1.4.1 Spatial requirements
The drawing below indicates how much space is needed for servicing, replacing fil-
ters, cleaning, etc.
1550
755
805
RD
1166
5-
01
NB:
A free height of at least 200 mm is required above the unit’s connection box.
1.4.2 Requirements for underlying surface
When fitting the unit directly to an existing surface - i.e. without using the mounting
base (accessory) - the surface must be:
● level
● horizontal (±3 mm per metre
● hard
● vibration-resistant
1.4.3 Requirements for duct system
Silencers
The duct system must be fitted with silencers specified by the Project Manager,
which meet the requirements of the operating area.
Bends
A duct bend may be fitted immediately after the unit, because the airflow in the
spigot has a uniformly moderate speed profile, which results in negligible system
pressure loss.
Insulation
The duct system must be insulated against:
● condensation
● sound leakage
● heating/cooling losses
Condensation
Condensation in the ducts may occur when the exhaust/outdoor air has high hu-
midity. EXHAUSTO recommends a condensation outlet is also fitted at the lowest
point in the ducts.
3005039-2018-01-08
Product information
8/32
Summary of Contents for VEX200 series
Page 23: ...Supply air Supply airflow diagram 3005039 2018 01 08 Maintenance 23 32...
Page 24: ...Extract air Extract airflow diagram 3005039 2018 01 08 Maintenance 24 32...
Page 29: ...3005039 2018 01 08 29 32...
Page 30: ...3005039 2018 01 08 30 32...
Page 31: ...3005039 2018 01 08 31 32...
Page 32: ......