Component
Explanation
M1
Extract air motor
M2
Supply air motor
BP1
Bypass damper motor 1
MC1
Motor control, extract air/exhaust air motor
MC2
Motor control, outdoor air/supply air motor
MPT1
AFC (airflow control)
MPT2
MPTF (pressure drop across filter)
MPT3
DEP (Ice detection in case of pressure drop across counterflow heat
exchanger)
TE1.1
Temperature sensor, extract air
TE1.2
Temperature sensor, exhaust air
TE2.1
Temperature sensor, outdoor air
TE2.2
Supply air temperature sensor
TE-RPT
Temperature sensor in return pipe from water heating coil (internal)
Tice
Temperature sensor for ice in exchanger
2.3.1 Control fuses integrated in VEX 150-160-170 with water heating coil
VEX size
Voltage[V]
Fuse for control sys-
tem (1x230V) 2 pole
Fuse for MC1 (1x230V)
2 pole
Fuse for MC2 (1x230V)
2 pole
VEX150
3 x 400 V+N+PE
C-10A
C-10A
C-10A
VEX160
3 x 400 V+N+PE
C-10A
C-16A
C-16A
VEX170
3 x 400 V+N+PE
C-10A
VEX size
Voltage[V]
Common fuse for MC1 and MC2 (3x400V) 3 pole
Total number of fuses
VEX150
3 x 400 V+N+PE
3
VEX160
3 x 400 V+N+PE
3
VEX170
3 x 400 V+N+PE
C-20A
2
3005760-2017-05-03
Installation of the VEX
13/20