

y

A scraper may also be used.

CAUTION

Never place hands or fingers on top of fan base when closing.

6.3 Troubleshooting

Problem

Possible Cause

What to do

The fan is not operating.

No power to the fan.

Check the power supply wires in the junction box by the fan.

Check the circuit breaker.

Check that the fan is actually turned ON. 

The fan is not running at full 

speed and/or is humming.

The capacitor is improperly connected 

or not connected at all (single-phase 

fans only).

Check the connections inside the junction box.

 

The capacitor must be 

installed according to wiring diagram.

The fan is rotating backwards 

(RSV 400/450 only).

Phase sequence in the power to the fan 

is reversed.

Swap two phases in the junction box.

The fan is vibrating vigorously. The motor shaft is damaged.

Foreign matter or grease buildup on 
vane

Turn the power off immediately.

 

Open the fan and check if the shaft 

is straight.

 

If not, contact ENERVEX at [email protected] or at tel.: 

1-800.255.2923.

Turn off the power and remove the foreign article/clean the fan.

The fan is noisy.

A transportation device has not been 

removed.

Foreign matter is stuck in the fan.

A ball bearing is damaged.

Remove the transportation device.

Turn off the power and remove the foreign article.

Turn off the power.

 

Wait for the motor to stop revolving.

 

Spin the wheel and 

listen for any grinding noise from the motor.

 

If necessary, replace bearing.

The fan stops in the middle of 

a firing cycle.

The motor is overheating.

Check the flue gas temperature below the fan.

 

The temperature should 

not exceed 400°F during continuous operation.

 

Call ENERVEX at tel.: 

1-800.255.2923..

3001391_US_Grease_Fan_GSV200-450_171114

10

 • 

US

Summary of Contents for GSV 200

Page 1: ...A CAN Product information Chapters 1 2 Mechanical installation Chapter 3 Electrical installation Chapter 4 Start up and configuration Chapter 5 Maintenance and troubleshooting Chapter 6 READ AND SAVE...

Page 2: ...s guidelines and safety standards such as those published by the National Fire Protection Association NFPA and the American Society for Heating Refrig eration and Air Conditioning Engineers ASHRAE an...

Page 3: ...bearings and is maintenance free Listings Installations must conform to the requirements of the authority having jurisdiction Where required by the author ity having jurisdiction the installation must...

Page 4: ...rranty We promise the original user that we will replace or repair as we may elect any part or parts of the new RS Chimney Fan which are defective in material or workmanship without charge for parts a...

Page 5: ...ngs kW 0 10 0 16 0 35 0 75 1 5 0 15 0 2 0 5 1 0 2 0 Weight lbs 47 60 92 127 155 kg 18 26 42 58 70 Dimensions A in 11 03 13 20 16 94 16 94 23 23 mm 280 335 430 430 590 B x B in 15 37 19 11 25 61 25 61...

Page 6: ...es in the bottom with lag bolts or self tapping sheet metal screws one at each corner y y Check the gasket to insure that it forms a complete seal CAUTION Never place hands or fingers on top of fan ba...

Page 7: ...below shows how the fan is connected to the fan speed control and the power source see fig 6 Use a 2 conductor wire of min 14 AWG with ground Wiring must be run outside the duct but can be run between...

Page 8: ...be run outside the duct but can run between the duct and the roof curb If variable speed is required a variable frequency drive VFD can be used This will eliminate the need for a magnetic starter as s...

Page 9: ...motor nameplate rating y y Check that the transport securing device holding the motor shaft and impeller in place has been removed y y Determine if the impeller is free and has not been subject to mi...

Page 10: ...ot running at full speed and or is humming The capacitor is improperly connected or not connected at all single phase fans only Check the connections inside the junction box The capacitor must be inst...