Installer menu
Temperature
Description
Shown at following
temperature regula-
tions:
● Constant extract
air temperature
● Constant room
temperature
Set summer/winter change
Summer
● Room temperature
Winter
● Supply air temperature
Summer/winter changeover
● Off
● Outdoor air temperature
● Calendar
● Summer
● Winter
Shown if change is:
Outdoor air tempera-
ture
Set change, outside air temperature
● Summer for higher temperature [˚C]
● Winter for lower temperature [˚C]
● Not changed if the temperature is within the sum-
mer/winter limits.
Shown if change is:
Calendar
Set changeover date
● Changeover to summer operation on this date
● Changeover to winter operation on this date
3.1.3 Initial adjustment
Installer menu
Initial adjustment
Description
INITIAL SETTINGS
Lock fan speeds while making manual adjustments to
the VAV damper in the ventilation ducts.
Submenu
Any comments
Setting of time during which fan speeds are locked
at the speed level set in the FIRE menu.
● Set time: hh:mm
The fans are locked at their current speed if the time is
set to any value other than 00:00.
The time automatically counts down.
The lock is deactivated by setting the time to 00:00 and
waiting max. 60 s
3005858-2017-09-28
Installer level
17/52