© 2017 OJ Electronics A/S
Table 1
Modbus actuator
Modbus address
1.
VAV damper, exhaust
1
2.
VAV damper, inlet
2
3.
VAV damper, inlet
3
4.
Cooling valve
4
5.
Heating valve
5
6.
Combination valve
(heating/cooling)
6
7.
6 way valve (heating/cooling)
7
Modbus address and communication parameters are set in Belimo actuators using
the Servicetool ZTH-EU programming unit from Belimo. The Modbus communication
protocol is 38.4 kBaud, 1 start bit, 8 data bits, 2 stop bits and no parity (see example
of ZTH-EU menu settings for VAV actuators in fig. 22). Instructions for setting Modbus
addresses in Belimo actuators can be found at www.belimo.eu.
LED indications “D”
(see figs 3 and 15)
OJ GreenZone™ Module M is equipped with five LEDs, which indicate the status of the
Modbus actuators (see table 2).
Table 2
LED
Off
Flashing
1.
Nothing connected
VAV damper, exhaust = Communication OK
2.
Nothing connected
VAV damper, inlet = Communication OK
3.
Nothing connected
VAV damper, inlet = Communication OK
4.
Nothing connected
Heating valve = Communication OK
5.
Nothing connected
Cooling valve = Communication OK
4 and 5
Combination/6 way valve = Communication OK
NOTE!
• A flashing LED indicates that the actuator is correctly connected and addressed.
• An inactive LED indicates that the actuator is not installed, not connected correctly or
not addressed correctly on the actuator itself.
• LEDs 4 and 5 flashing simultaneously indicates that the actuator on the combination
valve/6 way valve is connected correctly and that Modbus communication is OK.
English / Instruction
OJ GreenZone™ Module M