INSTALLATION INSTRUCTIONS FOR
NEW YORK APPROVED RECESSED EDGE-LIT LED EXIT SIGN
WITH BATTERY BACKUP
6. Slide the trim plate through the EXIT PANEL and connect the two switch wires and place the
LED indicator light inside the hole (Figure G). Screw the plate to the unit.
7. Remove the protective films from the exit panel (Figure H).
STEP TWO:
Making the electrical connection
1. Remove the junction box cover on the top of the unit (Figure J).
2. Remove knock out and install conduit connector in the J-Box (Figure K).
3. Connect bi-pin plug for battery wires (Figure L). The unit will turn on at this point.
4. Make the proper electrical AC connection by bringing the supply wires into the J-Box and
connecting them to the proper wires.
(120 Volt: use BLACK for HOT and WHITE for COMMON)
(277 Volt: use RED for HOT and WHITE for COMMON)
5. Replace J-Box cover (Figure J).
ELECTRICAL CONNECTIONS:
WARNING
1. MAKE SURE THAT POWER IS OFF BEFORE MAKING ANY ELECTRICAL CONNECTIONS!
2. UNUSED WIRES MUST BE CAPPED USING ENCLOSED WIRE NUTS.
WHITE: Return for 120VAC or 277VAC wiring
BLACK: Hot lead for 120VAC wiring
RED/ORANGE: Hot lead for 277VAC wiring
GREEN: Equipment ground
Figure G
Figure H
Figure J
Figure K
Figure L