background image

6/16

1

3

2

2.  Installing the Chimney Fan 

Transport Safety Device
 

 

If a transport safety device is present, remove it from the 

 

 

vane and make sure that the vane can revolve without 

 

 

hindrance.

 

 

RS 14/16:  Before mounting, the transport safety device on 

 

 

the hinges must be removed.    

 

 

2.1  Single Fan on Steel Chimney

 

Step 1:   Prepare fan location

 

 

If a stack cap is already installed, it must be removed.  The 

 

 

steel adapter (FRS) slides right into the chimney, where the 

 

 

long collar engagement ensures safe anchoring.  If 

 

 

necessary, the adaptor can be secured by means of long 

 

 

self-tapping stainless steel screws into the side of the collar 

 

 

through the chimney wall.

 

 

Measure the inside diameter of the flue and cut a 

 

 

corresponding hole in the center of the fiber mat.  If the flue is 

 

 

so big that the throat in the adapter has been reduced to fit 

 

 

the throat of the fan, the hole in the fiber mat should 

 

 

correspond to the throat. 

 

 

The aluminum foil on the fiber mat must face upward (against 

 

 

fan base).

 

 

Step 2:  Preparation of fan

 

 

Locate the installation brackets in the grooves on the under

 

 

side of the fan base, using the bolts and nuts supplied to 

 

 

secure the brackets.  Note that the bolts shall be 

 

 

installed from the bottom side in the two inner holes. 

 

 

Adjust the final position of the installation brackets 

 

 

ensuring that there is a small gap between the brackets 

 

 

and the flue wall/adapter throat.  Tighten the nuts.

 

 

If the brackets touch the flue wall, it is likely to create some 

 

 

vibration noise.

 

Step 3:  Attaching the fan

 

 

The chimney fan is now ready for installation on the top of the 

 

 

chimney.  Place the fiber mat with the aluminum foil facing 

 

 

upwards on the top of the adapter, and place the fan on top 

 

 

of the mat.

 

 

If extremely strong winds constantly surround the top of the 

 

 

chimney, the chimney fan must be secured by using two 

 

 

safety wires. 

 

 

Caution:  Under conditions with extremely strong 

 

 

winds constantly surrounding the top of the 

 

 

chimney, the chimney fan must be secured by steel 

 

 

wires or similar.

NorthlineExpress.com

http://www.northlineexpress.com

Toll-Free 1-866-667-8454

Summary of Contents for RS 12

Page 1: ...76 770 587 3238 800 255 2923 Fax 770 587 4731 info exhausto com us exhausto com RS Chimney Fan For Gas Oil Applications CAN Installation Operating Manual USA 3000270 10 01 NorthlineExpress com http ww...

Page 2: ...8 2 6 Installation for high temperatures 8 3 Installing Safety System 3 1 Installing Dwyer Pressure Switch 9 4 Wiring the Chimney Fan 4 1 General 10 4 2 Wiring diagram for solenoid operated gas valve...

Page 3: ...having jurisdiction the installation must also conform to the Standard for Draft Equipment All electrical wiring must be in accordance with the requirements of authority having jurisdiction or in abs...

Page 4: ...1 Hinges 6 Bird Screen Fan Size RS 9 RS 12 RS 14 RS 16 A 10 11 13 16 B 12 14 16 19 C 11 2 5 14 15 4 5 18 D 3 3 3 5 4 4 E 8 1 2 11 1 8 12 3 4 14 3 4 Weight lbs 28 36 46 60 Elec Character 120 1 60 Amps...

Page 5: ...on otherwise improper operation and inadequate venting of deadly flue gases may result Support system for the chimney fan Prior to installation of the chimney fan it must be assured the chimney can sa...

Page 6: ...the fiber mat must face upward against fan base Step 2 Preparation of fan Locate the installation brackets in the grooves on the under side of the fan base using the bolts and nuts supplied to secure...

Page 7: ...de of the fiber mat The aluminum foil on the fiber mat must face upwards against fan base Step 2 Preparation of fan Locate the installation brackets in the grooves on the underside of the fan base usi...

Page 8: ...nd bolt the base onto the wall with the hinges pointing upwards After mounting the base securely attach the fan motor housing by assembling the fan hinges again Seal with silicone all around the fiber...

Page 9: ...of the probe is approximately 2 and if necessary it should be cut back so it is flush with the inner wall of the pipe Attach the probe to the outer pipe wall with the two metal screws Step 4 Connect...

Page 10: ...erential Switch fan proving switch must be wired so they shut down all appliances connected to the chimney Wiring diagrams can be found on the following pages Power requirements for the system depends...

Page 11: ...rruption of the draft causing the draft to fall below the pressure switch set point will open the pressure switch and deactivate the Solenoid Operated Gas Valve 1 The thermostat closes the relay RE 2...

Page 12: ...in the system Check the system for flue gas spillage Mark this setting on the fan speed control cover 5 3 Adjusting the pressure switch setting Remove the snap on cover from the conduit enclosure by...

Page 13: ...s inspected Creosote and other deposits should be removed from the fan blades and the bottom of the motor housing The top of the fan is hinged and can be opened in order to ease the cleaning Warning D...

Page 14: ...14 16 Notes NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Page 15: ...15 16 Notes NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Page 16: ...0 Northmeadow Parkway STE 180 Roswell GA 30076 770 587 3238 800 255 2923 Fax 770 587 4731 info exhausto com us exhausto com Inc NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8...

Reviews: