background image

Exhausto-FireDampersKitVEX40T

-Inst-11029950B - 03/2021 - RCS L

yon 956 506 828 - 

Aldes - Imprimé en France/ Printed in France

  

5.  DESCRIPTION OF FUNCTIONS AND SETTINGS • BESKRIVELSE AF FUNKTIONER OG INDSTILLINGER

EN

**This kit requires the VEX40T unit software 1.10 or more recent. 
Please check your software version in the HMI menu INFORMATION 
> Product ID > Software version > Software unit **

This fire dampers box allows the ventilation unit to pilot and 
test regularly one or two fire dampers. This box is not a security 
component. The fire dampers are the only security elements of the
installation. In case of fire dampers activation, the unit will stop 
automatically.
The status of the fire-dampers can be tested regularly and saved in 
the unit history.
Settings available via HMI or can be done with Aldes Configurator. In 
HMI > Installer > Connectivity > Fire Dampers

DA

** Dette kit kræver VEX40T aggregat med software version 1.10 eller 
nyere. Check din software version i HMI-menuen: INFORMATION > 
Produkt-id > Software > SW Ver. VEX40T**

Brandspjæld-kit for VEX40T muliggør regelmæssig afprøvning og 
testning af en eller to brandspjæld via ventilationsaggregatet. Dette 
Brandspjæld-kit er ikke en sikkerhedskomponent. Brandspjældene 
er installationens eneste sikkerhedselementer. Hvis brandspjældene 
aktiveres, vil anlægget automatisk stoppe.
Brandspjældenes status kan testes regelmæssigt og gemmes I 
enhedens historik.
Indstillinger er tilgængelige via HMI eller kan udlæses med Aldes  
Configurator. I HMI:  INSTALLATØR > Tilbehør > Brandspjæld

Settings / Indstillinger

Possible values / Mulige værdier

Number of dampers / Antal spjæld

1 or 2  /1 eller 2

Frequency (in days) / Frekvens (i dage)

7-14-21-28

Hours / Timer 

From 00:00 to 23:59 / Fra 00:00 til 23:59

Day / Dag

Monday to Sunday / Mandag til søndag

6. TEST, STATUS, ERROR AND HISTORIC • TEST, STATUS, FEJL OG HISTORIK

EN

The tests will be performed according to the settings of the 
regulation (factory parameter: every 28 days / on Monday / at 
10:00). 
Or it can be force with the HMI by a qualified worker: 
Installer> Connectivity > Fire-dampers > Test
In case of errors, following codes may appear:

DA

Testene udføres ifølge reguleringsindstillingerne (fabriksindstilling: 
hver 28 dag) / mandag / kl. 10:00). 
Eller kan forceres med HMI'et via Installationsmenu kræver 
password: 
INSTALLATØR > Tilbehør > Brandspjæld > Test
I tilfælde af fejl kan følgende koder blive vist:

Error code

Fejlkode

Description

Beskrivelse

Behaviour of VEX40T

Reaktion på VEX40T

Correction

Korrigerende handling

90

Fire damper test failed 

Brandspjældtest mislykkedes

The unit HMI displays the Error. 

The unit stops working

after 2 min.

HMI-enheden viser fejlen. 

Anlægget stopper

efter 2 min.

Check the fire-dampers, the connection to the 

kit and to the unit. When everything

is conform. Cut the unit power supply and 

restart it. Perform a manual fire damper test to 

check correct function.

Check brandspjældene samt forbindelsen til 

brandspjældboksen og anlægget. Når alt er

korrekt forbundet, afbryd da strømmen 

og genstart anlægget. Udfør en manuel 

brandspjældstest for at kontrollere korrekt 

funktion.

91

Fire damper fault on 1 or 2 fire dampers

Fejl på 1 eller 2 brandspjæld

92

Lost communication between the unit, the box and/or the fire-damper(s)

Ingen kommunikation mellem anlæg, brandspjældsboks og brandspjæld

EN

All test dates and status are stored in the unit historic. To download 
the historic: 

  This operation must be done by trained operators. 

The unit must stay ON during all steps:
- Open the green channel by removing the screw
- Connect a USB stick to VEX40T USB port. The USB stick must be blank
- Wait up to 2 minutes during data log download and remove the USB 
stick 
- Connect the USB stick to your PC and use Aldes Configurator to read the 
.hst file or send it to EXHAUSTO service team.

DA

Alle testdata samt status gemmes i enhedens historik. Download af 
historikken:

 Dette skal udføres af fagpersonale.

Enheden skal forblive TÆNDT under alle trin:
- Åbn den grønne dæksel ved af fjerne skruen
- Tilslut et USB-stik til USB-porten på VEX40T. USB-stikket skal være 
tomt
  - Vent op til 2 minutter mens data log downloades og fjern herefter
  USB-stikket
  - Tilslut USB-stikket til din PC og brug Aldes Configurator for at 
udlæse .hst-filen eller send den til EXHAUSTO Service team. 

7. INSTALLATION RECOMMENDATIONS • 

ANBEFALINGER TIL INSTALLATIONEN

EN

The fire damper box must be fixed on wall and remains accessible  
for maintenance anytime. 
Four screws are necessary to fix the box on the wall adapted to the 
type of wall (not included in the delivery).

DA

Brandspjæld-kit skal monteres på væggen og skal til hver en tid 
være tilgængelig for vedligeholdelse. 
Der kræves fire skruer til fastgørelse af kassen på væggen, tilpasset 
vægtypen (ikke omfattet i leveringsomfanget).