Menu 3.1.1.1.x - Room temperature regulation, relative
Air setpoint >
Air setpoint,cool >
Temp. setpoint >
Abs. / Rel. >
Cool rel. start >
Cool abs. start >
Heat rel. start >
Heat abs. start >
60
80
21,0
Relativ
1,0
---
-1,0
---
%
%
°c
K
K
3.1.1.1.x xxxxxxx
If
the following will be adjusted....
Maximum room temp. is set to a value low-
er than (Temp. se Cooling rel. start)
but higher than (Temp. se 0.5 K).
Cooling rel. start, automatically ad-
justed to (Maximum room temp. -
Temp. setpoint).
Maximum room temp. is set to a value low-
er than (Temp. se Cooling rel. start)
and less than (Temp. se 0.5 K).
Temp. setpoint automatically (Maxi-
mum room temperature – 0.5 K).And
Cooling rel. start to 0.5 K.
Minimum room temp. is set to a value high-
er than (Temp. se Heating rel. start)
and greater than (Temp. setpoint - 0.5 K).
Heating rel. start, automatically ad-
justed to (Minimum room temp. -
Temp. setpoint).
Minimum room temp. is set to a value high-
er than (Temp. se Heating rel. start)
and less than (Temp. setpoint - 0.5 K).
Temp. setpoint automatically set to
(Minimum room tempe 0.5
K). And Heating rel. start to -0.5 K.
Note for Cooling rel.
start
The absolute min./max. values for Cooling rel. start are from 0.5 K to 5.0 K. If
(Maximum room temperature – Temp. setpoint) is less than 5.0 K, the max. value
for Cooling rel. start is changed to (Maximum room temperature – Temp. setpoint).
Note for Heating rel.
start
The absolute min./max. values for Heating rel. start are from -5.0 K to -0.5 K. If
(Minimum room temp. - Temp. setpoint) is greater than -5.0 K, the max. value for
Heating rel. start is changed to (Minimum room temp. - Temp. setpoint).
Example 1:
No limitation from Minimum and Maximum room temp.: